Schneider Electric VLS3P025R1 Disconnect switch, TeSys VLS, body switch, 25A, 15HP at 480VAC, UL508, three phase, 5kA SCCR, size 1, DIN rail mount
Schneider Electric
$38.30
These TeSys VLS disconnect switches are for integration into control systems in applications like material handling, HVAC, pumping, solar energy, mining and many more. This family of disconnect switches has switches ranging from 16A to 125A. The 16A, 25A, 32A, 40A and 63A disconnect switches are UL508 motor disconnect switches rated. The 30A, 63A, 80A, 100A and 125A disconnect switches are UL98 non fusible disconnect switch rated. This 25A disconnect switch has 3 normally open poles and mounts on DIN rail. Per UL and CSA this this disconnect switch has a 1.5 HP rating at 120 VAC and a 3 HP at 240 VAC single phase. Per UL and CSA this disconnect switch has a 7.5 HP rating at 200 to 208 VAC and 240 VAC, a 15 HP rating at 480 VAC and a 20 HP rating at 600 VAC three phase. Per UL508A this this disconnect switch has up to a 5 kA at 600 V short circuit current rating (SCCR) with a 30A Type RK5 fuse maximum. Per IEC requirements, this disconnect switch has a 11 kW rating at 400 V, a 15 kW rating at 500 V and a 22 kW rating at 690V three phase. The screw clamp terminals will accept 10 mm solid or 16 mm stranded wire. The clamps will also accept solid or stranded wire from 18 AWG to 6 AWG. This disconnect switch is 3.07 inches tall, 1.42 inches wide and 2.95 inches deep. The switch weighs 0.30 lbs. There are many handles and accessories available this TeSys VLS disconnect switch. This TeSys VLS disconnect switch is cULus Listed and meets IEC 60947-3 requirements.
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529
- Tightening Torque:
- power circuit 1.8-2 N.m screw clamp terminals
- Poles Description:
- 3P
- Fixing Mode:
- by clips back
- [Icm] Rated Short-Circuit Making Capacity:
- 1128 A 690 V
- Intermittent Duty Class:
- class 120 - 60 %
- [Ith] Conventional Free Air Thermal Current:
- 25 A (at 55°C)
- Rotary Handle Mounting Style:
- direct
- Contacts Type And Composition:
- 3 NO
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 508
- Ambient Air Temperature For Operation:
- -25-55°C
- Mechanical Durability:
- 100000 cycles
- Handle Front Plate Colour:
- grey
- Mounting Support:
- back DIN rail
- Device Short Name:
- VLS3P
- Compatibility Code:
- VLS
- [Icw] Rated Short-Time Withstand Current:
- 800 A 690 V 1 s
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Control Type:
- rotary handle
- Marking:
- 0 - 1
- Standards:
- UL 508 || CSA C22.2 No 14 || IEC 60947-3
- Suitability For Isolation:
- yes
- Height:
- 75 mm
- Reach Free Of Svhc:
- Yes
- Mercury Free:
- Yes
- Handle Colour:
- black
- Device Composition:
- switch || handle
- Rated Operational Power In W:
- 11 kW 400 V AC-23A) || 15 kW 500 V AC-23A) || 22 kW 690 V AC-23A)
- Eu Rohs Directive:
- Compliant
- Mechanical Robustness:
- vibrations 2...100 Hz Fc 0.7 g) IEC 60068-2-6 || shocks 11 ms Ea 15 gn) IEC 60068-2-27
- Connections - Terminals:
- power circuit screw clamp terminals 10-10 mm² solid || power circuit screw clamp terminals 16-16 mm² flexible - without cable end
- Weight:
- 0.135 kg
- Color:
- Gray
- Net Weight:
- 0.135 kg
- Rotary Handle Padlocking:
- 1 padlock 4-4 mm
- Rated Conditional Short-Circuit Current:
- 50 kA 400 V 25 A gG
- Breaking Capacity:
- 37.5 A 690 V AC-21A) || 75 A 690 V AC-22A) || 200 A 690 V AC-23A)
- Product Name:
- TeSys VARIO LS
- Product Certifications:
- cULus || GL
- Product Or Component Type:
- switch body
- Electrical Durability:
- 100000 cycles AC-21A
- Range:
- TeSys
- Width:
- 36 mm
- Making Capacity:
- 37.5 A 690 V AC-21A || 75 A 690 V AC-22A || 250 A 690 V AC-23A
- Performance Level:
- high performance
- Depth:
- 78 mm
- Toxic Heavy Metal Free:
- Yes
- Country of Origin:
- United States
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- [Ie] Rated Operational Current:
- 25 A Ue: 600 V UL 508 || 25 A AC-21A Ue: 400 V || 25 A AC-21A Ue: 500 V || 25 A AC-21A Ue: 690 V || 25 A AC-22A Ue: 400 V || 25 A AC-22A Ue: 500 V || 25 A AC-22A Ue: 690 V || 25 A AC-23A Ue: 400 V || 25 A AC-23A Ue: 500 V || 25 A AC-23A Ue: 690 V