
Schneider Electric ABE7S16E2E1 Bas Rel St W10 16I 48Vdc Isolated
Schneider Electric
$1,497.00
sub-base - soldered solid state output relay ABE7 - 16 inputs - 48 V DC
- Standards:
- IEC 61131-2 Type 2
- Minimum Switching Current:
- 1 mA for PLC end
- Current State 1 Guaranteed:
- >= 6 mA sensor end)
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Resistance To Electrostatic Discharge:
- 4 kV contact) level 3 IEC 61000-4-2 || 8 kV air) level 3 IEC 61000-4-2
- Net Weight:
- 0.37 kg
- Warranty:
- 18 months
- Number Of Terminal Per Channel:
- 2
- Pollution Degree:
- 2 IEC 60664-1
- Resistance To Fast Transients:
- 2 kV level 3 IEC 61000-4-4
- Ambient Air Temperature For Operation:
- -5-60 °C IEC 61131-2
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Connections - Terminals:
- screw type terminals, 1 x 0.09...1 x 1.5 mm², 0.09-1.5 mm² AWG 28...AWG 16) flexible with cable end || screw type terminals, 1 x 0.14...1 x 2.5 mm², 0.14-2.5 mm² AWG 26...AWG 12) solid || screw type terminals, 1 x 0.14...1 x 2.5 mm², 0.14-2.5 mm
- Supply Voltage Limits:
- 19-30 V DC PLC end)IEC 61131-2
- Shock Resistance:
- 15 gn 11 ms IEC 60068-2-27
- Range Of Product:
- Modicon ABE7
- Dielectric Strength:
- 2000 V 50/60 Hz IEC 60947-1
- Number Of Channels:
- 16
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Response Time:
- <= 0.05 ms from state 0 to 1 || <= 0.4 ms from state 1 to 0
- Terminal Block Type:
- removable
- Rohs Exemption Information:
- Yes
- Mercury Free:
- Yes
- Switching Frequency:
- <= 1000 Hz 50 %
- Environmental Disclosure:
- ENVPEP121229EN
- Product Or Component Type:
- solid state input relay sub-base
- Product Certifications:
- CSA || UL || DNV || GL || EAC
- Circularity Profile:
- ENVEOLI1212029EN
- Ip Degree Of Protection:
- IP2X conforming to IEC 60529
- China Rohs Regulation:
- X
- Ambient Air Temperature For Storage:
- -40-80 °C IEC 61131-2
- Protection Type:
- internal fuse 1 A 5 x 20 mm fast blow PLC end || adjustable by external fuse fast blow sensor end
- Current Per Channel:
- 0.013 A
- Vibration Resistance:
- 2 gn 10-150 Hz)IEC 60068-2-6
- Resistance To Radiated Fields:
- 10 V/m 26000000-1000000000 Hz)IEC 61000-4-3 level 3
- [Uimp] Rated Impulse Withstand Voltage:
- 2.5 kV IEC 60947-1
- Installation Category:
- II IEC 60664-1
- Tightening Torque:
- 0.6 N.m flat à 3.5 mm
- [Us] Rated Supply Voltage:
- 24 V DC PLC end) || 48 V DC sensor end)
- Voltage State 1 Guaranteed:
- >= 30 V sensor end
- Fixing Mode:
- by clips 35 mm symmetrical DIN rail) || by screws solid plate with fixing kit)
- [Ui] Rated Insulation Voltage:
- 2000 V
- Resistance To Incandescent Wire:
- 750 °C IEC 60695-2-11
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Isolation Plc/Operative Part:
- yes
- Sustainable Offer Status:
- Green Premium product
- Maximum Switching Current:
- 15 mA PLC end)
- Datasheet:
- View