- Quantity Per Set:
- 1
- Electrical Connection:
- lugs, line || lugs, load
- Mounting Mode:
- unit mount lug)
- Ambient Air Temperature For Operation:
- -25-70°C
- Length:
- 25 mm
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Continuous Current Rating:
- 0.8
- Pollution Degree:
- 3 IEC 60947-1
- Net Weight:
- 32 lb(US)
- Sustainable Offer Status:
- Green Premium product
- Rohs Exemption Information:
- Yes
- Control Type:
- toggle
- Ambient Air Temperature For Storage:
- -50-85°C
- Circuit Breaker Application:
- HACR rated
- Mounting Support:
- lug
- Poles Description:
- 3P
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Depth:
- 8.05 in
- Network Frequency:
- 50/60 Hz
- Range:
- PowerPact
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Product Name:
- PowerPact P
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Line Rated Current:
- 600-600 A
- Terminal Identifier:
- AL800M23K
- Circularity Profile:
- ENVEOLI1407012EN
- Local Signaling:
- overload 1 trip indicator green) || 1 trip indicator green) || trip causes 1 trip indicator green)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Country of Origin:
- United States
- Product Certifications:
- UL || CSA || NOM
- Environmental Disclosure:
- ENVPEP1407012EN
- Quality Labels:
- CE
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 5.0 A, LSI
- Tightening Torque:
- 50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Warranty:
- 18 months
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Wire Stripping Length:
- 25 mm
- Product Or Component Type:
- circuit breaker
- Pvc Free:
- Yes
- Weight:
- 32 lb(US)
- Breaking Capacity Code:
- J
- Awg Gauge:
- 3 x AWG 3/0...500 kcmil aluminium/copper
- Eu Rohs Directive:
- Compliant
- Mercury Free:
- Yes
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)