Schneider Electric

Schneider Electric TPRSS025 SIL motor starter, TeSys island, 30A at AC-1, 25A at AC-3, 11kW, 15hp, DOL type

(No reviews yet) Write a Review
SKU:
TPRSS025
MPN:
TPRSS025
Condition:
New
Product Or Component Type:
SIL motor starter
Standards:
EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-1
Rohs Exemption Information:
Yes
Connections - Terminals:
screw-clamp terminals 1 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 2 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 1 2.5-10 mm² AWG 14...AWG 8)flexible without cable end || screw-clamp terminals 2 2.5-10 mm² AWG 14...A
Fire Resistance:
960°C UL 94 || 850°C IEC 60695-2-1 || 650°C IEC 60695-2-12
Product Compatibility:
TPRBC bus coupler || TPRVM voltage interface module || TPRSM SIL interface module
Device Short Name:
TPRSS
Country of Origin:
Mexico
Overvoltage Category:
III for Ue <= 480 V || II for Ue <= 690 V
Depth:
115 mm
Device Presentation:
direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
Warranty:
18 months
Poles Description:
3P 3 NO
Vibration Resistance:
1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
Electromagnetic Compatibility:
electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transient immunity test, level 4, 4 kV, conforming to E
Electrical Durability:
1.65 Mcycles 25 A AC-3 440 V || 2 Mcycles 30 A AC-1 440 V
Environmental Disclosure:
ENVPEP1904009EN
Protection Type:
thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || phase sequence || rapid restart lockout || phase reversal || phase loss || phase unbalance || ground current
Irms Rated Making Capacity:
450 A at 440 V conforming to IEC 60947
Operating Time:
< 100 ms closing || < 30 ms opening
Mercury Free:
Yes
Function Available:
upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module || safe stop function available when connected with a TPRSM module
Motor Power Kw:
5.5 kW at 230 V 50 Hz (AC-3) || 11 kW at 380...415 V 50 Hz (AC-3) || 11 kW at 440 V 50 Hz (AC-3) || 15 kW at 500 V 50 Hz (AC-3) || 15 kW at 690 V 50 Hz (AC-3)
Range:
TeSys
Sustainable Offer Status:
Green Premium product
Shock Resistance:
15 gn 11 ms) IEC 60068-2-27
Maximum Operating Rate:
3600 cyc/mn AC-3
Mechanical Durability:
30 Mcycles
Rated Breaking Capacity:
450 A at 440 V conforming to IEC 60947
Safety Function:
safe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module || safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module
Net Weight:
0.718 kg
Relative Humidity:
5-95 %
Average Impedance:
2 mOhm - Ith 30 A 50 Hz
Ambient Air Temperature For Storage:
-25-70°C
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Operating Altitude:
0...6561.68 ft (0...2000 m) without derating
[Uc] Control Circuit Voltage:
24 V DC supplied by the bus coupler
Reset:
remotely or automatically
Thermal Protection Adjustment Range:
0.5-25 A
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Protective Treatment:
TC
Power Dissipation In W:
6.6 W at Ie AC-3
Pollution Degree:
2
Tightening Torque:
2.5-2.5 N.m flat Ø 6 mm || 2.5-2.5 N.m Philips No 3
Product Name:
TeSys island
[Ie] Rated Operational Current:
25 A (at <50°C) at <= 440 V AC-3 || 30 A (at <50°C) at <= 440 V AC-1
[Icw] Rated Short-Time Withstand Current:
380 A 40°C - 1 s || 240 A 40°C - 10 s || 120 A 40°C - 1 min || 50 A 40°C - 10 min
$328.00

Description

TeSys island direct SIL starter, 3 poles, 25A/690V. Connected to a TPRBC bus coupler it controls, protects and monitors loads up to 25A and motors up to 11kW@400V / 15hp@480V. In association with a TPRSM001 module and an external safety device, it can be used for safety related systems conforming to IEC 61508. It provides motor protection functions including thermal overload (setting 0.5-25A, tripping class 5-30), phase loss, phase unbalance and reversal, long start (stall), locked rotor (jam), rapid cycle lockout, ground current detection. Monitoring of the load includes max/average voltages and currents, number of switching cycles, number of faults, active and reactive power/energy when associated to a TPRVM001 voltage module. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
View AllClose