Circuit Breakers
-
Schneider Electric RGF36160CU33A Molded Case Circuit Breaker 600V 1600A
Schneider Electric
$30,081.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RGF36160CU33A
- Breaking Capacity Code:
- G
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Range:
- PowerPact
- Ip Degree Of Protection:
- IP40
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Quality Labels:
- CE
- Trip Unit Name:
- MicroLogic 5.0
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Ambient Air Temperature For Operation:
- -25-70 °C
- Control Type:
- operating handle
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Eu Rohs Directive:
- Compliant with Exemptions
- Halogen Content Performance:
- Halogen free plastic parts product
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Mounting Support:
- busbar
- Sustainable Offer Status:
- Green Premium product
- Electrical Connection:
- busbar connection, line || busbar connection, load
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Terminal Identifier:
- AL2500RK
- Quantity Per Set:
- 1
- Pvc Free:
- Yes
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Network Frequency:
- 50/60 Hz
- Mounting Mode:
- unit mount busbar)
- Wire Stripping Length:
- 35 mm
- Local Signalling:
- alarm 1 LED yellow)long-time pick up)
- Mercury Free:
- Yes
- Net Weight:
- 52 lb(US)
- Trip Unit Technology:
- electronic, standard, MicroLogic 5.0, LSI
- Warranty:
- 18 months
- Product Certifications:
- UL || CSA || NOM
- Suitability For Isolation:
- yes IEC 60947-2
- Width:
- 16.53 in
- Line Rated Current:
- 1600-1600 A
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Poles Description:
- 3P
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Device Application:
- distribution
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Height:
- 16.24 in
- Rohs Exemption Information:
- Yes
- Continuous Current Rating:
- 1
- Depth:
- 14.49 in
- Pollution Degree:
- 3 IEC 60947-1
- Environmental Disclosure:
- ENVPEP2206034EN
- Circuit Breaker Application:
- HACR rated
- Product Name:
- PowerPact R
- Circularity Profile:
- ENVEOLI2206034EN
- Utilisation Category:
- category A
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$30,081.00 -
Schneider Electric RGF36160CU31A Molded Case Circuit Breaker 600V 1600A
Schneider Electric
$29,775.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RGF36160CU31A
- Tightening Torque:
- 62-62 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 62-62 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Wire Stripping Length:
- 35 mm
- Ambient Air Temperature For Operation:
- -25-70 °C
- Mounting Support:
- busbar
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity Code:
- G
- Trip Unit Name:
- MicroLogic 3.0
- Local Signalling:
- alarm 1 LED yellow)long-time pick up)
- Width:
- 16.53 in
- Line Rated Current:
- 1600-1600 A
- Pollution Degree:
- 3 IEC 60947-1
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Net Weight:
- 52 lb(US)
- Product Or Component Type:
- circuit breaker
- Range:
- PowerPact
- Device Application:
- distribution
- Pvc Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Eu Rohs Directive:
- Compliant with Exemptions
- Poles Description:
- 3P
- Height:
- 16.24 in
- Product Name:
- PowerPact R
- Terminal Identifier:
- AL2500RK
- Depth:
- 14.49 in
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Ip Degree Of Protection:
- IP40
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Ambient Air Temperature For Storage:
- -50-85 °C
- Warranty:
- 18 months
- Continuous Current Rating:
- 1
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Quantity Per Set:
- 1
- Sustainable Offer Status:
- Green Premium product
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Utilisation Category:
- category A
- Rohs Exemption Information:
- Yes
- Halogen Content Performance:
- Halogen free plastic parts product
- Environmental Disclosure:
- ENVPEP2206034EN
- Product Certifications:
- UL || CSA || NOM
- Control Type:
- operating handle
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Quality Labels:
- CE
- Network Frequency:
- 50/60 Hz
- Suitability For Isolation:
- yes IEC 60947-2
- Circularity Profile:
- ENVEOLI2206034EN
- Mounting Mode:
- unit mount busbar)
- Mercury Free:
- Yes
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$29,775.00 -
Schneider Electric PGF36100U31A Molded Case Circuit Breaker 600V 1000A
Schneider Electric
$19,836.00PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- PGF36100U31A
- Eu Rohs Directive:
- Compliant with Exemptions
- Circuit Breaker Application:
- HACR rated
- Ambient Air Temperature For Operation:
- -2-70 °C
- Device Application:
- distribution
- Product Name:
- PowerPact P
- Width:
- 8.27 in
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Tightening Torque:
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Wire Stripping Length:
- 30 mm
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Depth:
- 8.05 in
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Warranty:
- 18 months
- Local Signalling:
- overload 1 trip indicator green) || 1 trip indicator green)
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Quality Labels:
- CE
- Network Frequency:
- 50/60 Hz
- Range:
- PowerPact
- Poles Description:
- 3P
- Terminal Identifier:
- AL1200P25K
- Control Type:
- toggle
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Pvc Free:
- Yes
- Breaking Capacity Code:
- G
- Ip Degree Of Protection:
- front cover IP40
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Storage:
- -50-85 °C
- Pollution Degree:
- 3 IEC 60947-1
- Trip Unit Name:
- MicroLogic 3.0
- Quantity Per Set:
- 1
- Continuous Current Rating:
- 0.8
- Mounting Support:
- busbar
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Rohs Exemption Information:
- Yes
- Environmental Disclosure:
- ENVPEP2206033EN
- Net Weight:
- 32 lb(US)
- Product Certifications:
- UL || CSA || NOM
- Mercury Free:
- Yes
- Line Rated Current:
- 1000-1000 A
- Sustainable Offer Status:
- Green Premium product
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Mode:
- unit mount busbar)
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circularity Profile:
- ENVEOLI2206033EN
- Height:
- 16.16 in
$19,836.00 -
Schneider Electric PGA36100U31A Molded Case Circuit Breaker 600V 1000A
Schneider Electric
$20,790.00PowerPacT P-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT P-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- PGA36100U31A
- Electrical Connection:
- I-Line connection, line || lugs, load
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Pvc Free:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Ambient Air Temperature For Storage:
- -50-85 °C
- Height:
- 16.16 in
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Continuous Current Rating:
- 0.8
- Line Rated Current:
- 1000-1000 A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Quality Labels:
- CE
- Net Weight:
- 32 lb(US)
- Product Certifications:
- UL || CSA || NOM
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Phase Connection:
- ABC
- Tightening Torque:
- 50-50 N.m 95-240 mm² (4 x AWG 3/0...500 kcmil) || 1.0-1.3 N.m
- Depth:
- 8.05 in
- Mounting Support:
- bracket
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Ip Degree Of Protection:
- front cover IP40
- Mercury Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- Trip Unit Name:
- MicroLogic 3.0
- Circularity Profile:
- ENVEOLI2206033EN
- Quantity Per Set:
- 1
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Range:
- PowerPact
- Long Time Pick-Up Adjustment Range:
- 0.4...1 x Ir
- Network Frequency:
- 50/60 Hz
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Local Signalling:
- overload 1 trip indicator green) || 1 trip indicator green)
- Eu Rohs Directive:
- Compliant with Exemptions
- Device Application:
- distribution
- Mounting Mode:
- I-Line bracket)
- Breaking Capacity Code:
- G
- Control Type:
- toggle
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Wire Stripping Length:
- 30 mm
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Rohs Exemption Information:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Height:
- 9 in
- Ambient Air Temperature For Operation:
- -2-70 °C
- Product Name:
- PowerPact P
- Environmental Disclosure:
- ENVPEP2206033EN
- Poles Description:
- 3P
- Width:
- 8.27 in
- Awg Gauge:
- 4 x AWG 3/0...500 kcmil aluminium/copper
- Product Or Component Type:
- circuit breaker
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Terminal Identifier:
- AL1200P25K
- Warranty:
- 18 months
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$20,790.00 -
Schneider Electric LLN36000S40XABY023 Automatic Molded Case Switch 600V 400A
Schneider Electric
$8,530.00Automatic switch, PowerPacT L, 400A, 3 pole, 600VAC, 50kA, plug in, magnetic, aux, special- SKU:
- LLN36000S40XABY023
- Sustainable Offer Status:
- Green Premium product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mercury Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Accessory / Separate Part Type:
- auxiliary switch 2 NO + 2 NC
- Depth:
- 6.61 in
- Range Of Product:
- PowerPact L
- Width:
- 5.51 in
- Trip Unit Technology:
- magnetic
- Magnetic Tripping Current:
- 4800-4800 A
- Rohs Exemption Information:
- Yes
- Electrical Connection:
- plug-in, line || plug-in, load
- Eu Rohs Directive:
- Compliant with Exemptions
- Line Rated Current:
- 400 A
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- [Ue] Rated Operational Voltage:
- 600 V AC
- Environmental Disclosure:
- ENVPEP2206029EN
- Poles Description:
- 3P
- Tightening Torque:
- 50-50 N.m 95-240 mm² (AWG 3/0...500 kcmil)
- Short-Circuit Withstand:
- 125 kA 240 V UL 489 || 100 kA 480 V UL 489 || 50 kA 600 V UL 489
- Breaking Capacity Code:
- L
- Product Or Component Type:
- automatic switch
- Pvc Free:
- Yes
- Height:
- 13.38 in
- Mounting Mode:
- plug-in
- Terminal Identifier:
- AL600LF52K3
- Circularity Profile:
- ENVEOLI2206029EN
- Warranty:
- 18 months
- Product Certifications:
- NMX || UL Listed || IEC || CCC || CE || CSA
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$8,530.00 -
Schneider Electric LLA36250U31X Molded Case Circuit Breaker 600V 250A
Schneider Electric
$10,213.00PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are...- SKU:
- LLA36250U31X
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 overcurrent trip switch SDE plug-in) || 1 voltage release MN or MX plug-in)
- Network Frequency:
- 50/60 Hz
- Breaking Capacity Code:
- L
- Product Name:
- PowerPact L
- Mounting Mode:
- I-Line bracket)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Sustainable Offer Status:
- Green Premium product
- Rohs Exemption Information:
- Yes
- Phase Connection:
- ABC
- Ambient Air Temperature For Operation:
- -2-70 °C
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Tightening Torque:
- 50-50 N.m 35-300 mm² (AWG 2...600 kcmil) || 50-50 N.m 35-240 mm² (AWG 2...500 kcmil)
- Circuit Breaker Application:
- HACR rated
- Electrical Connection:
- I-Line connection, line || lugs, load
- Breaking Capacity:
- 125 kA 240 V AC 50/60 Hz UL 489 || 100 kA 480 V AC 50/60 Hz UL 489 || 50 kA 600 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 50 kA 500 V DC UL 489
- Mounting Support:
- bracket
- Utilisation Category:
- category A
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.3, LI
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz IEC 60947-3
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Ambient Air Temperature For Storage:
- -50-85 °C
- Suitability For Isolation:
- yes IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 125 kA 220/240 V AC 50/60 Hz IEC 60947-2 || 100 kA 380/440/415 V AC 50/60 Hz IEC 60947-2 || 50 kA 500/525 V AC 50/60 Hz IEC 60947-2 || 20 kA 250 V DC IEC 60947-2 || 20 kA 500 V DC IEC 60947-2
- Communication Interface:
- Modbus || Ethernet
- Long Time Pick-Up Adjustment Range:
- 0.25...1 x In
- Depth:
- 110 mm
- Awg Gauge:
- AWG 2...600 kcmil copper || AWG 2...500 kcmil aluminium
- Wire Stripping Length:
- 31 mm
- Ip Degree Of Protection:
- front cover IP40
- Mounting Height:
- 6 in
- Warranty:
- 18 months
- Eu Rohs Directive:
- Compliant with Exemptions
- Mercury Free:
- Yes
- Product Certifications:
- UL || CSA || NOM
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Protection Technology:
- current limiter
- Height:
- 340 mm
- Pvc Free:
- Yes
- Terminal Identifier:
- AL400L61K3
- Standards:
- UL || CSA || NEMA || NOM-003-SCFI-2000 || IEC 60947-2
- Trip Unit Name:
- MicroLogic 3.3
- Poles Description:
- 3P
- Device Application:
- distribution
- Net Weight:
- 6.2 kg
- Device Short Name:
- L-Frame
- Local Signalling:
- ready 1 LED green) || alarm 1 LED 90 % Ir orange) || alarm LED 105 % Ir red) || switched off (OFF) 1 trip indicator green)
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circularity Profile:
- ENVEOLI2206029EN
- Continuous Current Rating:
- 0.8
- Range:
- PowerPact
- Width:
- 140 mm
- Line Rated Current:
- 250-250 A
- Pollution Degree:
- 3 IEC 60947-1
- Control Type:
- toggle
- Color:
- Black
- Environmental Disclosure:
- ENVPEP2206029EN
- Product Or Component Type:
- circuit breaker
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$10,213.00 -
Schneider Electric RJF36250CU44A Molded Case Circuit Breaker 600V 2500A
Schneider Electric
$64,253.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJF36250CU44A
- Control Type:
- operating handle
- Net Weight:
- 52 lb(US)
- Quality Labels:
- CE
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Pvc Free:
- Yes
- Height:
- 16.24 in
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Eu Rohs Directive:
- Compliant with Exemptions
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Rohs Exemption Information:
- Yes
- Device Application:
- distribution
- Pollution Degree:
- 3 IEC 60947-1
- Continuous Current Rating:
- 1
- Circuit Breaker Application:
- HACR rated
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Trip Unit Name:
- MicroLogic 6.0 A
- Suitability For Isolation:
- yes IEC 60947-2
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Ip Degree Of Protection:
- IP40
- Depth:
- 14.49 in
- Halogen Content Performance:
- Halogen free plastic parts product
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Mounting Support:
- busbar
- Ambient Air Temperature For Operation:
- -25-70 °C
- Range:
- PowerPact
- Warranty:
- 18 months
- Environmental Disclosure:
- ENVPEP2206034EN
- Width:
- 16.53 in
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Network Frequency:
- 50/60 Hz
- Mounting Mode:
- unit mount busbar)
- Product Or Component Type:
- circuit breaker
- Terminal Identifier:
- AL2500RK
- Mercury Free:
- Yes
- Circularity Profile:
- ENVEOLI2206034EN
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Product Name:
- PowerPact R
- Ambient Air Temperature For Storage:
- -50-85 °C
- Sustainable Offer Status:
- Green Premium product
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Wire Stripping Length:
- 35 mm
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity Code:
- J
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Utilisation Category:
- category A
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Quantity Per Set:
- 1
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Poles Description:
- 3P
- Line Rated Current:
- 2500-2500 A
$64,253.00 -
Schneider Electric RJF36120CU44A Molded Case Circuit Breaker 600V 1200A
Schneider Electric
$33,308.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJF36120CU44A
- Product Certifications:
- UL || CSA || NOM
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Circularity Profile:
- ENVEOLI2206034EN
- Environmental Disclosure:
- ENVPEP2206034EN
- Utilisation Category:
- category A
- Wire Stripping Length:
- 35 mm
- Line Rated Current:
- 1200-1200 A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Continuous Current Rating:
- 1
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Depth:
- 14.49 in
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Breaking Capacity Code:
- J
- Halogen Content Performance:
- Halogen free plastic parts product
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Suitability For Isolation:
- yes IEC 60947-2
- Ip Degree Of Protection:
- IP40
- Circuit Breaker Application:
- HACR rated
- Quantity Per Set:
- 1
- Product Name:
- PowerPact R
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Range:
- PowerPact
- Warranty:
- 18 months
- Network Frequency:
- 50/60 Hz
- Device Application:
- distribution
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Width:
- 16.53 in
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Pvc Free:
- Yes
- Height:
- 16.24 in
- Ambient Air Temperature For Operation:
- -25-70 °C
- Mercury Free:
- Yes
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Product Or Component Type:
- circuit breaker
- Sustainable Offer Status:
- Green Premium product
- Mounting Mode:
- unit mount busbar)
- Eu Rohs Directive:
- Compliant with Exemptions
- Quality Labels:
- CE
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Rohs Exemption Information:
- Yes
- Poles Description:
- 3P
- Mounting Support:
- busbar
- Control Type:
- operating handle
- Terminal Identifier:
- AL2500RK
- Ambient Air Temperature For Storage:
- -50-85 °C
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Net Weight:
- 52 lb(US)
- Trip Unit Name:
- MicroLogic 6.0 A
$33,308.00 -
Schneider Electric RJA36120CU33A Molded Case Circuit Breaker 600V 1200A
Schneider Electric
$36,599.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJA36120CU33A
- Pollution Degree:
- 3 IEC 60947-1
- Electrical Connection:
- I-Line connection, line || lugs, load
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Terminal Identifier:
- AL1200R53K
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Quality Labels:
- CE
- Trip Unit Technology:
- electronic, standard, MicroLogic 5.0, LSI
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Halogen Content Performance:
- Halogen free plastic parts product
- Sustainable Offer Status:
- Green Premium product
- Line Rated Current:
- 1200-1200 A
- Ambient Air Temperature For Operation:
- -25-70 °C
- Net Weight:
- 52 lb(US)
- Height:
- 13.38 in
- Awg Gauge:
- 4 x AWG 3/0…600 kcmil aluminium/copper || 4 x AWG 3/0...500 kcmil copper
- Eu Rohs Directive:
- Compliant with Exemptions
- Tightening Torque:
- 28-28 N.m 95-240 mm² (4 x AWG 3/0…600 kcmil)
- Product Name:
- PowerPact R
- Device Application:
- distribution
- Rohs Exemption Information:
- Yes
- Ip Degree Of Protection:
- IP40
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Quantity Per Set:
- 1
- Mounting Support:
- bracket
- Breaking Capacity Code:
- J
- Control Type:
- operating handle
- Mounting Mode:
- I-Line bracket)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Wire Stripping Length:
- 30 mm
- Poles Description:
- 3P
- Product Certifications:
- UL || CSA || NOM
- Product Or Component Type:
- circuit breaker
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Range:
- PowerPact
- Network Frequency:
- 50/60 Hz
- Ambient Air Temperature For Storage:
- -50-85 °C
- Local Signalling:
- alarm 1 LED yellow)long-time pick up)
- Width:
- 14.96 in
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Depth:
- 13.78 in
- Environmental Disclosure:
- ENVPEP2206034EN
- Continuous Current Rating:
- 1
- Circularity Profile:
- ENVEOLI2206034EN
- Utilisation Category:
- category A
- Trip Unit Name:
- MicroLogic 5.0
- Warranty:
- 18 months
$36,599.00 -
Schneider Electric RJA36120CU44A Molded Case Circuit Breaker 600V 1200A
Schneider Electric
$40,829.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJA36120CU44A
- Awg Gauge:
- 4 x AWG 3/0â¦600 kcmil aluminium/copper || 4 x AWG 3/0...500 kcmil copper
- Continuous Current Rating:
- 1
- Height:
- 13.38 in
- Ambient Air Temperature For Operation:
- -25-70 °C
- Depth:
- 13.78 in
- Pvc Free:
- Yes
- Sustainable Offer Status:
- Green Premium product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Quantity Per Set:
- 1
- Circularity Profile:
- ENVEOLI2206034EN
- Control Type:
- operating handle
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Terminal Identifier:
- AL1200R53K
- Quality Labels:
- CE
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Product Name:
- PowerPact R
- Pollution Degree:
- 3 IEC 60947-1
- Network Frequency:
- 50/60 Hz
- Poles Description:
- 3P
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Warranty:
- 18 months
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Circuit Breaker Application:
- HACR rated
- Tightening Torque:
- 28-28 N.m 95-240 mm² (4 x AWG 3/0â¦600 kcmil)
- Suitability For Isolation:
- yes IEC 60947-2
- Mounting Support:
- bracket
- Ip Degree Of Protection:
- IP40
- Mercury Free:
- Yes
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Rohs Exemption Information:
- Yes
- Net Weight:
- 52 lb(US)
- Product Or Component Type:
- circuit breaker
- Eu Rohs Directive:
- Compliant with Exemptions
- Utilisation Category:
- category A
- Mounting Mode:
- I-Line bracket)
- Range:
- PowerPact
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Width:
- 14.96 in
- Breaking Capacity Code:
- J
- Wire Stripping Length:
- 30 mm
- Trip Unit Name:
- MicroLogic 6.0 A
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Device Application:
- distribution
- Environmental Disclosure:
- ENVPEP2206034EN
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Electrical Connection:
- I-Line connection, line || lugs, load
- Line Rated Current:
- 1200-1200 A
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Halogen Content Performance:
- Halogen free plastic parts product
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$40,829.00 -
Schneider Electric RJF36120U44A Molded Case Circuit Breaker 600V 1200A
Schneider Electric
$28,553.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJF36120U44A
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Rohs Exemption Information:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Suitability For Isolation:
- yes IEC 60947-2
- Product Name:
- PowerPact R
- Height:
- 16.24 in
- Utilisation Category:
- category A
- Circularity Profile:
- ENVEOLI2206034EN
- Sustainable Offer Status:
- Green Premium product
- Device Application:
- distribution
- Warranty:
- 18 months
- Product Or Component Type:
- circuit breaker
- Environmental Disclosure:
- ENVPEP2206034EN
- Mounting Mode:
- unit mount busbar)
- Poles Description:
- 3P
- Halogen Content Performance:
- Halogen free plastic parts product
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Mercury Free:
- Yes
- Quantity Per Set:
- 1
- Quality Labels:
- CE
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Control Type:
- operating handle
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Range:
- PowerPact
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Pvc Free:
- Yes
- Line Rated Current:
- 1200-1200 A
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Network Frequency:
- 50/60 Hz
- Width:
- 16.53 in
- Ambient Air Temperature For Storage:
- -50-85 °C
- Pollution Degree:
- 3 IEC 60947-1
- Tightening Torque:
- 62-62 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 62-62 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Terminal Identifier:
- AL2500RK
- Trip Unit Name:
- MicroLogic 6.0 A
- Depth:
- 14.49 in
- Ip Degree Of Protection:
- IP40
- Mounting Support:
- busbar
- Ambient Air Temperature For Operation:
- -25-70 °C
- Wire Stripping Length:
- 35 mm
- Continuous Current Rating:
- 0.8
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Net Weight:
- 52 lb(US)
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Breaking Capacity Code:
- J
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$28,553.00 -
Schneider Electric RJF36200CU44A Molded Case Circuit Breaker 600V 2000A
Schneider Electric
$40,995.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJF36200CU44A
- Suitability For Isolation:
- yes IEC 60947-2
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Depth:
- 14.49 in
- Mercury Free:
- Yes
- Range:
- PowerPact
- Wire Stripping Length:
- 35 mm
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Mounting Support:
- busbar
- Product Or Component Type:
- circuit breaker
- Poles Description:
- 3P
- Ambient Air Temperature For Storage:
- -50-85 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circularity Profile:
- ENVEOLI2206034EN
- Line Rated Current:
- 2000-2000 A
- Ambient Air Temperature For Operation:
- -25-70 °C
- Electrical Connection:
- busbar connection, line || busbar connection, load
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Network Frequency:
- 50/60 Hz
- Halogen Content Performance:
- Halogen free plastic parts product
- Width:
- 16.53 in
- Quantity Per Set:
- 1
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Net Weight:
- 52 lb(US)
- Circuit Breaker Application:
- HACR rated
- Mounting Mode:
- unit mount busbar)
- Warranty:
- 18 months
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Rohs Exemption Information:
- Yes
- Quality Labels:
- CE
- Environmental Disclosure:
- ENVPEP2206034EN
- Product Name:
- PowerPact R
- Terminal Identifier:
- AL2500RK
- Pollution Degree:
- 3 IEC 60947-1
- Control Type:
- operating handle
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Height:
- 16.24 in
- Trip Unit Name:
- MicroLogic 6.0 A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pvc Free:
- Yes
- Utilisation Category:
- category A
- Continuous Current Rating:
- 1
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Product Certifications:
- UL || CSA || NOM
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Device Application:
- distribution
- Ip Degree Of Protection:
- IP40
- Eu Rohs Directive:
- Compliant with Exemptions
- Breaking Capacity Code:
- J
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$40,995.00 -
Schneider Electric RJF36160U44A Molded Case Circuit Breaker 600V 1600A
Schneider Electric
$28,553.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJF36160U44A
- Warranty:
- 18 months
- Ambient Air Temperature For Operation:
- -25-70 °C
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Product Or Component Type:
- circuit breaker
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Eu Rohs Directive:
- Compliant with Exemptions
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Net Weight:
- 52 lb(US)
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Support:
- busbar
- Terminal Identifier:
- AL2500RK
- Network Frequency:
- 50/60 Hz
- Ambient Air Temperature For Storage:
- -50-85 °C
- Trip Unit Name:
- MicroLogic 6.0 A
- Product Name:
- PowerPact R
- Wire Stripping Length:
- 35 mm
- Breaking Capacity Code:
- J
- Control Type:
- operating handle
- Product Certifications:
- UL || CSA || NOM
- Ip Degree Of Protection:
- IP40
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Width:
- 16.53 in
- Device Application:
- distribution
- Mounting Mode:
- unit mount busbar)
- Halogen Content Performance:
- Halogen free plastic parts product
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Sustainable Offer Status:
- Green Premium product
- Poles Description:
- 3P
- Pvc Free:
- Yes
- Line Rated Current:
- 1600-1600 A
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Range:
- PowerPact
- Mercury Free:
- Yes
- Depth:
- 14.49 in
- Circularity Profile:
- ENVEOLI2206034EN
- Suitability For Isolation:
- yes IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Continuous Current Rating:
- 0.8
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Quantity Per Set:
- 1
- Utilisation Category:
- category A
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Height:
- 16.24 in
- Quality Labels:
- CE
- Rohs Exemption Information:
- Yes
- Environmental Disclosure:
- ENVPEP2206034EN
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$28,553.00 -
Schneider Electric RJF36160CU44A Molded Case Circuit Breaker 600V 1600A
Schneider Electric
$35,436.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJF36160CU44A
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Height:
- 16.24 in
- Mounting Mode:
- unit mount busbar)
- Net Weight:
- 52 lb(US)
- Communication Interface:
- Modbus
- Electrical Connection:
- busbar connection, line || busbar connection, load
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Device Application:
- distribution
- Product Or Component Type:
- circuit breaker
- Eu Rohs Directive:
- Compliant with Exemptions
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Ip Degree Of Protection:
- IP40
- Product Name:
- PowerPact R
- Line Rated Current:
- 1600-1600 A
- Trip Unit Name:
- MicroLogic 6.0 A
- Pvc Free:
- Yes
- Pollution Degree:
- 3 IEC 60947-1
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Breaking Capacity Code:
- J
- Sustainable Offer Status:
- Green Premium product
- Product Certifications:
- UL || CSA || NOM
- Rohs Exemption Information:
- Yes
- Mounting Support:
- busbar
- Circuit Breaker Application:
- HACR rated
- Ambient Air Temperature For Operation:
- -25-70 °C
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Circularity Profile:
- ENVEOLI2206034EN
- Wire Stripping Length:
- 35 mm
- Terminal Identifier:
- AL2500RK
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Control Type:
- operating handle
- Warranty:
- 18 months
- Continuous Current Rating:
- 1
- Poles Description:
- 3P
- Utilisation Category:
- category A
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Quality Labels:
- CE
- Ambient Air Temperature For Storage:
- -50-85 °C
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Mercury Free:
- Yes
- Quantity Per Set:
- 1
- Depth:
- 14.49 in
- Network Frequency:
- 50/60 Hz
- Range:
- PowerPact
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Halogen Content Performance:
- Halogen free plastic parts product
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206034EN
- Width:
- 16.53 in
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$35,436.00 -
Schneider Electric RGF36200U44A Molded Case Circuit Breaker 600V 2000A
Schneider Electric
$27,378.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RGF36200U44A
- Wire Stripping Length:
- 35 mm
- Trip Unit Name:
- MicroLogic 6.0 A
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Height:
- 16.24 in
- Mercury Free:
- Yes
- Mounting Mode:
- unit mount busbar)
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Net Weight:
- 52 lb(US)
- Sustainable Offer Status:
- Green Premium product
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Network Frequency:
- 50/60 Hz
- Product Name:
- PowerPact R
- Device Application:
- distribution
- Quality Labels:
- CE
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Eu Rohs Directive:
- Compliant with Exemptions
- Rohs Exemption Information:
- Yes
- Terminal Identifier:
- AL2500RK
- Ambient Air Temperature For Operation:
- -25-70 °C
- Environmental Disclosure:
- ENVPEP2206034EN
- Circularity Profile:
- ENVEOLI2206034EN
- Pollution Degree:
- 3 IEC 60947-1
- Poles Description:
- 3P
- Quantity Per Set:
- 1
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Depth:
- 14.49 in
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Width:
- 16.53 in
- Continuous Current Rating:
- 0.8
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity Code:
- G
- Halogen Content Performance:
- Halogen free plastic parts product
- Line Rated Current:
- 2000-2000 A
- Range:
- PowerPact
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Pvc Free:
- Yes
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Ip Degree Of Protection:
- IP40
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Certifications:
- UL || CSA || NOM
- Utilisation Category:
- category A
- Warranty:
- 18 months
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Product Or Component Type:
- circuit breaker
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mounting Support:
- busbar
- Control Type:
- operating handle
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$27,378.00 -
Schneider Electric RGF36200U31A Molded Case Circuit Breaker 600V 2000A
Schneider Electric
$23,160.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RGF36200U31A
- Breaking Capacity Code:
- G
- Device Application:
- distribution
- Height:
- 16.24 in
- Depth:
- 14.49 in
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Ambient Air Temperature For Operation:
- -25-70 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Utilisation Category:
- category A
- Suitability For Isolation:
- yes IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Product Or Component Type:
- circuit breaker
- Ip Degree Of Protection:
- IP40
- Poles Description:
- 3P
- Circularity Profile:
- ENVEOLI2206034EN
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Range:
- PowerPact
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Sustainable Offer Status:
- Green Premium product
- Quality Labels:
- CE
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Pvc Free:
- Yes
- Mounting Mode:
- unit mount busbar)
- Terminal Identifier:
- AL2500RK
- Circuit Breaker Application:
- HACR rated
- Pollution Degree:
- 3 IEC 60947-1
- Mounting Support:
- busbar
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Local Signalling:
- alarm 1 LED yellow)long-time pick up)
- Product Name:
- PowerPact R
- Halogen Content Performance:
- Halogen free plastic parts product
- Warranty:
- 18 months
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Wire Stripping Length:
- 35 mm
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Rohs Exemption Information:
- Yes
- Width:
- 16.53 in
- Control Type:
- operating handle
- Line Rated Current:
- 2000-2000 A
- Network Frequency:
- 50/60 Hz
- Eu Rohs Directive:
- Compliant with Exemptions
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206034EN
- Product Certifications:
- UL || CSA || NOM
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Continuous Current Rating:
- 0.8
- Quantity Per Set:
- 1
- Trip Unit Name:
- MicroLogic 3.0
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Mercury Free:
- Yes
- Net Weight:
- 52 lb(US)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$23,160.00 -
Schneider Electric RGF36200CU31A Molded Case Circuit Breaker 600V 2000A
Schneider Electric
$35,042.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RGF36200CU31A
- Product Certifications:
- UL || CSA || NOM
- Suitability For Isolation:
- yes IEC 60947-2
- Quantity Per Set:
- 1
- Poles Description:
- 3P
- Net Weight:
- 52 lb(US)
- Continuous Current Rating:
- 1
- Ambient Air Temperature For Operation:
- -25-70 °C
- Ip Degree Of Protection:
- IP40
- Height:
- 16.24 in
- Control Type:
- operating handle
- Circuit Breaker Application:
- HACR rated
- Local Signalling:
- alarm 1 LED yellow)long-time pick up)
- Ambient Air Temperature For Storage:
- -50-85 °C
- Utilisation Category:
- category A
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Pvc Free:
- Yes
- Mounting Support:
- busbar
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Environmental Disclosure:
- ENVPEP2206034EN
- Pollution Degree:
- 3 IEC 60947-1
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Wire Stripping Length:
- 35 mm
- Circularity Profile:
- ENVEOLI2206034EN
- Product Name:
- PowerPact R
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Mounting Mode:
- unit mount busbar)
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Device Application:
- distribution
- Quality Labels:
- CE
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Line Rated Current:
- 2000-2000 A
- Breaking Capacity Code:
- G
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Network Frequency:
- 50/60 Hz
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Halogen Content Performance:
- Halogen free plastic parts product
- Rohs Exemption Information:
- Yes
- Trip Unit Name:
- MicroLogic 3.0
- Depth:
- 14.49 in
- Warranty:
- 18 months
- Mercury Free:
- Yes
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Terminal Identifier:
- AL2500RK
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Electrical Connection:
- busbar connection, line || busbar connection, load
- Range:
- PowerPact
- Sustainable Offer Status:
- Green Premium product
- Width:
- 16.53 in
- Eu Rohs Directive:
- Compliant with Exemptions
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$35,042.00 -
Schneider Electric RGF36160U44A Molded Case Circuit Breaker 600V 1600A
Schneider Electric
$27,378.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RGF36160U44A
- Electrical Connection:
- busbar connection, line || busbar connection, load
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Sustainable Offer Status:
- Green Premium product
- Ip Degree Of Protection:
- IP40
- Breaking Capacity Code:
- G
- Height:
- 16.24 in
- Wire Stripping Length:
- 35 mm
- Awg Gauge:
- AWG 3/0...750 kcmil aluminium/copper
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Trip Unit Name:
- MicroLogic 6.0 A
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Circularity Profile:
- ENVEOLI2206034EN
- Net Weight:
- 52 lb(US)
- Quantity Per Set:
- 1
- Mercury Free:
- Yes
- Range:
- PowerPact
- Quality Labels:
- CE
- Product Certifications:
- UL || CSA || NOM
- Tightening Torque:
- 68-68 N.m 50-400 mm² (AWG 1/0...750 kcmil) || 68-68 N.m 50-150 mm² (2 x AWG 1/0...2 x 300 kcmil)
- Pollution Degree:
- 3 IEC 60947-1
- Product Or Component Type:
- circuit breaker
- Suitability For Isolation:
- yes IEC 60947-2
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Width:
- 16.53 in
- Mounting Mode:
- unit mount busbar)
- Environmental Disclosure:
- ENVPEP2206034EN
- Network Frequency:
- 50/60 Hz
- Mounting Support:
- busbar
- Warranty:
- 18 months
- Poles Description:
- 3P
- Local Signalling:
- alarm 1 LED yellow)long-time pick up) || 1 LED red)long-time pick up) || trip causes 1 LED red) || 1 LED red)digital ammeter) || ground indicator 1 LED red) || phase-loading LED green)load balancing)
- Control Type:
- operating handle
- Pvc Free:
- Yes
- Halogen Content Performance:
- Halogen free plastic parts product
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Ambient Air Temperature For Storage:
- -50-85 °C
- Continuous Current Rating:
- 0.8
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Device Application:
- distribution
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Ambient Air Temperature For Operation:
- -25-70 °C
- Utilisation Category:
- category A
- Trip Unit Technology:
- electronic, ammeter, MicroLogic 6.0 A, LSIG
- Line Rated Current:
- 1600-1600 A
- Eu Rohs Directive:
- Compliant with Exemptions
- Rohs Exemption Information:
- Yes
- Depth:
- 14.49 in
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Terminal Identifier:
- AL2500RK
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Product Name:
- PowerPact R
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$27,378.00 -
Schneider Electric RJA36120CU31A Molded Case Circuit Breaker 600V 1200A
Schneider Electric
$36,111.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RJA36120CU31A
- Terminal Identifier:
- AL1200R53K
- Pollution Degree:
- 3 IEC 60947-1
- Environmental Disclosure:
- ENVPEP2206034EN
- Range:
- PowerPact
- Net Weight:
- 52 lb(US)
- Mercury Free:
- Yes
- Ambient Air Temperature For Operation:
- -25-70 °C
- Height:
- 13.38 in
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Storage:
- -50-85 °C
- Circularity Profile:
- ENVEOLI2206034EN
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Mounting Mode:
- I-Line bracket)
- Network Frequency:
- 50/60 Hz
- Product Or Component Type:
- circuit breaker
- Width:
- 14.96 in
- Product Name:
- PowerPact R
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Mounting Support:
- bracket
- Depth:
- 13.78 in
- Quality Labels:
- CE
- Circuit Breaker Application:
- HACR rated
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Poles Description:
- 3P
- Halogen Content Performance:
- Halogen free plastic parts product
- Eu Rohs Directive:
- Compliant with Exemptions
- Quantity Per Set:
- 1
- Warranty:
- 18 months
- Breaking Capacity:
- AIR 100 kA 240 V AC 50/60 Hz UL 489 || AIR 65 kA 480 V AC 50/60 Hz UL 489 || AIR 25 kA 600 V AC 50/60 Hz UL 489 || Icu 65 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 50 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Trip Unit Name:
- MicroLogic 3.0
- Utilisation Category:
- category A
- Control Type:
- operating handle
- Suitability For Isolation:
- yes IEC 60947-2
- [Ics] Rated Service Breaking Capacity:
- 35 kA 240 V AC 50/60 Hz IEC 60947-2 || 25 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Device Application:
- distribution
- Continuous Current Rating:
- 1
- Rohs Exemption Information:
- Yes
- Ip Degree Of Protection:
- IP40
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Wire Stripping Length:
- 30 mm
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Certifications:
- UL || CSA || NOM
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Electrical Connection:
- I-Line connection, line || lugs, load
- Pvc Free:
- Yes
- Tightening Torque:
- 28-28 N.m 95-240 mm² (4 x AWG 3/0â¦600 kcmil)
- Line Rated Current:
- 1200-1200 A
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- Awg Gauge:
- 4 x AWG 3/0â¦600 kcmil aluminium/copper || 4 x AWG 3/0...500 kcmil copper
- Local Signalling:
- alarm 1 LED yellow)long-time pick up)
- Breaking Capacity Code:
- J
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$36,111.00 -
Schneider Electric RGA36100CU31A Molded Case Circuit Breaker 600V 1000A
Schneider Electric
$33,945.00PowerPacT R-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT R-Frame circuit breakers have either a fixed long time electronic trip unit, ET 1.0I, or Micrologic trip units...- SKU:
- RGA36100CU31A
- Quantity Per Set:
- 1
- Eu Rohs Directive:
- Compliant with Exemptions
- Control Type:
- operating handle
- Mounting Support:
- bracket
- Number Of Slots:
- 2 auxiliary switch OF plug-in) || 1 alarm switch SD plug-in) || 1 voltage release MN or MX plug-in)
- Trip Unit Name:
- MicroLogic 3.0
- Breaking Capacity Code:
- G
- Rohs Exemption Information:
- Yes
- Standards:
- UL || CSA || NEMA || NMX J-266 || IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70 °C
- [Ue] Rated Operational Voltage:
- 600 V AC 50/60 Hz UL 489
- [Ui] Rated Insulation Voltage:
- 750 V IEC 60947-2
- Circularity Profile:
- ENVEOLI2206034EN
- Electrical Connection:
- I-Line connection, line || lugs, load
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Terminal Identifier:
- AL1200R53K
- Breaking Capacity:
- AIR 65 kA 240 V AC 50/60 Hz UL 489 || AIR 35 kA 480 V AC 50/60 Hz UL 489 || AIR 18 kA 600 V AC 50/60 Hz UL 489 || Icu 50 kA 240 V AC 50/60 Hz IEC 60947-2 || Icu 35 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Pollution Degree:
- 3 IEC 60947-1
- Quality Labels:
- CE
- Mercury Free:
- Yes
- Line Rated Current:
- 1000-1000 A
- Range:
- PowerPact
- Utilisation Category:
- category A
- Depth:
- 13.78 in
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Width:
- 14.96 in
- Suitability For Isolation:
- yes IEC 60947-2
- Environmental Disclosure:
- ENVPEP2206034EN
- Pvc Free:
- Yes
- Net Weight:
- 52 lb(US)
- Trip Unit Technology:
- electronic, standard, MicroLogic 3.0, LI
- Ambient Air Temperature For Storage:
- -50-85 °C
- Halogen Content Performance:
- Halogen free plastic parts product
- Product Certifications:
- UL || CSA || NOM
- Wire Stripping Length:
- 30 mm
- Ip Degree Of Protection:
- IP40
- Tightening Torque:
- 28-28 N.m 95-240 mm² (4 x AWG 3/0â¦600 kcmil)
- Circuit Breaker Application:
- HACR rated
- Network Frequency:
- 50/60 Hz
- Local Signalling:
- alarm 1 LED yellow)long-time pick up)
- Height:
- 13.38 in
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Poles Description:
- 3P
- Product Name:
- PowerPact R
- Mounting Mode:
- I-Line bracket)
- Device Application:
- distribution
- Warranty:
- 18 months
- [Ics] Rated Service Breaking Capacity:
- 25 kA 240 V AC 50/60 Hz IEC 60947-2 || 20 kA 380/415 V AC 50/60 Hz IEC 60947-2
- Sustainable Offer Status:
- Green Premium product
- Awg Gauge:
- 4 x AWG 3/0â¦600 kcmil aluminium/copper || 4 x AWG 3/0...500 kcmil copper
- Continuous Current Rating:
- 1
- Product Or Component Type:
- circuit breaker
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View
$33,945.00