Schneider Electric

Schneider Electric SSP02EMA12F Surge protection device, Surgelogic, 120kA, 208Y/120 VAC, 3 phase, 4 wire, NEMA 1, enhanced filter

(No reviews yet) Write a Review
SKU:
SSP02EMA12F
MPN:
SSP02EMA12F
Condition:
New
Depth:
135 mm
Phase:
3 phase
Rohs Exemption Information:
Yes
Surge Current:
120 kA
Country of Origin:
Mexico
Nominal Discharge Current:
20 kA
Nema Degree Of Protection:
NEMA 1
Enclosure Material:
Gray painted sheet steel
Short-Circuit Protection:
200 kA
Device Short Name:
EMA
Standards:
CSA C22.2 No 8 || UL 1449:ed. 4 || UL 1283:ed. 5
Cable Length:
483 mm
Local Signaling:
status LED green per phase normal operation || status LED red per phase fault
Mercury Free:
Yes
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Uc] Maximum Continuous Operating Voltage:
150 V
Range Of Product:
Surgelogic
Ambient Air Temperature For Operation:
65-65°C
Wiring Configuration:
4-wire
Provided Equipment:
alarm enable/disable switch || surge counter || sine wave tracking module || dry contacts
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
[Ue] Rated Operational Voltage:
208Y/120 V AC
Connections - Terminals:
lugs AWG 10...AWG 2 copper 4 N.m
Length:
483 mm
Eu Rohs Directive:
Compliant with Exemptions
Device Mounting:
surface
Product Or Component Type:
surge protection device
$5,124.30

Description

Surgelogicâ„¢ Type EMA Series surge protective devices deliver specification grade performance for service entrance or critical branch panel applications. These multi-phase surge suppression systems provide transient suppression, noise filtration in a durable modular package. They provide better performance with a diagnostic interface with push to test switches, red and green status LEDs, module status LEDs per mode, dry contacts, audible alarm with disable switch, and a surge counter. It has 10 year product warranty.