Chillers

SMC Thermo-Chillers • Process Cooling

SMC Industrial Chillers - Precision Process Cooling, End to End

Shop the full SMC thermo-chiller catalog: low-GWP refrigerated units, high-performance heat exchangers, rack-mount systems, Peltier benchtop chillers, SEMI-standard semiconductor chillers, and factory spare parts. 760 SKUs across 14 series, from 0.2 kW benchtop units to 30.5 kW inverter-driven production chillers.

Find Your Chiller → Request a Sizing Review
760
SKUs In-Catalog
14
Chiller Series
0.2 - 30.5
kW Cooling Range
±0.01°C
Tightest Stability
Authorized
SMC Distributor

SMC builds three kinds of process cooling, and the difference decides your series: refrigerated chillers (compressor cycle, loads above roughly 1 kW, set points below ambient), Peltier Thermo-cons (no compressor, no refrigerant, under 1.2 kW, tightest stability in the catalog), and heat exchangers (facility water as the heat sink, the only family that reaches 90°C). Pick a subcategory below, or use the filters on the left to narrow by series, capacity, cooling method, or refrigerant. Full selection guide, series table, and FAQ are below the product grid.

Shop by Subcategory

Seven Chiller Subcategories. One Click to the Right Fit.

Most Popular

Low GWP Chillers (286)

R-454C, R-32, and CO₂ refrigerants. Drop-in replacements for legacy HFC units. EPA AIM Act and CARB compliant. 1.2 to 30.5 kW across HRSF, HRSC, HRSHF, HRRF, HRZC, and HRLF.

Shop Low GWP →
General Purpose

General Purpose Chillers (259)

Refrigerated thermo-chillers for machine tools, laser equipment, welding, and production cooling. HRSF, HRSC, HRSHF, HRSE, and HRLF. 1.3 to 30.5 kW, single- or three-phase, ±0.1°C PID control.

Shop General Purpose →
Heat Exchanger

Heat Exchangers (232)

HRW series. Compressor-free thermo-coolers that use facility water as the heat sink. 1 to 30 kW, 20 to 90°C set range, ±0.3°C. Runs DI water, glycol, or fluorinated fluids. The high-temperature option.

Shop Heat Exchangers →
19-inch Rack

Rack Mount Chillers (118)

Fits a standard 19-inch instrumentation rack. HECR Peltier Thermo-cons (0.2 to 1.2 kW, refrigerant-free), HRR refrigerated units (0.2 to 5 kW), and HRRF low-GWP R-454C (1.2 to 1.8 kW). RS-232C/RS-485.

Shop Rack Mount →
Lab & Bench

Benchtop Chillers (36)

Peltier Thermo-cons. No compressor, no refrigerant, low vibration.
HEC precision (25)HED chemical (7)HEB bath (4)

Shop Benchtop →
Semiconductor

SEMI Standard Chillers (34)

SEMI S2, S8, F47 for fab use. HRZC double-inverter on CO₂ (GWP 1), -20 to 90°C, fluorinated fluid or glycol. Legacy HRZ-F F-Gas units for existing installs.

Shop SEMI Standard →
Service

Spare Parts (81)

Factory-original SMC replacement parts: pumps, panels, sensors, breakers, piping assemblies, DI resin cartridges, and controller modules. Keep the installed base running while planning the next upgrade.

Shop Spare Parts →

Not sure which family?

Three questions get you to one or two series: how much heat are you rejecting, is your set point above or below ambient, and what fluid is in the loop. If the answer is "under 1 kW and I cannot have a compressor," you want a Peltier Thermo-con. If it is "20 to 90°C and I have facility water," you want the HRW heat exchanger. Everything else is refrigerated.

Jump to the selection guide →

The Full SMC Chiller Lineup

One Authorized Distributor. Every SMC Thermo-Chiller Family.

An industrial chiller removes heat from a process or piece of equipment and rejects it to the surrounding environment. SMC builds three distinct types, and the difference matters when you specify: refrigerated chillers use a closed vapor-compression cycle for heat loads above roughly 1 kW and set points below ambient; Peltier Thermo-cons use thermoelectric modules with no compressor and no refrigerant at all; and heat exchangers reject heat to facility water without a compression cycle.

The catalog spans 0.2 kW benchtop Peltier units for analytical instruments, 19-inch rack systems for test labs, compact 1.3 to 5.9 kW refrigerated units for machine tools and laser processing, 15 to 30.5 kW inverter-driven chillers for high-heat production lines, high-temperature heat exchangers running to 90°C, and SEMI-certified fab chillers on fluorinated coolants.

Automation Distribution carries the full catalog, including the low-GWP lineup (R-454C, R-32, and CO₂) that meets EPA AIM Act, CARB, and EU F-Gas thresholds. If you are replacing a legacy HRS, HRZ, HRL, or HRSH unit, we can map your existing model to its low-GWP successor.


Chiller Selection Basics

Three Decisions That Narrow the Catalog Fast

Decision 1

Air-Cooled vs. Water-Cooled

Air-cooled units dissipate heat into ambient air via fans. Simpler install, no facility water needed, but sensitive to ambient temperature.

Water-cooled units reject heat to a facility loop or cooling tower. Higher efficiency at high loads, quieter, but requires water infrastructure. HRW and HRZC are water-cooled only.

Decision 2

Refrigerated, Peltier, or Heat Exchanger

Refrigerated (HRSF, HRSC, HRSHF, HRSE, HRR, HRRF, HRLF, HRZC) use a compressor cycle for loads above roughly 1 kW and set points below ambient.

Peltier Thermo-cons (HEC, HECR, HED, HEB) are refrigerant-free and compressor-free. Tightest stability in the catalog, low vibration, no AIM Act exposure. Under 1.2 kW.

Heat exchangers (HRW) use facility water as the heat sink. No compressor, and the only family that runs to 90°C.

Decision 3

Standard Coolant vs. DI / Fluorinated

Water / glycol covers most machine tool, laser, and general process loops.

Deionized water requires copper-free wetted materials. Available on HRW, HRSC, HRRF, and select HRZC.

Fluorinated fluids (Fluorinert, GALDEN) for semiconductor service use HRZC, HRZ-F, or HRW.


Series Quick Reference

All 14 SMC Chiller Series at a Glance

Series Type Capacity Refrigerant Best Fit
HRW Heat exchanger, no compressor 1 - 30 kW None High-temp process to 90°C, facility-water sites, DI and fluorinated service
HRSF Refrigerated, low GWP 1.3 - 20.5 kW R-454C (GWP 146) Machine tools, lasers, general manufacturing. HRS successor.
HRSC Refrigerated, CO₂ 1.3 - 11.5 kW CO₂ / R-744 (GWP 1) Lowest GWP, non-flammable A1 facilities, air-freight eligible
HECR Peltier Thermo-con, rack mount 0.2 - 1.2 kW None 19-inch rack, refrigerant-free, ±0.01 to 0.03°C, low vibration
HRR Refrigerated, rack mount 0.2 - 5 kW Legacy HFC Existing rack installs. See HRRF for the low-GWP successor.
HRZC SEMI, double inverter 2 - 10 kW CO₂ / R-744 (GWP 1) Semiconductor fab, fluorinated fluids, -20 to 90°C, SEMI S2/S8/F47
HEC Peltier Thermo-con, benchtop 0.2 - 1.2 kW None Analytical instruments, built-in equipment cooling, refrigerant-free
HRSHF Refrigerated, smart inverter 15.7 - 30.5 kW R-32 (GWP 675) Large-capacity production cooling, IPX4 outdoor-rated, HRSH successor
HRSE Refrigerated, basic compact 1 - 5 kW Legacy HFC Cost-sensitive general cooling, air-cooled only, 100 to 240 VAC
HRRF Refrigerated, rack mount, low GWP 1.2 - 1.8 kW R-454C (GWP 146) Labs, test equipment, space-constrained installs. HRR successor.
HED Peltier Thermo-con, chemical 0.3 - 0.9 kW None Direct temperature control of chemical liquids. Fluoropolymer heat exchanger.
HEB Peltier thermoelectric bath 0.2 kW None Immersion and sample conditioning. Compact, low noise, uniform bath temperature.
HRZ-F SEMI, legacy F-Gas 2 - 10 kW EU F-Gas compliant Existing SEMI installs, fluorinated and glycol service
HRLF Refrigerated, dual channel 20.5 kW + 1 kW R-454C (GWP 146) High-power fiber, CO₂, and YAG laser cooling. Oscillator plus optical head.

Legacy HRS, HRZ, HRL, and HRSH series remain supported for existing installations. Browse Spare Parts or contact us for replacement sizing.


Specifying a New Chiller in 2026?

Start With the Low GWP Lineup

The EPA HFC Management Rule took effect January 1, 2026, and the Technology Transitions Rule caps most new industrial process chillers at 700 GWP. SMC's low-GWP R-454C, R-32, and CO₂ chillers are engineered as drop-in replacements for legacy HFC units - same footprint, same port sizes, same performance. Peltier Thermo-cons and HRW heat exchangers sit outside the rule entirely: no refrigerant, no compressor, nothing to transition.

Browse Low GWP →

Common Applications

Where SMC Chillers Go to Work

Machine Tool / CNC

Spindle, coolant, and hydraulic cooling on mills, lathes, grinders. HRSF or HRSC for most platforms.

Laser Processing

Fiber, CO₂, YAG cutting and welding. HRLF dual-channel for oscillator plus optical head.

Semiconductor Fab

Wafer processing, etch, CVD, metrology. HRZC on CO₂ or HRZ-F for SEMI S2/S8/F47.

High-Temp Process

Set points to 90°C where refrigeration will not reach. HRW heat exchangers on facility water.

Lab & Analytical

Instruments, chambers, test benches. HEC benchtop Thermo-cons and HECR or HRRF rack units.

Wet Chemistry

Direct control of aggressive process liquids. HED chemical Thermo-cons with fluoropolymer heat exchangers.

EV / Battery

Formation, cycle testing, thermal shock chambers. HRSHF large-capacity inverter units.

Plastics & Extrusion

Mold, platen, melt-stream, and granulator cooling on injection and extrusion lines.


Frequently Asked Questions

Industrial Chillers: Common Questions

What is an industrial chiller and how does it work?

An industrial chiller removes heat from a process fluid or piece of equipment and rejects it to the surrounding environment. Refrigerated chillers use a closed vapor-compression cycle: refrigerant absorbs heat from the process fluid at the evaporator, a compressor raises its pressure and temperature, and an air- or water-cooled condenser dissipates that heat before the refrigerant returns to the evaporator. Peltier Thermo-cons and heat exchangers move heat without a compression cycle at all.

What is a Thermo-con, and how is it different from a Thermo-chiller?

A Thermo-con is SMC's Peltier-type temperature control unit. It places a thermoelectric module between heat exchangers for the circulating fluid and the facility water, then controls the DC supplied to that module to hold the outlet temperature. There is no compressor and no refrigerant, so it is quieter, lower-vibration, holds tighter stability (±0.01 to 0.03°C), and sits entirely outside refrigerant regulation. The tradeoff is capacity: Thermo-cons top out around 1.2 kW, where refrigerated Thermo-chillers run to 30.5 kW. The HEC, HECR, HED, and HEB series are Thermo-cons.

What types of SMC chillers are available?

Automation Distribution carries seven SMC chiller subcategories: Low GWP Chillers (R-454C, R-32, CO₂), General Purpose Chillers, Heat Exchangers, Rack Mount Chillers, Benchtop Chillers, SEMI Standard Chillers, and Spare Parts. Those cover 14 series and 760 SKUs.

How do I choose the right chiller for my application?

Start with five inputs: required cooling capacity (kW or BTU/hr), process fluid set point, ambient conditions at the install location, fluid type (water, glycol, DI water, fluorinated), and facility constraints (available power, footprint, noise, indoor/outdoor, flammable-refrigerant policy). Those five narrow 760 SKUs to one or two series quickly. Share your current chiller model number or the heat load of the equipment you are cooling and we will map it.

What is the difference between air-cooled and water-cooled chillers?

Air-cooled chillers dissipate heat into ambient air using integrated fans. They are simpler to install and need no facility water loop, but efficiency drops as ambient temperature rises. Water-cooled chillers reject heat to a facility loop or cooling tower: higher efficiency at high loads, quieter, more stable in hot environments, but they require an accessible water source. Most refrigerated series offer both. HRW and HRZC are water-cooled only.

How tight is temperature control across the range?

It varies by technology, and the difference is worth knowing before you specify. Peltier Thermo-cons (HEC, HECR, HED, HEB) hold ±0.01 to 0.03°C - the tightest in the catalog. Refrigerated thermo-chillers (HRSF, HRSC, HRSHF, HRRF, HRLF) hold ±0.1°C. SEMI HRZC units hold ±0.02°C under stable load. HRW heat exchangers hold ±0.3°C, trading stability for a 20 to 90°C range no refrigerated unit reaches. All series use PID control with multi-alarm monitoring and support RS-232C/RS-485 serial, contact I/O, or analog for PLC and HMI integration.

Should I buy a new high-GWP chiller or a low-GWP model?

For new purchases in 2026 and beyond, the practical answer is low-GWP. The EPA Technology Transitions Rule caps most new industrial process chillers at 700 GWP, the HFC Management Rule is in effect, and state-level regulations (CARB in particular) are actively enforced. SMC's low-GWP lineup is engineered as drop-in replacements for legacy HFC units with matching dimensions and performance. Existing installed chillers are grandfathered and can run to end of life. Worth noting: Peltier Thermo-cons and HRW heat exchangers use no refrigerant at all, so they sit outside the rule entirely.

What maintenance do SMC chillers require?

Routine maintenance includes checking circulating fluid level, inspecting and cleaning the condenser coil or water strainer, verifying flow and pressure, and replacing in-line filters or DI resin cartridges per the model manual. Most wear items are available as factory-original spare parts. Peltier Thermo-cons have fewer moving parts than refrigerated units - no compressor - which is part of their reliability case.

Does Automation Distribution provide chiller sizing and technical support?

Yes. As an authorized SMC distributor, we provide pre-sale sizing reviews, replacement mapping for legacy HRS, HRZ, HRL, and HRSH units, lead-time confirmation, and post-sale technical support. Contact our team with your current chiller model, heat load, and fluid type, or use the SMC Thermo-Chiller Model Selection Software to configure online.

Not Sure Which Chiller Fits?

Share your current chiller model number, heat load, set-point temperature, and process fluid. Our application team will confirm the right SMC series, verify drop-in fit against your existing footprint, and provide lead times.

Request a Chiller Evaluation → Read the 2026 Transition Guide →