Schneider Electric

Schneider Electric PJL36080U64AE1 Circuit breaker, PowerPacT P, 800A, 3 pole, 600VAC, 25kA, lugs, Micrologic 6.0P, 80%, modbus

(No reviews yet) Write a Review
SKU:
PJL36080U64AE1
MPN:
PJL36080U64AE1
Condition:
New
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Local Signaling:
overload 1 1 LED amber) || 1 flag green) || trip causes 4 trip indicator red)
Product Name:
PowerPact P
Circuit Breaker Application:
HACR rated
Number Of Slots:
2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
Continuous Current Rating:
0.8
Country of Origin:
Italy
Device Application:
distribution
Tightening Torque:
50-50 N.m 95-240 mm² (3 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
Ambient Air Temperature For Operation:
-25-70°C
Sustainable Offer Status:
Green Premium product
Product Certifications:
UL || CSA || NOM
Pollution Degree:
3 IEC 60947-1
Range:
PowerPact
[Ics] Rated Service Breaking Capacity:
35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
California Proposition 65:
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
Eu Rohs Directive:
Compliant
Trip Unit Name:
MicroLogic 6.0 P
[Uimp] Rated Impulse Withstand Voltage:
8 kV IEC 60947-2
Communication Interface:
Modbus
[Ui] Rated Insulation Voltage:
750 V IEC 60947-2
Ambient Air Temperature For Storage:
-50-85°C
Network Frequency:
50/60 Hz
Accessory / Separate Part Type:
Modbus connecting cable
Weight:
32 lb(US)
Quantity Per Set:
1
Circularity Profile:
ENVEOLI1407012EN
Line Rated Current:
800-800 A
Mercury Free:
Yes
Wire Stripping Length:
25 mm
Mounting Mode:
unit mount lug)
[Ue] Rated Operational Voltage:
600 V AC 50/60 Hz UL 489
Pvc Free:
Yes
Ip Degree Of Protection:
front cover IP40
Breaking Capacity:
AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
Standards:
UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
Warranty:
18 months
Long Time Pick-Up Adjustment Range:
0.4...1 x Ir
Net Weight:
32 lb(US)
Mounting Support:
lug
Quality Labels:
CE
Control Type:
toggle
Operating Altitude:
< 6561.68 ft (2000 m) without derating || 13123.36 ft (4000 m) with derating
Poles Description:
3P
Trip Unit Technology:
electronic, power, MicroLogic 6.0 P, LSI
Environmental Disclosure:
ENVPEP1407012EN
$23,414.00

Description

PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units. Micrologic trip units can be interchanged in the field to allow for maximum flexibility; the basic electronic trip unit doesn't have that interchangeability. This circuit breaker has a Micrologic Interchangeable Power with a 6.0P trip unit and an LSIG function with Modbus communications. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT P circuit breakers are available in 2, 3, and 4-pole unit mount, I-Line, or drawout construction. This unit has lugs on both the line and load sides. This PowerPacT P, 800A, 3 pole, circuit breaker has an interrupting rating of 25kA at 600VAC. This circuit breaker has a continuous current rating of 80%. PowerPacT P circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
View AllClose