4-channel analog input; Resistance measurement; Measurement range: -30 C +150 C
Technical Data
- Number of analog inputs: 4
- Total number of channels (module): 4
- Type of signal: Resistance measurement
- Configurable type of signal: yes
- Sensor connection: 4 x (2-conductor)
- Bit width: 4 x 16-bit data; 4 x 8-bit control/status (optional)
- Resolution (over entire range): 0.1 C
- Measuring error (25 C): 0.5 K in temperature range: -30C ... +150C
- Temperature coefficient: 20 ppm/K
- Measuring current (typ.): 350 A
- Measurement repetition rate (standard): 1.1 s
- Measurement repetition rate (2-channel/2-conductor): 0.63 s
- Response time (max.): 4 s
- Sensor types: Pt1000 (default setting), Ni1000, Ni1000 TK5000, KTY81 110, KTY81 210
- Temperature range: -30 +150 C
- System supply voltage: DC 5 V; via data contacts
- Current consumption, system supply (5 V): 50 mA
- Field supply voltage: DC 24 V (-25 +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Isolation: 500 V system/supply
- Number of incoming power jumper contacts: 2
- Number of outgoing power jumper contacts: 2
Connection Data
- Connection technology: In-/Outputs: 8 x CAGE CLAMP<sup></sup>
- Connection type (1): Inputs/Outputs
- Solid conductor: 0.08 2.5 mm / 28 14 AWG
- Fine-stranded conductor: 0.08 2.5 mm / 28 14 AWG
- Strip length: 8 9 mm / 0.31 0.35 inch
Geometrical Data
- Width: 12 mm / 0.472 inch
- Height: 67.8 mm / 2.669 inch
- Height from upper-edge of DIN-35 rail: 60.6 mm / 2.386 inch
- Depth: 100 mm / 3.937 inch
Mechanical Data
- Type of mounting: DIN-35 rail
Material Data
- Color: light gray
- Housing material: Polycarbonate, polyamide 6.6
- Fire load: 0.000 MJ
- Weight: 49.664 g
- Conformity marking: CE
Environmental Requirements
- Surrounding air (operating) temperature: 0 55 C
- Surrounding air (storage) temperature: -40 85 C
- Protection class: IP20
- Degree of pollution (5): 2 per IEC 61131-2
- Operating altitude: 0 2000 m
- Mounting position: horizontal (standing/lying) or vertical
- Relative air humidity (no condensation): 95 %
- Vibration resistance: acc. to IEC 60068-2-6
- Shock resistance: 15g per IEC 60068-2-27
- EMC immunity to interference: acc. to EN 61000-6-1, EN 61000-6-2
- EMC emission of interference: acc. to EN 61000-6-3
- Exposure to pollutants: Per IEC 60068-2-42 and IEC 60068-2-43
- Permissible H<sub>2</sub>S contaminant concentration at a relative humidity <lt/> 75 %: 10 ppm
- Permissible SO<sub>2</sub> contaminant concentration at a relative humidity <lt/> 75 %: 25 ppm
Commercial data
- Packaging type: BOX
- Country of origin: DE
- GTIN: 4050821419181
- Customs Tariff No.: 85389099990
The WAGO 750 series standard analog input slice module (750-463) features 4 configurable analog inputs for RTD sensors (Pt1000, Ni1000, Thermistor KTY 81) with a 0.1°C resolution. It operates on a 5V DC supply voltage provided by the system and includes spring CAGE CLAMP connections for secure wiring. Designed for DIN-35 rail mounting with a 12mm width, it is rated for ambient temperatures ranging from 0°C to +55°C and has an IP20 protection rating.
- color:
- Light gray
- conformity marking:
- CE
- connection technology inputs outputs:
- 8 x CAGE CLAMP
- connection type 1:
- Inputs/outputs
- country of origin sales organisation germany:
- DE
- data width:
- 4 x 16-bit data: 4 x 8-bit control/status (optional)
- depth:
- 67.8 mm / 2.669 inch
- depth from upper edge of din rail:
- 60.6 mm / 2.386 inch
- emc emission of interference:
- Per EN 61000-6-3
- emc immunity to interference:
- Per EN 61000-6-1: EN 61000-6-2
- exposure to pollutants:
- Per IEC 60068-2-42 and IEC 60068-2-43
- fine stranded conductor:
- 0.08 2.5 mm / 28 14 AWG
- fire load:
- 0.881 MJ
- height:
- 100 mm / 3.937 inch
- housing material:
- Polycarbonate: polyamide 6.6
- isolation:
- 500 V system/field
- measured current typ:
- ¤ 350 A
- measurement error 25 c:
- ¤ 0.5 K in temperature range: 30 +150 C
- measurement repetition rate 2 channel 2 conductor:
- 0.63 s
- measurement repetition rate standard:
- 1.1 s
- mounting position:
- Horizontal (standing/lying): vertical
- mounting type:
- DIN-35 rail
- number of analog inputs:
- 4
- number of incoming power jumper contacts:
- 2
- number of outgoing power jumper contacts:
- 2
- operating altitude:
- 0 2000 m
- packaging type:
- Box
- permissible h2s contaminant concentration at a relative humidity 75:
- 10 ppm
- permissible so2 contaminant concentration at a relative humidity 75:
- 25 ppm
- pollution degree 5:
- 2 per IEC 61131-2
- power consumption 5 v system supply:
- 50 mA
- protection type:
- IP20
- relative humidity without condensation:
- 0.95
- resolution over entire range:
- 0.1 C
- response time max:
- 4 s
- sensor connection:
- 4 x (2-wire)
- sensor types:
- Pt1000: Configurable: Ni1000, KTY 81
- shock resistance:
- 15g per IEC 60068-2-27
- signal type:
- Resistance measurement
- signal type configurable:
- Yes
- solid conductor:
- 0.08 2.5 mm / 28 14 AWG
- strip length:
- 8 9 mm / 0.31 0.35 inch
- supply voltage field:
- 24 VDC (-25 +30 %): via power jumper contacts (power supply via blade contact: transmission via spring contact)
- supply voltage system:
- 5 VDC: via data contacts
- surrounding air temperature operation:
- 0 55 C
- surrounding air temperature storage:
- -40 85 C
- temperature coefficient:
- ¤ 20 ppm/K
- temperature range:
- 30 +150 C
- total number of channels module:
- 4
- vibration resistance:
- Per IEC 60068-2-6
- weight:
- 49.664 g
- width:
- 12 mm / 0.472 inch