Schneider Electric ATV212HU15N4 Atv212 1,5Kw 2Hp 480V Tri Cem Ip20

(No reviews yet) Write a Review
SKU:
ATV212HU15N4
UPC:
3606480322457
Condition:
New
Dielectric Strength:
3535 V DC between earth and power terminals || 5092 V DC between control and power terminals
Device Short Name:
ATV212
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Warranty:
18 months
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immu
Option Card:
communication card LonWorks
Transmission Frame:
RTU
Electrical Connection:
VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 2.5-2.5 mm² / AWG 14 || L1/R, L2/S, L3/T terminal 6-6 mm² / AWG 10
Switching Frequency:
6...16 kHz adjustable || 12...16 kHz with derating factor
Transient Overtorque:
120-120 % of nominal motor torque +/- 10 % 60 s
Number Of Addresses:
1-247
Motor Power Kw:
1.5 kW
Environmental Characteristic:
classes 3C1 IEC 60721-3-3 || classes 3S2 IEC 60721-3-3
Assembly Style:
with heat sink
Physical Interface:
2-wire RS 485
Product Or Component Type:
variable speed drive
Product Specific Application:
pumps and fans in HVAC
Maximum Horse Power Rating:
2 hp
Power Dissipation In W:
78 W
Product Certifications:
UL || NOM 117 || C-tick || CSA
Speed Range:
45301
Motor Slip Compensation:
adjustable || not available in voltage/frequency ratio motor control || automatic whatever the load
Sampling Duration:
2 ms +/- 0.5 ms F discrete || 2 ms +/- 0.5 ms R discrete || 2 ms +/- 0.5 ms RES discrete || 3.5 ms +/- 0.5 ms VIA analog || 22 ms +/- 0.5 ms VIB analog
Analogue Input Type:
VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits || VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits || VIB configurable PTC probe 0...6 probes 1500 Ohm || VIA switch-configurable current 0...20 mA 250 Ohm 10 bits
Air Flow:
27 m3/h
Relative Humidity:
5-95 % without condensation IEC 60068-2-3 || 5-95 % without dripping water IEC 60068-2-3
Prospective Line Isc:
5 kA
Pollution Degree:
2 IEC 61800-5-1
Depth:
150 mm
Functionality:
mid
Supply Voltage Limits:
323-528 V
Communication Port Protocol:
APOGEE FLN || BACnet || Modbus || LonWorks || METASYS N2
Apparent Power:
2.8 kVA 380 V
Maximum Transient Current:
4 A 60 s
Protection Type:
overheating protection drive || thermal power stage drive || short-circuit between motor phases drive || input phase breaks drive || overcurrent between output phases and earth drive || overvoltages on the DC bus drive || break on the control circuit
Braking To Standstill:
by DC injection
Width:
107 mm
Transmission Rate:
9600 bps or 19200 bps
Nominal Switching Frequency:
12 kHz
Speed Drive Output Frequency:
0.5-200 Hz
Ip Degree Of Protection:
IP20 on upper part without blanking plate on cover IEC 61800-5-1 || IP20 on upper part without blanking plate on cover IEC 60529 || IP21 IEC 61800-5-1 || IP21 IEC 60529 || IP41 on upper part IEC 61800-5-1 || IP41 on upper part IEC 60529
Emc Filter:
Class C2 EMC filter integrated
Analogue Input Number:
2
Data Format:
8 bits, 1 stop, odd even or no configurable parity
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Linearity Error:
VIA +/- 0.15 % of maximum value input || VIB +/- 0.15 % of maximum value input || FM +/- 0.2 % output
Rohs Exemption Information:
Yes
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Operating Altitude:
3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m || <= 3280.84 ft (1000 m) without derating
Discrete Input Logic:
positive logic (source) F, R, RES), <= 5 V, >= 11 V || negative logic (sink) F, R, RES), >= 16 V, <= 10 V
Net Weight:
2 kg
Supply Frequency:
50...60 Hz - 5...5 %
Type Of Cable:
without mounting kit 1 IEC cable 45 °C, copper 90 °C / XLPE/EPR || without mounting kit 1 IEC cable 45 °C, copper 70 °C / PVC || with UL Type 1 kit 3 UL 508 cable 40 °C, copper 75 °C / PVC
Power Range:
1.1-2 kW 380-440 V 3 phase || 1.1-2 kW 480-500 V 3 phase
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01 to 3200 s || automatic based on the load
Vibration Resistance:
1.5 mm 3-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)EN/IEC 60068-2-8
Discrete Output Type:
configurable relay logic FLA, FLC) NO - 100000 cycles || configurable relay logic FLB, FLC) NC - 100000 cycles || configurable relay logic RY, RC) NO - 100000 cycles
Frequency Resolution:
display unit 0.1 Hz || analog input 0.024/50 Hz
Communication Service:
read device identification (43) || time out setting from 0.1 to 100 s || monitoring inhibitable || write single register (06) || read holding registers (03) 2 words maximum || write multiple registers (16) 2 words maximum
Type Of Polarization:
no impedance
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Mercury Free:
Yes
Operating Position:
vertical +/- 10 degree
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
Insulation Resistance:
>= 1 mOhm 500 V DC for 1 minute
Maximum Switching Current:
5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R) || 5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R) || 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R) || 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
Accuracy:
+/- 0.6 % VIA) for a temperature variation 60 °C || +/- 0.6 % VIB) for a temperature variation 60 °C || +/- 1 % FM) for a temperature variation 60 °C
Standards:
EN 55011 class A group 1 || IEC 61800-3 environments 2 category C1 || EN 61800-3 category C3 || IEC 61800-3 || IEC 61800-3 environments 2 category C2 || IEC 61800-3 environments 1 category C3 || UL Type 1 || IEC 61800-3 environments 2 category C3 ||
Discrete And Process Manufacturing:
building - HVAC compressor for scroll || building - HVAC fan || building - HVAC pump
Ip Degree Of Protection:
IP21
Response Time:
FM 2 ms +/- 0.5 ms analog || FLA, FLC 7 ms +/- 0.5 ms discrete || FLB, FLC 7 ms +/- 0.5 ms discrete || RY, RC 7 ms +/- 0.5 ms discrete
Noise Level:
51 dB 86/188/EEC
Isolation:
electrical between power and control
Ambient Air Temperature For Storage:
-25-70 °C
Ambient Air Temperature For Operation:
-10-40 °C without derating) || 40-50 °C with derating factor)
Output Voltage:
<= power supply voltage
Connector Type:
1 open style || 1 RJ45
Marking:
CE
Minimum Switching Current:
3 mA 24 V DC configurable relay logic
Discrete Output Number:
2
Product Destination:
asynchronous motors
Height:
143 mm
Local Signalling:
for DC bus energized 1 LED (red)
Discrete Input Type:
F programmable 24 V DC level 1 PLC 4700 Ohm || R programmable 24 V DC level 1 PLC 4700 Ohm || RES programmable 24 V DC level 1 PLC 4700 Ohm
Phase:
3 phase
Analogue Output Number:
1
Network Frequency:
47.5...63 Hz
Speed Accuracy:
+/- 10 % of nominal slip 0.2 Tn to Tn
Supply:
internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection || internal supply 24 V DC 21-27 V), <200 A overload and short-circuit protection
Motor Starter Type:
variable speed drive
Tightening Torque:
1.3 N.m, 11.5 lb.in L1/R, L2/S, L3/T) || 0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
Torque Accuracy:
+/- 15 %
Line Current:
2.5 A 480 V || 3.2 A 380 V
Analogue Output Type:
FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits || FM switch-configurable current 0...20 mA 970 Ohm 10 bits
Asynchronous Motor Control Profile:
voltage/frequency ratio - Energy Saving, quadratic U/f || voltage/frequency ratio, 5 points || voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) || voltage/frequency ratio, 2 points || flux vector control without sensor, standar
China Rohs Regulation:
X
Range Of Product:
Altivar 212
Specific Application:
HVAC
Regulation Loop:
adjustable PI regulator
Continuous Output Current:
3.7 A 380 V || 3.7 A 460 V
$766.73

Description

This Altivar 212 variable speed drive can feed 3-phase asynchronous motors. Its protection index is IP21 and it has a built-in EMC filter. It works at a rated power up to 1.5kW / 2hp and a rated voltage from 380V to 480V AC. Its design is based on eco-energy with a reduction in energy consumption of up to 70% compared to a conventional control system. Thanks to its cable temperature rise reduction technology, the Altivar 212 drive offers immediate, disturbance-free operation avoiding additional options such as a line choke or DC choke to deal with current harmonics. It weighs 2kg and its dimensions are, 107mm wide, 143mm high, 150mm deep. It is specifically designed for the most common fluid management applications in tertiary sector buildings (HVAC) like heating, ventilation, air conditioning and pumping. It conforms to international standards IEC/EN 61800-5-1 and IEC/EN 61800-3 (immunity and conducted and radiated EMC emissions). It is also CE, UL, CSA, C-Tick and NOM certified. The Altivar 212 offers optional motor chokes which can increase the maximum cable lengths between the drive and the motor and limit disturbance at the motor terminals. It is designed to be mounted in vertical position (+/- 10 °) on a panel, thanks to 4 fixing holes. It can also be mounted directly on a 35 mm wide DIN rail, thanks to the kit VW3A31852, to order separately. The Altivar 212 drive can easily be adapted to all building management systems thanks to its numerous functions and communication protocols integrated as standard, Modbus, METASYS N2, APOGEE FLN P1 and BACnet.
View AllClose