Schneider Electric

Schneider Electric XPSUDN13AP safety module, Harmony XPSU, Cat 4, features 6 x XPSUAF, 24V AC or DC, screw

(No reviews yet) Write a Review
SKU:
XPSUDN13AP
MPN:
XPSUDN13AP
Condition:
New
Rohs Exemption Information:
Yes
Maximum Response Time On Input Open:
20 ms
Power Consumption In Va:
10.5 VA 24 V AC 50/60 Hz
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Relative Humidity:
5-95 % non-condensing
Function Of Module:
emergency stop button with 2 NC contacts || guard monitoring with 1 or 2 limit switches || monitoring 2 PNP sensors || magnetic switch monitoring || light curtain monitoring || RFID switch || monitoring of electro-sensitive protection equipment (ESPE
[Ie] Rated Operational Current:
5 A AC-1 for normally open relay contact || 3 A AC-15 for normally open relay contact || 5 A DC-1 for normally open relay contact || 3 A DC-13 for normally open relay contact || 3 A AC-1 for normally closed relay contact || 1 A AC-15 for normally clo
Weight:
0.350 kg
China Rohs Regulation:
X
Input Protection Type:
internal, electronic
Minimum Output Current:
10 mA relay output
[Us] Rated Supply Voltage:
24 V AC - 15...10 % || 24 V DC - 20...20 %
Environmental Disclosure:
ENVPEP1811003EN
Input Compatibility:
normally closed circuit ISO 14119 || XC limit switch ISO 14119 || mechanical contact ISO 14119 || normally closed circuit ISO 13850 || antivalent pair ISO 14119 || OSSD pair IEC 61496-1-2 || 3-wire proximity sensors PNP
Country of Origin:
Indonesia
[Uimp] Rated Impulse Withstand Voltage:
4 kV II IEC 60947-1
Synchronisation Time Between Inputs:
0.5 s || 2 s || 2.2 s || 4 s
[Ith] Conventional Free Air Thermal Current:
16 A
Number Of Inputs:
6 safety input 24 V DC 5
Power Consumption In W:
4.5 W 24 V DC
Mounting Support:
35 mm symmetrical DIN rail
Safety Module Application:
monitoring antivalent contacts || for emergency stop, guard and light curtain monitoring
Ambient Air Temperature For Storage:
-25-85°C
Net Weight:
0.350 kg
Pvc Free:
Yes
Associated Fuse Rating:
10 A gG NO relay output circuit IEC 60947-1 || 4 A gG NC relay output circuit IEC 60947-1
Ip Degree Of Protection:
IP20 terminals)IEC 60947-1 || IP40 housing)IEC 60947-1 || IP54 mounting area)IEC 60947-1
Mercury Free:
Yes
Depth:
120 mm
Safety Reliability Data:
MTTFd > 30 years ISO 13849-1 || Dcavg >= 99 % ISO 13849-1 || PFHd = 0.88E-09 ISO 13849-1 || HFT = 1 IEC 62061 || PFHd = 0.88E-09 IEC 62061 || SFF > 99% IEC 62061 || HFT = 1 IEC 61508-1 || PFHd = 0.88E-09 IEC 61508-1 || SFF > 99% IEC 61508-1 || type =
Maximum Line Resistance:
500 Ohm
[Ui] Rated Insulation Voltage:
250 V 2)IEC 60947-1
Minimum Output Voltage:
12 V relay output
Safety Level:
can reach PL e/category 4 for normally open relay contact ISO 13849-1 || can reach SILCL 3 for normally open relay contact IEC 62061 || can reach SIL 3 for normally open relay contact IEC 61508 || can reach PL c/category 1 for normally closed relay c
Number Of Outputs:
7 on/off configurable pulsed output
Sustainable Offer Status:
Green Premium product
Product Certifications:
TÃœV || cULus
Ambient Air Temperature For Operation:
-25-50°C at 24 V AC || -25-55°C at 24 V DC
Product Or Component Type:
safety module
Input/Output Type:
semiconductor pulsed diagnostic output 24 V DC, 20 mA Z1, not safety-related
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Standards:
IEC 60947-5-1 || IEC 61508-1 functional safety standard || IEC 61508-2 functional safety standard || IEC 61508-3 functional safety standard || IEC 61508-4 functional safety standard || IEC 61508-5 functional safety standard || IEC 61508-6 functional
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Safety Module Name:
XPSUDN
Connections - Terminals:
removable screw terminal block, 0.2...2.5 mm² solid or flexible || removable screw terminal block, 0.25...2.5 mm² flexible with ferrule single conductor || removable screw terminal block, 0.2...1.5 mm² solid or flexible twin conductor || removable
Electrical Circuit Type:
NC pair || PNP pair || antivalent pair || OSSD pair
$461.64

Description

This safety relay is designed for monitoring Emergency stop, Guard switch, Magnetic switch, Proximity safety switch, PNP sensor, RFID safety switch or safety light curtain. The safety relay is powered with 24V AC/DC, and equipped with a screw removable terminal block. This universal safety module embeds pre-defined safety functions, or selectable safety functions via rotary selectors. This safety relay embeds 6 safety inputs, 7 ON/OFF configurable pulsed outputs, 3 NO, 1 NC safety outputs, and 1 solid-state diagnostic output with complete status information. The maximum safety level achieved by this safety relay is PLe/Category 4 conforming to ISO 13849-1, SILCL 3 conforming to IEC 62061, SIL 3 conforming to IEC 61508. This safety relay weighs 0,350kg. Its dimensions are 45mm (Width) x 120mm (Depth) x 100mm (Height). This safety relay weighs 0,350kg. Its dimensions are 45mm (Width) x 120mm (Depth) x 100mm (Height). This safety relays is suitable for applications such as Food and Beverage, Hoisting, Material Handling, Material Working, Packaging. This safe relay conforms to IEC60947-5-1, IEC61508-1/2/3, ISO13849-1, IEC62061 functional safety standards, is certified by cULus, TÃœV, EAC, CCC and KC marking. Harmony safety relays are compatible with Modicon logic controllers. This relay is mounted on a 35mm symmetrical DIN rail. Harmony XPS Basic and Universal safety relays are the first choice for managing single safety functions easily, typically in machines of simple to medium complexity. Harmony XPS Universal is the first choice for a broad range of simple to mid-complex machines.
View AllClose