Schneider Electric

Schneider Electric PJF36100 Circuit breaker, PowerPacT P, 1000A, 3 pole, 600VAC, 25kA, busbar, ET1.0l, 80%

(No reviews yet) Write a Review
SKU:
PJF36100
MPN:
PJF36100
Condition:
New
Terminal Identifier:
AL1200P25K
Pollution Degree:
3 IEC 60947-1
Net Weight:
32 lb(US)
Wire Stripping Length:
30 mm
Product Certifications:
UL || CSA || NOM
Weight:
32 lb(US)
Mounting Mode:
unit mount busbar)
Trip Unit Name:
ET 1.0I
Rohs Exemption Information:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mercury Free:
Yes
Poles Description:
3P
Local Signaling:
1 trip indicator green)
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Length:
30 mm
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Eu Rohs Directive:
Compliant with Exemptions
Product Name:
PowerPact P
Tightening Torque:
50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Range:
PowerPact
Environmental Disclosure:
ENVPEP2206033EN
Country of Origin:
United States
Ambient Air Temperature For Storage:
-50-85°C
Line Rated Current:
1000-1000 A
Mounting Support:
busbar
Awg Gauge:
4 x AWG 3/0...500 kcmil aluminium/copper
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Long Time Pick-Up Adjustment Range:
1 In
Breaking Capacity Code:
J
Sustainable Offer Status:
Green Premium product
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Control Type:
toggle
Pvc Free:
Yes
Electrical Connection:
busbar connection, line || busbar connection, load
Depth:
8.05 in
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Device Application:
distribution
Circularity Profile:
ENVEOLI2206033EN
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Quantity Per Set:
1
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Continuous Current Rating:
0.8
Warranty:
18 months
Network Frequency:
50/60 Hz
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
$30,375.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has an electronic trip unit, ET 1.0I. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has a busbar connection. This PowerPacT P, 1000A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose