Lutze 728753 dra30-24

(No reviews yet) Write a Review
SKU:
728753
Condition:
New
QN-QUOTE-REQUEST:
true
$48.92

Description

Technical Data

Input

Number of phases
1
Rated voltage UN
AC 100??240 V
Operation voltage range
AC 85??264 V / DC 90??375 V
Line frequency
47??63 Hz
Rated current IN
360 mA @ AC 115 V / 190 mA @ AC 230 V
Inrush current
20 A @ AC 115 V / 40 A @ AC 230 V
Internal fuse
2 A Typ-T AC 250 V
External fuse
Mini-circuit breaker: B 4 A

Output

Rated voltage UN
DC24V
Rated current IN
1,25 A
Heat dissipation
5.5 W @ AC 230 V
Setting range Uout min./Uout max.
24-28 V
Accuracy
??ñ1 %
Load regulation
??ñ0.5 %
Line regulation
??ñ0.5 %
Rise time
1 s
Temperature coefficient
??ñ0.03 % / ???C
Ripple and Noise
<50 mV
Hold up time
20 ms @ 115 V / 30 ms @ 230 V
Status indication DC ON LED green
?19.2 V
Parallel / redundant mode
max. 2 devices / via external decoupling diodes
Efficiency
86 %
Over voltage protection
125??137 %
Rated over load protection
110??140 %
Short circuit
Hiccup Mode

Monitoring

DC ON Control (Rdy)
Open Collector
Switching voltage
DC 24 V
Switching current
?35 mA
Isolation voltage
none

General

Switching frequency
approx. 80 kHz
Insulation voltage input / output
AC 3.0 kVeff
Insulation voltage input / ground
AC 1.5 kVeff
Insulation resistance at DC 500 V
100 M?
Derating
Capacity: -2.5 %/???C starting at 60 ???C
Operation temperature range
-25 ???C ?? +70 ???C (Derating)
Storage temperature range
-25???C??85???C
MTBF
588000 h
Relative air humidity
20 ?? 90 % RH, not condensing
Cooling
Air convection, 25 mm clearance all-round
Housing material
Plastic
Mounting
  • DIN rail mountable TS35
  • (EN 60715)
Application height
2000 m
Installation position
vertical
Protection class
IP20
Protection class
II (SELV, PELV)
Over voltage category
II
Degree of polution
2
Weight
0,29 kg/piece
Connection type
  • Spring terminal
  • 0.20 mm2 ?? 2.0 mm2
Dimensions (w ????? h ????? d)
40,5?????90?????115 mm
Approvals
  • UL 508 listed
  • UL 60950-1
  • EN 60950-1
  • EN 61000-6-3
  • EN 55022 Class B
  • EN 61000-3-2
  • EN 61000-3-3
  • EN 55024
  • EN 61000-6-2
  • EN 61000-4-2
  • EN 61000-4-3
  • EN 61000-4-4
  • EN 61000-4-5
  • EN 61000-4-6
  • EN 61000-4-8
  • EN 61000-4-11
PU
1 piece
Dimensions
PIN assignment
Derating
Redundant operation
Short circuit characteristics

View AllClose