Schneider Electric SDSA3650D Surge protection device, Surgelogic, 40kA, 600 VAC delta, 3 phase, 4 wire, NEMA 4X
Schneider Electric
$257.92
Square D™ load center surge protective devices, SDSA3650D, are easy to install plug-in units that install as quickly as a standard circuit breaker. The surge suppressors use two pole spaces in a QO™ or Homeline™ load center, or NQ panelboard. US and Canadian UL® Listed as Type 2 SPD to the UL 1449 standard. Complies with requirements of NEC® Article 285, CSA 233.1-87, and CSA C22.2 No. 8- M1986 as appropriate.
- Length:
- 24 in
- [Uc] Maximum Continuous Operating Voltage:
- 1020 V
- Short-Circuit Protection:
- 200 kA
- Cable Length:
- 24 in
- Local Signaling:
- status LED green normal operation
- Eu Rohs Directive:
- Compliant with Exemptions
- Nema Degree Of Protection:
- NEMA 4X
- Range Of Product:
- Surgelogic
- Product Or Component Type:
- surge protection device
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Enclosure Material:
- Black Plastic
- Ambient Air Temperature For Operation:
- 65-65°C
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ue] Rated Operational Voltage:
- 600 V delta AC
- Surge Current:
- 40 kA per phase
- Rohs Exemption Information:
- Yes
- Phase:
- 3 phase
- Nominal Discharge Current:
- 10 kA
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Country of Origin:
- Mexico
- Warranty:
- 18 months
- Standards:
- UL 1449:ed. 4: type I || NEC 285: type I || CSA C22.2 No 8
- Depth:
- 3.4 in
- Wiring Configuration:
- 3-wire