Schneider Electric

Schneider Electric PJL36060CU44A Circuit breaker, PowerPacT P, 600A, 3 pole, 600VAC, 25kA, lugs, Micrologic 6.0A, 100%

(No reviews yet) Write a Review
SKU:
PJL36060CU44A
MPN:
PJL36060CU44A
Condition:
New
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Environmental Disclosure:
ENVPEP2206033EN
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Poles Description:
3P
Depth:
8.05 in
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Range:
PowerPact
Length:
25 mm
Continuous Current Rating:
1
Eu Rohs Directive:
Compliant with Exemptions
Pollution Degree:
3 IEC 60947-1
Breaking Capacity Code:
J
Country of Origin:
Italy
Electrical Connection:
lugs, line || lugs, load
Circuit Breaker Application:
HACR rated
Device Application:
distribution
Quality Labels:
CE
Net Weight:
32 lb(US)
Ambient Air Temperature For Storage:
-50-85°C
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Quantity Per Set:
1
Ambient Air Temperature For Operation:
-25-70°C
Control Type:
toggle
Ip Degree Of Protection:
front cover IP40
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Warranty:
18 months
Product Name:
PowerPact P
Weight:
32 lb(US)
Awg Gauge:
3 x AWG 3/0...500 kcmil aluminium/copper
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Network Frequency:
50/60 Hz
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Rohs Exemption Information:
Yes
Mounting Mode:
unit mount lug)
Mounting Support:
lug
Terminal Identifier:
AL800M23K
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Local Signaling:
overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
Trip Unit Name:
MicroLogic 6.0 A
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Wire Stripping Length:
25 mm
Line Rated Current:
600-600 A
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
Sustainable Offer Status:
Green Premium product
$26,849.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Ammeter with a 6.0A trip unit and an LSIG function. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 600A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 100%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose