- Range:
- TeSys
- Connections - Terminals:
- screw-clamp terminals 1 1-4 mm² AWG 16...AWG 12)rigid || screw-clamp terminals 2 1-4 mm² AWG 16...AWG 12)rigid || screw-clamp terminals 1 1.5-4 mm² AWG 16...AWG 12)flexible without cable end || screw-clamp terminals 2 1.5-4 mm² AWG 16...AWG 12
- Operating Time:
- < 100 ms closing || < 30 ms opening
- Protective Treatment:
- TC
- Metering Type:
- time device ON || time device switch ON || number of faults || number of switching cycles || number of device power cycles || average current Iavg || average voltage Vavg || max current Imax || max voltage Vmax || active and reactive power with volta
- Fire Resistance:
- 960°C UL 94 || 850°C IEC 60695-2-1 || 650°C IEC 60695-2-12
- Ambient Air Temperature For Operation:
- -10-50°C without derating || 50-60°C with current derating
- Device Short Name:
- TPRSS
- Product Compatibility:
- TPRBC bus coupler || TPRVM voltage interface module || TPRSM SIL interface module
- Mounting Mode:
- horizontal and vertical 35 mm symmetrical DIN rail)
- Power Dissipation In W:
- 3.5 W at Ie AC-3
- Product Name:
- TeSys island
- Width:
- 45 mm
- Utilisation Category:
- AC-1 || AC-2 || AC-3 || AC-4 || AC-3e
- Vibration Resistance:
- 1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
- Electromagnetic Compatibility:
- electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transient immunity test, level 4, 4 kV, conforming to E
- Device Presentation:
- direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
- Irms Rated Making Capacity:
- 250 A at 440 V conforming to IEC 60947
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Product Certifications:
- EAC || UL || CSA || CCC
- Ambient Air Temperature For Storage:
- -25-70°C
- Current Consumption:
- 160 mA contactor sealed || 160 mA contactor closing
- Power Dissipation Per Pole:
- 0.2 W AC-3 - Ith 9 A || 0.56 W AC-1 - Ith 15 A
- Relative Humidity:
- 5-95 %
- Poles Description:
- 3P 3 NO
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947-1
- Function Available:
- upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module || safe stop function available when connected with a TPRSM module
- Safety Function:
- safe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module || safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module
- Local Signaling:
- for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
- [Ui] Rated Insulation Voltage:
- 690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
- Pollution Degree:
- 2
- [Ie] Rated Operational Current:
- 9 A (at <50°C) at <= 440 V AC-3 || 15 A (at <50°C) at <= 440 V AC-1
- [Ue] Rated Operational Voltage:
- <= 690 V AC 47...63 Hz
- Motor Starter Type:
- direct on line
- Protection Type:
- thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || rapid restart lockout || phase sequence || phase loss || phase reversal || phase unbalance || ground current
- Average Impedance:
- 2.5 mOhm - Ith 15 A 50 Hz
- Depth:
- 115 mm
- Country of Origin:
- Mexico
- Standards:
- EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
- Ip Degree Of Protection:
- IP20
- [Ith] Conventional Free Air Thermal Current:
- 15 A (at 50°C)
- Rohs Exemption Information:
- Yes
- Reset:
- remotely or automatically
- Product Or Component Type:
- SIL motor starter
- [Icw] Rated Short-Time Withstand Current:
- 210 A 40°C - 1 s || 105 A 40°C - 10 s || 61 A 40°C - 1 min || 30 A 40°C - 10 min
- Weight:
- 0.656 kg
- Maximum Operating Rate:
- 3600 cyc/mn AC-3
- Eu Rohs Directive:
- Compliant with Exemptions