Schneider Electric

Schneider Electric TPRSS009 SIL motor starter, TeSys island, 15A at AC-1, 9A at AC-3, 4kW, 5hp, DOL type

(No reviews yet) Write a Review
SKU:
TPRSS009
MPN:
TPRSS009
Condition:
New
Range:
TeSys
Connections - Terminals:
screw-clamp terminals 1 1-4 mm² AWG 16...AWG 12)rigid || screw-clamp terminals 2 1-4 mm² AWG 16...AWG 12)rigid || screw-clamp terminals 1 1.5-4 mm² AWG 16...AWG 12)flexible without cable end || screw-clamp terminals 2 1.5-4 mm² AWG 16...AWG 12
Operating Time:
< 100 ms closing || < 30 ms opening
Protective Treatment:
TC
Metering Type:
time device ON || time device switch ON || number of faults || number of switching cycles || number of device power cycles || average current Iavg || average voltage Vavg || max current Imax || max voltage Vmax || active and reactive power with volta
Fire Resistance:
960°C UL 94 || 850°C IEC 60695-2-1 || 650°C IEC 60695-2-12
Ambient Air Temperature For Operation:
-10-50°C without derating || 50-60°C with current derating
Device Short Name:
TPRSS
Product Compatibility:
TPRBC bus coupler || TPRVM voltage interface module || TPRSM SIL interface module
Mounting Mode:
horizontal and vertical 35 mm symmetrical DIN rail)
Power Dissipation In W:
3.5 W at Ie AC-3
Product Name:
TeSys island
Width:
45 mm
Utilisation Category:
AC-1 || AC-2 || AC-3 || AC-4 || AC-3e
Vibration Resistance:
1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
Electromagnetic Compatibility:
electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transient immunity test, level 4, 4 kV, conforming to E
Device Presentation:
direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
Irms Rated Making Capacity:
250 A at 440 V conforming to IEC 60947
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Product Certifications:
EAC || UL || CSA || CCC
Ambient Air Temperature For Storage:
-25-70°C
Current Consumption:
160 mA contactor sealed || 160 mA contactor closing
Power Dissipation Per Pole:
0.2 W AC-3 - Ith 9 A || 0.56 W AC-1 - Ith 15 A
Relative Humidity:
5-95 %
Poles Description:
3P 3 NO
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-1
Function Available:
upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module || safe stop function available when connected with a TPRSM module
Safety Function:
safe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module || safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module
Local Signaling:
for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
[Ui] Rated Insulation Voltage:
690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
Pollution Degree:
2
[Ie] Rated Operational Current:
9 A (at <50°C) at <= 440 V AC-3 || 15 A (at <50°C) at <= 440 V AC-1
[Ue] Rated Operational Voltage:
<= 690 V AC 47...63 Hz
Motor Starter Type:
direct on line
Protection Type:
thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || rapid restart lockout || phase sequence || phase loss || phase reversal || phase unbalance || ground current
Average Impedance:
2.5 mOhm - Ith 15 A 50 Hz
Depth:
115 mm
Country of Origin:
Mexico
Standards:
EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Ip Degree Of Protection:
IP20
[Ith] Conventional Free Air Thermal Current:
15 A (at 50°C)
Rohs Exemption Information:
Yes
Reset:
remotely or automatically
Product Or Component Type:
SIL motor starter
[Icw] Rated Short-Time Withstand Current:
210 A 40°C - 1 s || 105 A 40°C - 10 s || 61 A 40°C - 1 min || 30 A 40°C - 10 min
Weight:
0.656 kg
Maximum Operating Rate:
3600 cyc/mn AC-3
Eu Rohs Directive:
Compliant with Exemptions
$259.00

Description

TeSys island direct SIL starter, 3 poles, 9A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 9A and motors up to 4kW@400V / 5hp@480V. In association with a TPRSM001 module and an external safety device, it can be used for safety related systems conforming to IEC 61508. It provides motor protection functions including thermal overload (setting 0.18-9A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).