- Electromagnetic Compatibility:
- electrostatic discharge immunity test, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF field immunity test, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transient immunity test, level 4, 4 kV, conforming to E
- [Uc] Control Circuit Voltage:
- 24 V DC supplied by the bus coupler
- Maximum Operating Rate:
- 3600 cyc/mn AC-3
- Sustainable Offer Status:
- Green Premium product
- Mounting Mode:
- horizontal and vertical 35 mm symmetrical DIN rail)
- Protection Type:
- thermal overload protection || motor overheat || overcurrent || undercurrent || jam || long start || stall || rapid cycle lockout || rapid restart lockout || phase sequence || phase reversal || phase loss || phase unbalance || ground current
- Rated Breaking Capacity:
- 550 A at 440 V conforming to IEC 60947
- Motor Starter Type:
- direct on line
- [Ith] Conventional Free Air Thermal Current:
- 40 A (at 50°C)
- Local Signaling:
- for DS (device status) 1 LED (green/red) || for LS (load status) 1 LED (green/red)
- Maximum Horse Power Rating:
- 2 hp at 120 V AC 60 Hz for 1 phase motors || 5 hp at 240 V AC 60 Hz for 1 phase motors || 10 hp at 208 V AC 60 Hz for 3 phase motors || 10 hp at 240 V AC 60 Hz for 3 phase motors || 20 hp at 480 V AC 60 Hz for 3 phase motors || 25 hp at 600 V AC 60 H
- [Ie] Rated Operational Current:
- 38 A (at <50°C) at <= 440 V AC-3 || 40 A (at <50°C) at <= 440 V AC-1
- Product Name:
- TeSys island
- Irms Rated Making Capacity:
- 550 A at 440 V conforming to IEC 60947
- Electrical Durability:
- 1.4 Mcycles 38 A AC-3 440 V || 2 Mcycles 40 A AC-1 440 V
- Device Presentation:
- direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
- Shock Resistance:
- 15 gn 11 ms) IEC 60068-2-27
- Depth:
- 115 mm
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 60947-1
- Warranty:
- 18 months
- Standards:
- EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
- Reset:
- remotely or automatically
- Mechanical Durability:
- 30 Mcycles
- Metering Type:
- time device ON || time device switch ON || number of faults || number of switching cycles || number of device power cycles || average current Iavg || average voltage Vavg || max current Imax || max voltage Vmax || active and reactive power with volta
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- [Ue] Rated Operational Voltage:
- <= 480 V AC 47...63 Hz for overvoltage cat. III || <= 690 V AC 47...63 Hz for overvoltage cat. II
- Mercury Free:
- Yes
- Net Weight:
- 0.718 kg
- Halogen Content Performance:
- Halogen free plastic parts product
- Relative Humidity:
- 5-95 %
- Fire Resistance:
- 960°C UL 94 || 850°C IEC 60695-2-1 || 650°C IEC 60695-2-12
- Vibration Resistance:
- 1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
- Motor Power Kw:
- 9 kW at 230 V 50 Hz (AC-3) || 18.5 kW at 380...415 V 50 Hz (AC-3) || 18.5 kW at 440 V 50 Hz (AC-3) || 18.5 kW at 500 V 50 Hz (AC-3) || 18.5 kW at 690 V 50 Hz (AC-3)
- Range:
- TeSys
- Function Available:
- upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module || safe stop function available when connected with a TPRSM module
- Safety Function:
- safe stop: category 0 conforming to IEC 60204-1 when associated with a TPRSM module || safe stop: category 1 conforming to IEC 60204-1 when associated with a TPRSM module
- Safety Level:
- SIL 2 conforming to IEC 61508 in single channel system architecture || SILCL 2 conforming to IEC 62061 in single channel system architecture || PL = d category 2 conforming to ISO 13849-1 in single channel system architecture
- Thermal Protection Adjustment Range:
- 0.76-38 A
- Ip Degree Of Protection:
- IP20
- Protective Treatment:
- TC
- Safety Reliability Level:
- B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 || B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Product Certifications:
- CSA || EAC || UL || CCC
- Power Dissipation Per Pole:
- 2.9 W AC-3 - Ith 38 A || 3.2 W AC-1 - Ith 40 A
- Circularity Profile:
- ENVEOLI1904009EN
- Ambient Air Temperature For Storage:
- -25-70°C
- Connections - Terminals:
- screw-clamp terminals 1 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 2 1.5-10 mm² AWG 16...AWG 8)rigid || screw-clamp terminals 1 2.5-10 mm² AWG 14...AWG 8)flexible without cable end || screw-clamp terminals 2 2.5-10 mm² AWG 14...A
- [Icw] Rated Short-Time Withstand Current:
- 430 A 40°C - 1 s || 310 A 40°C - 10 s || 150 A 40°C - 1 min || 60 A 40°C - 10 min
- Product Compatibility:
- TPRBC bus coupler || TPRVM voltage interface module || TPRSM SIL interface module