Schneider Electric ATS01N222RT Soft-Start Stop 22A 440 480V
Schneider Electric
$262.80
This Altistart 01 soft starter is DIN rail mounted and can feed 3-phase asynchronous motors with a rating up to 22A. This Altistart 01 can be used for a motor rated power up to 5.5kW or 7.5hp for 3-phase (200V to 240V AC). This DIN rail mounted soft starter is designed to enable smooth start for simple machines such as conveyors, conveyor belts, pumps, fans, compressors, automatic doors and gates, small cranes and belt-driven machinery. It is 45mm wide, this makes it one of the smallest soft starters on the market; it can be installed nearly everywhere. It features an Integrated bypass, this reduces noise and decreases heat dissipation. Simple setup with only 2 settings: possible to configure by non-specialists. It provides smooth starting for your machinery, avoiding mechanical stresses and extending their service life.
- Supply Frequency:
- 50...60 Hz - 5...5 %
- Pollution Degree:
- 2 EN/IEC 60947-4-2
- Utilisation Category:
- AC-53B EN/IEC 60947-4-2
- Range Of Product:
- Altistart 01
- Ip Degree Of Protection:
- IP20
- Function Available:
- integrated bypass
- Net Weight:
- 0.56 kg
- Electrical Connection:
- 4 mm screw clamp terminal - rigid 1 1...10 mm² AWG 8 power circuit || screw connector - rigid without cable end 1 0.5...2.5 mm² AWG 14 control circuit || 4 mm screw clamp terminal - rigid 2 1...6 mm² AWG 10 power circuit || screw connector - rigid
- China Rohs Regulation:
- X
- Device Short Name:
- ATS01
- Product Or Component Type:
- soft starter
- Reach Free Of Svhc:
- Yes
- Discrete Input Voltage:
- 24...40 V
- Standards:
- EN/IEC 60947-4-2
- Starting Torque:
- 30...80 % of starting torque of motor connected directly on the line supply
- Discrete Input Type:
- logic LI1, LI2, BOOST) stop, run and boost on start-up functions <= 8 mA 27 kOhm
- Phase:
- 3 phase
- Product Specific Application:
- simple machine
- Maximum Switching Current:
- relay outputs 2 A 250 V AC cos phi = 0.5 20 ms inductive || relay outputs 2 A 30 V DC cos phi = 0.5 20 ms inductive
- Operating Altitude:
- <= 3280.84 ft (1000 m) without derating || > 3280.84 ft (1000 m) with current derating of 2.2 % per additional 100 m
- Operating Position:
- vertical +/- 10 degree
- Product Destination:
- asynchronous motors
- Vibration Resistance:
- 1 gn 13-150 Hz)EN/IEC 60068-2-6 || 1.5 mm peak to peak 3-13 Hz)EN/IEC 60068-2-6
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Ambient Air Temperature For Storage:
- -25-70 °C EN/IEC 60947-4-2
- Discrete Output Type:
- open collector logic LO1 end of starting signal || relay outputs R1A, R1C NO
- Minimum Switching Current:
- 10 mA 6 V DC relay outputs
- Output Voltage:
- <= power supply voltage
- Mercury Free:
- Yes
- Electromagnetic Compatibility:
- conducted and radiated emissions level B CISPR 11 || conducted and radiated emissions level B IEC 60947-4-2 || damped oscillating waves level 3 IEC 61000-4-12 || electrostatic discharge level 3 IEC 61000-4-2 || EMC immunity level 3 EN 50082-1 || EMC
- Display Type:
- 1 LED Green)starter powered up || 1 LED Yellow)nominal voltage reached
- Warranty:
- 18 months
- Reach Regulation:
- Free of Substances of Very High Concern above the threshold
- Product Certifications:
- UL || CCC || C-tick || GOST || CSA || B44.1-96/ASME A17.5 for starter wired to the motor delta terminal
- Current Consumption:
- 110 A at nominal load
- Height:
- 154 mm
- Type Of Start:
- start with voltage ramp
- Deceleration Time Symb:
- adjustable from 1 to 10 s
- Compatibility Code:
- ATS01N2
- Discrete Input Logic:
- positive LI1, LI2, BOOST < 5 V <= 0.2 mA > 13 V, >= 0.5 mA
- Discrete Output Voltage:
- 24 V 6...30 V) open collector logic
- Depth:
- 131 mm
- Shock Resistance:
- 15 gn 11 ms EN/IEC 60068-2-27
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Power Dissipation In W:
- 124.5 W in transient state || 4.5 W at full load and at end of starting
- Icl Starter Rating:
- 22 A
- Relative Humidity:
- 5-95 % without condensation or dripping water EN/IEC 60068-2-3
- Marking:
- CE
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Assembly Style:
- with heat sink
- Tightening Torque:
- 0.5-0.5 N.m || 1.9-2.5 N.m
- Network Frequency:
- 47.5...63 Hz
- Maximum Horse Power Rating:
- 10 hp, 3 phase 460...480 V || 15 hp, 3 phase 460...480 V
- Starting Time:
- 1 s / 100 || 5 s / 20 || 10 s / 10 || adjustable from 1 to 10 s
- Supply Voltage Limits:
- 414-528 V
- Discrete Output Current:
- 2 A DC-13 || 3 A AC-15
- Ambient Air Temperature For Operation:
- -10-40 °C without derating) || 40-50 °C with current derating of 2 % per °C)
- Toxic Heavy Metal Free:
- Yes
- [Uc] Control Circuit Voltage:
- built into the starter
- Width:
- 45 mm
- Rohs Exemption Information:
- Yes
- [Us] Rated Supply Voltage:
- 460...480 V - 10...10 %
- Catalog:
- View
- Datasheet:
- View