Description
4DO24 VDC valve Ex i
View AllClose
- Green LED (output status)
- Red LED (wire breakage, short circuit)
Additional Information
actuator connection: |
4 x (2-wire) |
color: |
Light blue |
conformity marking: |
CE |
connection technology inputs outputs: |
16 x CAGE CLAMP |
connection type 1: |
Inputs/outputs |
country of origin sales organisation germany: |
DE |
depth: |
67.8 mm / 2.669 inch |
depth from upper edge of din rail: |
60.6 mm / 2.386 inch |
emc emission of interference: |
Per EN 61000-6-3, marine applications |
emc immunity to interference: |
Per EN 61000-6-2, marine applications |
ex guideline: |
EN IEC 60079-0, -7, -11 |
exposure to pollutants: |
Per IEC 60068-2-42 and IEC 60068-2-43 |
fine stranded conductor: |
0.08 2.5 mm / 28 14 AWG |
fire load: |
1.683 MJ |
height: |
100 mm / 3.937 inch |
housing material: |
Polycarbonate: polyamide 6.6 |
input data width internal max: |
4 bits |
intrinsic safety ex i: |
Yes |
isolation: |
300 VAC system/field |
load type: |
Resistive, inductive, lamp load |
marking: |
ATEX, IECEx, INMETRO, Underwriters Laboratories Inc. |
mounting position: |
Horizontal (standing/lying): vertical |
mounting type: |
DIN-35 rail |
note: |
The digital output module must only be operated via 24 VDC Ex i!General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals! |
number of digital outputs: |
4 |
number of incoming power jumper contacts: |
2 |
number of outgoing power jumper contacts: |
2 |
output characteristic: |
High-side switching |
output internal data width max: |
4 bits |
packaging type: |
Box |
permissible h2s contaminant concentration at a relative humidity 75: |
10 ppm |
permissible so2 contaminant concentration at a relative humidity 75: |
25 ppm |
pollution degree 5: |
2 per IEC 61131-2 |
power consumption 5 v system supply: |
20 mA |
power consumption field supply module with no external load: |
10 mA |
power consumption pmax: |
4.86 W (at 47 mA output current) |
protection type: |
IP20 |
reactances ex ia i: |
Lo = 21 mH: Co = 540 nF |
reactances ex ia iia: |
Lo = 14 mH: Co = 2.28 F |
reactances ex ia iib: |
Lo = 8.1 mH: Co = 683 nF |
reactances ex ia iic: |
Lo = 13 H: Co = 88 nF |
reactances note: |
Reactances without accounting for the concurrence of L and C |
relative humidity without condensation: |
0.95 |
safety relevant data circuit: |
Uo = 27.3 V: Io = 117.5 mA: Po = 800.1 mW: Linear characteristic curve |
shock resistance: |
15g per IEC 60068-2-27 |
signal type: |
Voltage |
solid conductor: |
0.08 2.5 mm / 28 14 AWG |
strip length: |
8 9 mm / 0.31 0.35 inch |
supply voltage field: |
24 VDC: (Ex i power supply: UO = max. 27.3 V): via power jumper contacts (power supply via blade contact: transmission via spring contact) |
supply voltage system: |
5 VDC: via data contacts |
surrounding air temperature operation: |
0 55 C |
surrounding air temperature storage: |
-40 85 C |
switching frequency max: |
100 Hz |
total number of channels module: |
4 |
vibration resistance: |
Per IEC 60068-2-6 |
voltage signal type: |
24 VDC |
weight: |
88.500 g |
width: |
24 mm |