conformity marking:
CE
connection technology:
CAGE CLAMP
connection type 1:
Input/output/signaling
control deviation:
¤ 1 %
country of origin sales organisation germany:
DE
current limitation:
1.1 x Io nom (typ.)
default setting:
DC 24 V
depth from upper edge of din rail:
107.5 mm / 4.232 inch
derating:
-3 %/K (> 50 C)
discharge current:
¤ 0.25 mA
efficiency typ:
0.89
fine stranded conductor:
0.08 2.5 mm / 28 12 AWG
fire load:
0.000 MJ
height:
90 mm / 3.543 inch
input current ii:
¤ 0.48 A (240 VAC): ¤ 0.82 A (100 VAC)
input voltage derating:
-2.5 %/V (< 95 VAC)
input voltage range:
AC 85 264 V: DC 120 372 V
inrush current:
¤ 30 A
internal fuse:
T 4 A / 250 VAC
isolation voltage pri sec:
DC 4.242 kV
mains failure hold up time:
120 ms (230 VAC): 20 ms (100 VAC)
mounting type:
DIN-35 rail
mtbf:
> 500,000 h (per IEC 61709)
nominal input voltage ui nom:
1 x AC 100 240 V
nominal mains frequency range:
44 66 Hz: 0 Hz
nominal output current io nom:
2 A (24 VDC): 2.2 A (< 40 C)
nominal output power:
48 W
nominal output voltage uo nom:
DC 24 V (SELV)
open circuit proof:
Yes
operation status indicator:
Green LED (Uo)
output voltage range:
DC 23 28.5 V (adjustable)
overload behavior:
Constant current
overvoltage category:
II
overvoltage protection secondary:
Internal protective circuit || ¤ 37 VDC (in the event of a fault)
packaging type:
Box
parallel operation:
Yes
phases:
1
pollution degree:
2
power factor correction pfc:
Passive
power loss max pl max:
7 W (100 VAC / 24 VDC: 2 A)
power loss pl:
¤ 1 W (230 VAC: No load): ¤ 6 W (230 VAC: Nominal load)
protection class:
II
protection type:
IP20 (per EN 60529)
recommended backup fusing:
Circuit breaker: 6 A, 10 A, 16 A: Tripping characteristic: B or C
relative humidity:
5 96 % (no condensation permissible)
required backup fusing:
An external DC fuse is required for the DC input voltage.
residual ripple:
¤ 20 mV (Peak-to-peak)
resistance to reverse feed:
¤ DC 35 V
series operation:
Yes
short circuit protected:
Yes
signaling:
1 x LED DC OK (green) || 1 x Active signal output DC OK (24 VDC: 20 mA)
solid conductor:
0.08 2.5 mm / 28 12 AWG
standards specifications:
EN 61010-1 || EN 61010-2-201 || EN 61204-3 || EN 60335-1 || UL 60950-1 || UL 508 || GL
strip length:
8 9 mm / 0.31 0.35 inch
surrounding air temperature operation:
-25 70 C (Device starts at 40 C (type-tested))
surrounding air temperature storage:
-25 85 C
transient suppression primary:
Varistor
wago connector:
WAGO 721 Series
weight:
210.000 g
width:
45 mm / 1.772 inch
  • Wago 787-1606
  • Wago 787-1606
  • Wago 787-1606
$151.90

Description

Description Switched-Mode Power Supply EPSITRON CLASSIC Power; Output voltage DC 24 V; 2 A 
Remarks Item description:
  • Switched-mode power supply
  • Natural convection cooling when horizontally mounted
  • Enclosed for use in control cabinets
  • Bounce-free switching signal (DC OK)
  • Suitable for both parallel and series operation
  • Electrically isolated output voltage (SELV) per
    EN 60950-1/UL 60950-1



Overvoltage protection: Varistor (input side); internal protective circuit, < 37 VDC (output side in case of an error)

External fuse: Circuit breakers 6 A, 10 A, 16 A, B or C characteristic; An external DC fuse is required for the DC input voltage

 
 
Item properties

Miscellaneous

Name Value Unit
Switching capacity  30 A   
Power loss PV  < 1 W (230 VAC, no load); 6 W (230 VAC, nominal load)   
Protection class  II   
Factory preset  24 VDC   
Overload behavior  Constant current   
Degree of pollution (5)  2 (per EN 50178)   
Signaling  1 x active signal output 24 VDC, 20 mA   
MTBF  > 500000 h (per IEC 61709)   
Input voltage range  85 ... 264 VAC; 120 ... 372 VDC   
Output voltage range  23 28.5 VDC variable   
Nominal input voltage Vi nom  100 ... 240 VAC   
Input current Ii  0.48 A (240 VAC); 0.82 A (100 VAC)   
Mains failure hold-up time  120 ms (230 VAC); 20 ms (100 VAC)   
Internal fuse  T 4 A / 250 V   
Nominal output voltage Vo nom  24 VDC (SELV)   
Output current Io  2 A at 24 VDC (2.2 A up to 40 )   
Residual ripple  20 mV (peak-to-peak) typ.   
Derating  -3 %/K (> 50 )   
Adjustment accuracy [%]  < 1 
Current limitation  1.1 x Io typ.   
Parallel operation  yes   
Feedback voltage  Max. 35 VDC   
Efficiency  89 % typ.   
Test voltage PRI SEC [kV]  4.2 kV (DC)  kV 
Degree of protection  IP20 per EN 60529   
Operational indication  Green LED (Vo  
Short circuit protection  yes   
Overvoltage category  II   
No-load proof  Yes   
Connection technology  CAGE CLAMP    
Solid conductor  0.08 2.5 mm / 28 12 AWG   
Strip length  8 9 mm / 0.31 0.35 Inch   
Connection technology 2  CAGE CLAMP    
Solid conductor 2  0.08 2.5 mm / 28 12 AWG   
Strip length 2  8 9 mm / 0.31 0.35 Inch   
Connection technology 3  CAGE CLAMP    
Solid conductor 3  0.08 2.5 mm / 28 12 AWG   
Strip length 3  8 ... 9 mm / 0.31 ... 0.35 Inch   
Weight [g]  210 
Width  45 mm / 1.772 Inch   
Height  90 mm / 3.543 Inch   
Depth  107.5 mm / 4.232 Inch   
Storage temperature  -25 +85    
Type of mounting  DIN-35 x 15 carrier rail   
Ambient operating temperature  -25 +70 ; Device start at -40 type-tested   
Mounting type  Tragschienenmontage (EN 60715)   
Climatic category  3K3 (per EN 60721)   
Relative humidity  5 96 % (no condensation permissible)   