Schneider Electric

Schneider Electric METSEPM8110 Power quality meter, PowerLogic PM8000, Essential, integrated display, 64MB, 128s/c

(No reviews yet) Write a Review
SKU:
METSEPM8110
MPN:
METSEPM8110
Condition:
New
Web Services:
customizable home page || file upload/download via FTP || file upload/download via SFTP || web server || alarm notification by e-mail || viewing of captured waveform (FTP) || viewing of captured waveform (web) || HTTPS server
Standards:
IEC 62052-11 || IEC 61557-12 || IEC 62053-22 || IEC 62053-24 || IEEE 1588 || IEC 62586-2 || IEC 61326-1
Net Weight:
581 g
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Number Of Inputs:
3 digital 30 V AC || 3 digital 60 V DC
Environmental Disclosure:
ENVPEP1406023EN
Measurement Accuracy:
current +/- 0.1 % || voltage +/- 0.1 % || active energy +/- 0.2 %
Circularity Profile:
ENVEOLI1406023EN
Device Application:
power monitoring || WAGES metering
Operating Altitude:
9842.52 ft (3000 m)
Accuracy Class:
class 0.2S active energy IEC 62053-22 || class 0.2 active energy ANSI C12.20 || class 0.2 active power IEC 61557-12 || class 0.5S reactive energy IEC 62053-24 || class 0.5 power factor IEC 61557-12 || class 0.2 voltage IEC 61557-12 || class 0.2 curre
Sampling Rate:
128 samples/cycle
Sustainable Offer Status:
Green Premium product
Data Recording:
data logs || harmonics logs || waveform logs || min/max of instantaneous values || trending/forecasting || sag and swell logs || sequence of event recording || GPS synchronisation || alarm logs || event logs || time stamping || 10 data recorders
Information Displayed:
voltage || current || frequency || power || energy consumption || harmonic distortion
Variant:
essential
Product Or Component Type:
power meter
Communication Port Support:
ETHERNET || screw terminal block RS485
Memory Capacity:
64 MB
Analogue Input Type:
voltage (impedance 5 MOhm) || current (impedance 0.3 mOhm)
Electromagnetic Compatibility:
electrostatic discharge conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test conforming to IEC 61000-4-4 || surge immunity test confor
Ip Degree Of Protection:
IP54 front: conforming to IEC 60529 || IP30 body: conforming to IEC 60529
Frequency Measurement Range:
42-69 Hz
Display Resolution:
320 x 240 pixels QVGA
Mounting Support:
framework
Power Quality Analysis:
EN 50160 2010 compliance report || IEEE 519 2014 compliance report || up to the 63rd harmonic || harmonic distortion || waveform capture || voltage sag and swell detection || programmablity (logic and math functions) || IEC 62586 power quality m
Communication Service:
NTP time synchronization || SMTP e-mail notification || DHCP || RSTP support || SNMP || PTP time synchronization
Width:
96 mm
Network Frequency:
60 Hz || 50 Hz
Product Name:
PowerLogic PM8000
Eu Rohs Directive:
Compliant with Exemptions
Measurement Current:
50-10000 mA
Ambient Air Temperature For Storage:
-40-85°C
Line Rated Current:
10 A || 5 A || 1 A
Mounting Mode:
flush-mounted
Type Of Measurement:
current total || voltage || frequency || active and reactive power total || apparent power total || power factor total || active and reactive power per phase, rms || apparent power per phase, rms || power factor per phase, rms
China Rohs Regulation:
X
Measurement Voltage:
57-400 V AC 42...69 Hz between phase and neutral || 100-690 V AC 42...69 Hz between phases
Relative Humidity:
5-95 %
Poles Description:
3P || 1P + N || 3P + N
Number Of Outputs:
1 pulse
Communication Port Protocol:
Modbus RTU 115 kbauds - 2-wire || ION 115 kbauds - 2-wire || DNP3 || IEC 61850 || Modbus TCP/IP || Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s || RSTP 801.1d 2004
Range:
PowerLogic
Weight:
581 g
Device Short Name:
PM8110
Rohs Exemption Information:
Yes
[Us] Rated Supply Voltage:
20...60 V DC +/- 10 %
Product Certifications:
CE || cULus || N998
$7,106.39