Description
Technical Data
Input
Input variable
Analogue signals
Measurement input
0???10 V, 0???20 mA, 4???20 mA adjustable via switch
Galvanic isolation I/O
4-way isolation
Parameterisation
DIP switch
Zero /Span
Production comparison
Input resistance
500 k? @ 0???10 V, 100 ? @ 0???20 mA, 100 ? @ 4???20 mA
Output
Output signal
0???10 V, 0???20 mA, 4???20 mA
Max. load impedance at I-output
400 ? @ 0???20 mA, 4???20 mA
Min. load impedance at U-output
2 k? @ 0???10 V
Limitation for exceeding measurement range
yes, switchable
max. modulation range/output signal/output current
10.5 V @ 0???10 V, 21 mA @ 0???20 mA, 4???20 mA
Residual ripple
<20 mVeffeff
Parameterisation
DIP switch
Operating data
Accuracy
0.1 % FSR @ 23 ???C
Linearity error
??ñ0.1 % FSR
Critical frequency
30 Hz (filter off), 5 Hz (filter on)
General
Rated voltage UN
DC 24 V
Operation voltage range
16.8???30 V
Rated current
13 mA
Status indication
LED green/red
Input/output protection
Overvoltage DC 30 V, short circuit-proof output
Temperature error
<150 ppm FSR
Data storage
Flash
Insulation voltage input / output
2.5 kVeff
Resolution
16-bit
Configuration
Switch
Housing material
PA 6.6 (UL 94 V-0)
Color of the housing
light grey
Mounting
- DIN rail mountable TS35
- (EN 60715)
Protection class
IP20
Installation position
any
Connection type
- Screw terminal
- 0.14 mm2 ??? 1.5 mm2
Operation temperature range
-40 ???C ??? +70 ???C
Storage temperature range
-40???C???85???C
Dimensions (w ?? h ?? d)
6,2??90??115,5 mm
Weight
0,05 kg/piece
PU
1 piece
Approvals
- cULus (E135145) in preparation
- Cl.1 Div2, Gr. A, B, C, D, T4A (E319134) in preparation
- GL
Standards
EN 60947-5-1