Schneider Electric VLSA10R1E Disconnect switch, TeSys VLS, auxiliary contact block, one normally closed early break, size 1, DIN rail
Schneider Electric
$33.21
These TeSys VLS disconnect switches are for integration into control systems in applications like material handling, HVAC, pumping, solar energy, mining and many more. This family of disconnect switches has switches ranging from 16A to 125A. The 16A, 25A, 32A, 40A and 63A disconnect switches are UL508 motor disconnect switches rated. The 30A, 63A, 80A, 100A and 125A disconnect switches are UL98 non fusible disconnect switch rated. This auxiliary contact can be added to a VLS3P016R1, VLS3P025R1, VLS3P032R1, VLS3P040R1 or VLS3P063R1 DIN rail mount switch. This auxiliary contact can be mounted on the right or left hand side. This auxiliary contact has one normally open early beak contact. The operational voltage of this auxiliary contact is 600 V. This auxiliary contact block has A600 and Q600 current ratings. The screw clamp terminals will accept 18 AWG to 6 AWG wire. Auxiliary contact module is 3.07 inches tall, 0.47 inches wide and 1.72 inches deep. It weighs 0.08 lbs. This auxiliary contact module is cULus Listed and meets IEC 60947-3 requirements.
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Weight:
- 0.035 kg
- Contact Operation:
- early-break 1 NC
- Tightening Torque:
- control circuit 0.8-1 N.m screw clamp terminals
- Fire Resistance:
- 850°C IEC 60695-2-11
- Connections - Terminals:
- control circuit screw clamp terminals 2.5-2.5 mm² flexible - without cable end
- Ip Degree Of Protection:
- IP20 conforming to IEC 60529
- Rohs Exemption Information:
- Yes
- Minimum Output Current:
- 10 mA
- Mercury Free:
- Yes
- [Ith] Conventional Free Air Thermal Current:
- 10 A (at 55°C)
- [Ithe] Conventional Enclosed Thermal Current:
- 0.416666666666667
- Toxic Heavy Metal Free:
- Yes
- Standards:
- UL 508 || CSA C22.2 No 14 || IEC 60947-1 || IEC 60947-3 || IEC 60947-5
- Eu Rohs Directive:
- Compliant
- Color:
- Gray
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV
- Country of Origin:
- Italy
- Net Weight:
- 0.035 kg
- Product Certifications:
- cULus || GL
- Minimum Output Voltage:
- 5 V
- Range:
- TeSys
- Mechanical Robustness:
- vibrations 2...100 Hz Fc 0.7 g) IEC 60068-2-6 || shocks 11 ms Ea 15 gn) IEC 60068-2-27
- Contacts Type And Composition:
- 1 NC
- Network Frequency:
- 50/60 Hz
- [Ie] Rated Operational Current:
- 6 A AC-15)24 V AC || 6 A AC-15)48 V AC || 6 A AC-15)127 V AC || 3 A AC-15)240 V AC || 3 A DC-13)24 V DC || 1.5 A DC-13)48 V DC || 0.55 A DC-13)127 V DC || 0.27 A DC-13)240 V DC
- Mounting Location:
- right || left
- Ambient Air Temperature For Operation:
- -25-55°C
- Network Type:
- DC || AC
- China Rohs Regulation:
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Range Compatibility:
- TeSys TeSys VARIO LS VLS3P || TeSys TeSys VARIO LS VLS1P
- Device Short Name:
- VLSA
- Product Or Component Type:
- auxiliary contact block
- Depth:
- 46.2 mm
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz
- Reach Free Of Svhc:
- Yes
- Mounting Support:
- DIN rail
- Performance Level:
- high performance