Schneider Electric TPRVM001 Voltage interface module, TeSys island, 690VAC 47-63 Hz, Isolated switching input for safe stop
Schneider Electric
$135.00
TeSys island voltage interface module, 100-690V / 47-63Hz. Connected to a TPRBC bus coupler it measures the mains voltages powering the loads. It provides the voltage values for power and energy calculation, calculates the RMS values and phase sequence. Voltage measurement range 100-690 V +/- 5 %, phase frequency measurement range 47-63 Hz +/- 1 Hz in single phase or 3-phase systems. Mounting on DIN rail together with the other modules of the TeSys island configuration. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
- Weight:
- 0.159 kg
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Function Of Module:
- monitoring of voltages in single phase systems L-N or L-L || monitoring of voltages in 3-phase systems without neutral N connection || calculation of RMS phase voltages, voltage phase sequence, fundamental frequency || identification of dip and swell
- Environmental Disclosure:
- ENVPEP1904009EN
- Product Compatibility:
- TPRBC bus coupler
- Sustainable Offer Status:
- Green Premium product
- Fire Resistance:
- 960°C UL 94
- [Ui] Rated Insulation Voltage:
- 690 V IEC 61010-1
- Device Short Name:
- TPRVM
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Range:
- TeSys
- Shock Resistance:
- 15 gn 11 ms) IEC 60068-2-27
- Ambient Air Temperature For Operation:
- -10-60°C
- Connections - Terminals:
- measuring input removable spring terminal block 3 0.2-2.5 mm² AWG 24...AWG 14)rigid || measuring input removable spring terminal block 3 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || measuring input removable spring terminal block 3 0.2
- Relative Humidity:
- 5-95 %
- Operating Altitude:
- 0...6561.68 ft (0...2000 m) without derating
- Warranty:
- 18 months
- Electromagnetic Compatibility:
- electrostatic discharge, level 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || radiated RF fields, level 3, 10 V/m, conforming to EN/IEC 61000-4-3 || line voltage circuit: fast transients immunity test, level 3, 2 kV, conforming to EN/IE
- California Proposition 65:
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- Depth:
- 114 mm
- Ambient Air Temperature For Storage:
- -25-70°C
- Current Consumption:
- 2 mA
- Power Dissipation In W:
- 0.5 W maximum
- Product Name:
- TeSys island
- Halogen Content Performance:
- Halogen free plastic parts product
- Device Presentation:
- monitoring of the mains voltage powering the island || reporting of the voltage to the bus coupler to enable power & energy monitoring
- Overvoltage Category:
- III
- [Ue] Rated Operational Voltage:
- 690 V AC 47...63 Hz
- Measurement Accuracy:
- voltage +/- 5 %, || frequency +/- 1 Hz,
- Product Certifications:
- UL || CSA || EAC (pending)
- Mounting Mode:
- horizontal and vertical 35 mm symmetrical rail)
- Circularity Profile:
- ENVEOLI1904009EN
- Country of Origin:
- United States
- Local Signaling:
- for DS (device status) 1 LED (green/red) || for VS (voltage status) 1 LED (green/red)
- Rohs Exemption Information:
- Yes
- Width:
- 25 mm
- Standards:
- IEC 61010-2-201 || UL 61010-2-201 || CSA C22.2 No 61010-2-201
- Metering Type:
- phase voltage 100...690 V || phase frequency 47...63 Hz || phase sequence
- Product Or Component Type:
- voltage interface module
- Pollution Degree:
- 2
- [Us] Rated Supply Voltage:
- 24 V DC supplied by the bus coupler
- [Uimp] Rated Impulse Withstand Voltage:
- 6 kV IEC 61010-1
- Protective Treatment:
- TC
- Ip Degree Of Protection:
- IP20
- Net Weight:
- 0.159 kg
- Vibration Resistance:
- 1.5 mm peak to peak 3-13 Hz) IEC 60068-2-6 || 1 gn 13-200 Hz) IEC 60068-2-6
- Eu Rohs Directive: