Schneider Electric

Schneider Electric PJF36080U44A Circuit breaker, PowerPacT P, 800A, 3 pole, 600VAC, 25kA, busbar, Micrologic 6.0A, 80%

(No reviews yet) Write a Review
SKU:
PJF36080U44A
MPN:
PJF36080U44A
Condition:
New
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Eu Rohs Directive:
Compliant
Length:
25 mm
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Ambient Air Temperature For Storage:
-50-85°C
Network Frequency:
50/60 Hz
Sustainable Offer Status:
Green Premium product
Pvc Free:
Yes
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Mercury Free:
Yes
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Ambient Air Temperature For Operation:
-25-70°C
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Trip Unit Technology:
electronic, ammeter, MicroLogic 6.0 A, LSIG
Trip Unit Name:
MicroLogic 6.0 A
Mounting Mode:
unit mount busbar)
Quality Labels:
CE
Rohs Exemption Information:
Yes
Breaking Capacity Code:
J
Poles Description:
3P
Warranty:
18 months
Electrical Connection:
busbar connection, line || busbar connection, load
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Device Application:
distribution
Circularity Profile:
ENVEOLI1407012EN
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Mounting Support:
busbar
Depth:
8.05 in
Product Certifications:
UL || CSA || NOM
Pollution Degree:
3 IEC 60947-1
Net Weight:
32 lb(US)
Product Name:
PowerPact P
Local Signaling:
overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
Wire Stripping Length:
25 mm
Continuous Current Rating:
0.8
Product Or Component Type:
circuit breaker
Country of Origin:
United States
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Control Type:
toggle
Ip Degree Of Protection:
front cover IP40
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Terminal Identifier:
AL800M23K
Quantity Per Set:
1
Line Rated Current:
800-800 A
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
$29,680.50

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Ammeter with a 6.0A trip unit and an LSIG function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has a busbar connection. This PowerPacT P, 800A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.