Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Pvc Free:
Yes
Eu Rohs Directive:
Compliant with Exemptions
Device Application:
distribution
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Circuit Breaker Application:
HACR rated
[Ics] Rated Service Breaking Capacity:
25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
Country of Origin:
United States
Phase Connection:
ABC
Mounting Height:
9 in
Pollution Degree:
3 IEC 60947-1
Mercury Free:
Yes
Network Frequency:
50/60 Hz
Trip Unit Technology:
electronic, ammeter, MicroLogic 5.0 A, LSI
Quality Labels:
CE
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Mounting Support:
bracket
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Terminal Identifier:
AL800M23K
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Or Component Type:
circuit breaker
Continuous Current Rating:
0.8
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Breaking Capacity:
AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
Weight:
32 lb(US)
Control Type:
toggle
Circularity Profile:
ENVEOLI2206033EN
Quantity Per Set:
1
Sustainable Offer Status:
Green Premium product
Depth:
8.05 in
Line Rated Current:
800-800 A
Mounting Mode:
I-Line bracket)
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Warranty:
18 months
Breaking Capacity Code:
G
Ip Degree Of Protection:
front cover IP40
Range:
PowerPact
Local Signaling:
overload 1 1 LED amber) || 1 flag green) || trip causes 4 trip indicator red)
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Environmental Disclosure:
ENVPEP2206033EN
Length:
25 mm
Trip Unit Name:
MicroLogic 5.0 A
Product Certifications:
UL || CSA || NOM
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Ambient Air Temperature For Operation:
-25-70°C
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Net Weight:
32 lb(US)
$17,739.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Ammeter with a 5.0A trip unit and an LSI function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This PowerPacT P, 800A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.