Schneider Electric

Schneider Electric PJL36040U63AE1 Circuit breaker, PowerPacT P, 400A, 3 pole, 600VAC, 18kA, lugs, Micrologic 5.0P, 80%, modbus

(No reviews yet) Write a Review
SKU:
PJL36040U63AE1
MPN:
PJL36040U63AE1
Condition:
New
Range:
PowerPact
Warranty:
18 months
Communication Interface:
Modbus
Quantity Per Set:
1
Ambient Air Temperature For Storage:
-50-85°C
Rohs Exemption Information:
Yes
Pvc Free:
Yes
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Circuit Breaker Application:
HACR rated
Country of Origin:
United States
Eu Rohs Directive:
Compliant with Exemptions
Mercury Free:
Yes
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Continuous Current Rating:
0.8
Line Rated Current:
400-400 A
Mounting Support:
lug
Ambient Air Temperature For Operation:
-25-70°C
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Quality Labels:
CE
Accessory / Separate Part Type:
Modbus connecting cable
Control Type:
toggle
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Ip Degree Of Protection:
front cover IP40
Trip Unit Name:
MicroLogic 5.0 P
Breaking Capacity Code:
J
Width:
8.27 in
Circularity Profile:
ENVEOLI2206033EN
Local Signaling:
overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Product Or Component Type:
circuit breaker
Product Certifications:
UL || CSA || NOM
Weight:
32 lb(US)
Terminal Identifier:
AL800M23K
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Net Weight:
32 lb(US)
Environmental Disclosure:
ENVPEP2206033EN
Mounting Mode:
unit mount lug)
Pollution Degree:
3 IEC 60947-1
Trip Unit Technology:
electronic, power, MicroLogic 5.0 P, LSI
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
Length:
25 mm
Wire Stripping Length:
25 mm
Poles Description:
3P
Device Application:
distribution
$22,332.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Power with a 5.0P trip unit and an LSI function with Modbus communications. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 400A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.