- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Eu Rohs Directive:
- Compliant
- Length:
- 25 mm
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Ambient Air Temperature For Storage:
- -50-85°C
- Network Frequency:
- 50/60 Hz
- Sustainable Offer Status:
- Green Premium product
- Pvc Free:
- Yes
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Mercury Free:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70°C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Trip Unit Name:
- MicroLogic 6.0 A
- Mounting Mode:
- unit mount busbar)
- Quality Labels:
- CE
- Rohs Exemption Information:
- Yes
- Breaking Capacity Code:
- J
- Poles Description:
- 3P
- Warranty:
- 18 months
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
- Device Application:
- distribution
- Circularity Profile:
- ENVEOLI1407012EN
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Mounting Support:
- busbar
- Depth:
- 8.05 in
- Product Certifications:
- UL || CSA || NOM
- Pollution Degree:
- 3 IEC 60947-1
- Net Weight:
- 32 lb(US)
- Product Name:
- PowerPact P
- Local Signaling:
- overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
- Wire Stripping Length:
- 25 mm
- Continuous Current Rating:
- 0.8
- Product Or Component Type:
- circuit breaker
- Country of Origin:
- United States
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Control Type:
- toggle
- Ip Degree Of Protection:
- front cover IP40
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Terminal Identifier:
- AL800M23K
- Quantity Per Set:
- 1
- Line Rated Current:
- 800-800 A
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2