Schneider Electric

Schneider Electric ABE7S16E2E1 Bas Rel St W10 16I 48Vdc Isolated

(No reviews yet) Write a Review
SKU:
ABE7S16E2E1
UPC:
3389110546255
Condition:
New
Standards:
IEC 61131-2 Type 2
Minimum Switching Current:
1 mA for PLC end
Current State 1 Guaranteed:
>= 6 mA sensor end)
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Resistance To Electrostatic Discharge:
4 kV contact) level 3 IEC 61000-4-2 || 8 kV air) level 3 IEC 61000-4-2
Net Weight:
0.37 kg
Warranty:
18 months
Number Of Terminal Per Channel:
2
Pollution Degree:
2 IEC 60664-1
Resistance To Fast Transients:
2 kV level 3 IEC 61000-4-4
Ambient Air Temperature For Operation:
-5-60 °C IEC 61131-2
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Connections - Terminals:
screw type terminals, 1 x 0.09...1 x 1.5 mm², 0.09-1.5 mm² AWG 28...AWG 16) flexible with cable end || screw type terminals, 1 x 0.14...1 x 2.5 mm², 0.14-2.5 mm² AWG 26...AWG 12) solid || screw type terminals, 1 x 0.14...1 x 2.5 mm², 0.14-2.5 mm
Supply Voltage Limits:
19-30 V DC PLC end)IEC 61131-2
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Range Of Product:
Modicon ABE7
Dielectric Strength:
2000 V 50/60 Hz IEC 60947-1
Number Of Channels:
16
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Response Time:
<= 0.05 ms from state 0 to 1 || <= 0.4 ms from state 1 to 0
Terminal Block Type:
removable
Rohs Exemption Information:
Yes
Mercury Free:
Yes
Switching Frequency:
<= 1000 Hz 50 %
Environmental Disclosure:
ENVPEP121229EN
Product Or Component Type:
solid state input relay sub-base
Product Certifications:
CSA || UL || DNV || GL || EAC
Circularity Profile:
ENVEOLI1212029EN
Ip Degree Of Protection:
IP2X conforming to IEC 60529
China Rohs Regulation:
X
Ambient Air Temperature For Storage:
-40-80 °C IEC 61131-2
Protection Type:
internal fuse 1 A 5 x 20 mm fast blow PLC end || adjustable by external fuse fast blow sensor end
Current Per Channel:
0.013 A
Vibration Resistance:
2 gn 10-150 Hz)IEC 60068-2-6
Resistance To Radiated Fields:
10 V/m 26000000-1000000000 Hz)IEC 61000-4-3 level 3
[Uimp] Rated Impulse Withstand Voltage:
2.5 kV IEC 60947-1
Installation Category:
II IEC 60664-1
Tightening Torque:
0.6 N.m flat Ø 3.5 mm
[Us] Rated Supply Voltage:
24 V DC PLC end) || 48 V DC sensor end)
Voltage State 1 Guaranteed:
>= 30 V sensor end
Fixing Mode:
by clips 35 mm symmetrical DIN rail) || by screws solid plate with fixing kit)
[Ui] Rated Insulation Voltage:
2000 V
Resistance To Incandescent Wire:
750 °C IEC 60695-2-11
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Isolation Plc/Operative Part:
yes
Sustainable Offer Status:
Green Premium product
Maximum Switching Current:
15 mA PLC end)
Datasheet:
View
$1,497.00