Schneider Electric METSEPM8143 Power quality meter, PowerLogic PM8000, Essential, transducer, 64MB, 128s/c
SKU:
METSEPM8143
UPC:
MPN:
METSEPM8143
Condition:
New
Communication Service:
SMTP e-mail notification || DHCP || RSTP support || NTP time synchronization || PTP time synchronization
Number Of Inputs:
3 digital 30 V AC || 3 digital 60 V DC
Environmental Disclosure:
ENVPEP1406022EN
Device Short Name:
PM8143
Depth:
90.8 mm
Circularity Profile:
ENVEOLI1406022EN
Communication Network Type:
IPv6 (internet protocol)
Power Consumption In Va:
16 VA 230 V AC
Measurement Accuracy:
current +/- 0.1 % || voltage +/- 0.1 % || active energy +/- 0.2 %
Power Quality Analysis:
EN 50160 2010 compliance report || IEEE 519 2014 compliance report || up to the 63rd harmonic || harmonic distortion || waveform capture || voltage sag and swell detection || programmablity (logic and math functions) || IEC 62586 power quality m
electrostatic discharge conforming to IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test conforming to IEC 61000-4-4 || surge immunity test confor
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Web Services:
customizable home page || file upload/download via FTP || file upload/download via SFTP || web server || alarm notification by e-mail || viewing of captured waveform (FTP) || viewing of captured waveform (web) || HTTPS server
Line Rated Current:
1 A || 10 A || 5 A
Device Application:
WAGES metering || power monitoring
Poles Description:
1P + N || 3P + N || 3P
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Isolation Voltage:
III400-690 V conforming to IEC 61010-1:ed. 3 || III400-690 V conforming to EN 61010-1:ed. 3 || III347-600 V conforming to UL 61010-1:ed. 3 || III347-600 V conforming to CSA C22.2 No 61010-1:ed. 3
Sampling Rate:
128 samples/cycle
Cybersecurity:
password protection || port hardening || enable/disable communication ports || robust security logs || Syslog protocol support
Information Displayed:
voltage || current || frequency || power || energy consumption || harmonic distortion
Data Recording:
harmonics logs || sag and swell logs || GPS synchronisation || time stamping || data logs || trending/forecasting || waveform logs || alarm logs || sequence of event recording || min/max of instantaneous values || event logs || 10 data recorders
Product Name:
PowerLogic PM8000
Weight:
528 g
Network Frequency:
50 Hz || 60 Hz
Display Type:
Without Display
Rohs Exemption Information:
Yes
Analogue Input Type:
voltage (impedance 5 MOhm) || current (impedance 0.3 mOhm)
[Us] Rated Supply Voltage:
90...415 V AC 45...65 Hz +/- 10 % || 110...415 V DC +/- 10 %