Schneider Electric SSD1A320M7C1 DIN rail mount relay, Harmony Solid State Relays, 20A, zeroVoltage switching, input 90…280V AC/DC, output 48...600V AC
Schneider Electric
$65.03
This solid state DIN rail mounted relay belongs to the Schneider Electric Harmony solid state relays range. This electrical relay mounts on 35mm DIN rail and comes with a secure mounting latch. This is a 20A power rated relay with relay type configuration and zero voltage switching. This single-phase relay has a IP20 built-in heat sink and a built-in transient overvoltage protection. It is controlled with a 90Vdc/Vac to 280Vdc/Vac input, has a rated load voltage of 48Vac to 600Vac. It also has a LED input voltage status indicator and clip-in legend for easy identification. It weighs 0.298Kg and its dimensions are, 22.5mm wide, 116.6mm deep, 93.2mm high. It is the ideal solution for packaging, plastic molding, textile, and heating furnace applications. This relay conforms to international standards like EN/IEC 60068, IEC 61373, UL 508, CSA C22.2 No 14-13 and certifications like UL and CSA. Besides the existing standard screw connection for input and output, SSD provides more wiring options like the spring or screw pluggable input connectors, and telescopic or clamp cage output terminals.
- Weight:
- 0.298 kg
- Insulation Resistance:
- 1000 MOhm at 500 V DC
- Maximum I²T For Fusing:
- 409 A².s for 10 ms || 375 A².s for 8.33 ms
- Rohs Exemption Information:
- Yes
- Height:
- 93.2 mm
- Phase:
- 1 phase
- Flame Retardance:
- V-0 conforming to UL 94
- Net Weight:
- 0.298 kg
- Load Current:
- 0.1-20 A
- Input Current Limits:
- 6-10 mA
- Shock Resistance:
- 50 gn for 11 ms (peak acceleration) , longitudinal position conforming to IEC 60068-2-27 || 30 gn for 11 ms (peak acceleration) , vertical position conforming to IEC 60068-2-27
- Absolute Maximum Voltage:
- 1200 V
- Control Type:
- without test button
- Range Of Product:
- Harmony Solid State Relays
- Maximum Leakage Current:
- 1 mA off-state
- Ambient Air Temperature For Operation:
- -40-80°C
- Line Rated Current:
- 20 A
- Vibration Resistance:
- 0.75 mm (f = 10-150 Hz) conforming to IEC 60068-2-6
- Response Time:
- 20 ms (turn-on) || 30 ms (turn-off)
- Product Configuration Type:
- relay configuration
- Electromagnetic Compatibility:
- electrostatic discharge 6 kV criteria A contact discharge conforming to IEC 61000-4-2 || electrostatic discharge 8 kV criteria A air discharge conforming to IEC 61000-4-2 || conducted RF disturbances 10 V, 0.15...80 MHz criteria A level 3 conforming
- Ambient Air Temperature For Storage:
- -40-100°C
- Output Switching Mode:
- zero voltage switching
- Device Short Name:
- SSD1
- Contact Form:
- Form 5 semiconductor output DOL contactor
- Minimum Switching Voltage:
- 90 V AC/DC turn-on
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Standards:
- IEC 61373:class B: category 1 || IEC 60947-4-3 || IEC 62314 || IEC 60950-1 || CSA C22.2 No 14-13 || UL 508
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Rated Duty:
- uninterrupted
- Dielectric Strength:
- 4 kV AC for input/output circuit || 4 kV AC for input or output to case
- Coordination Type:
- type 1 || type 2
- Output Voltage:
- 48...600 V AC
- Overvoltage Category:
- III
- Inrush Current:
- 300 A at 60 Hz
- Product Or Component Type:
- modular DIN rail relay
- Power Factor:
- 0.5 with maximum load
- Mercury Free:
- Yes
- Maximum Voltage Drop:
- <1.3 V on-state
- Solid State Output Type:
- zero voltage switching
- Network Frequency:
- 47...440 Hz
- [Uc] Control Circuit Voltage:
- 90...280 V AC/DC
- Maximum Switching Voltage:
- 5 V AC/DC turn-off
- Country of Origin:
- United States
- Connections - Terminals:
- screw terminals, clamping connection capacity:1...4 mm², AWG 18...AWG 12 for input || screw terminals, clamping connection capacity:1...6 mm², AWG 18...AWG 10 for output
- Ip Degree Of Protection:
- IP20
- Tightening Torque:
- 1.5...1.7 N.m for control input || 13...15 lb.in for control input || 1.5...1.7 N.m for load output || 13...15 lb.in for load output
- Local Signaling:
- for control voltage LED (green)