Schneider Electric

Schneider Electric ATV630C11N4 Variable Speed Drive Ip00 110Kw 400V/480

(No reviews yet) Write a Review
SKU:
ATV630C11N4
UPC:
3.60648E+12
Condition:
New
Mercury Free:
Yes
Marking:
CE
Product Destination:
asynchronous motors || synchronous motors
Maximum Transient Current:
232.1 A 60 s normal duty) || 259.5 A 60 s heavy duty)
Analogue Input Number:
3
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Product Or Component Type:
variable speed drive
Vibration Resistance:
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Continuous Output Current:
211 A 2.5 kHz normal duty || 173 A 2.5 kHz heavy duty
Type Of Cooling:
forced convection
Discrete Output Number:
0
Input Compatibility:
DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
Discrete Input Logic:
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
Product Specific Application:
process and utilities
Line Current:
201 A 380 V normal duty) || 165 A 480 V normal duty) || 170 A 380 V heavy duty) || 143 A 480 V heavy duty)
Physical Interface:
Ethernet || 2-wire RS 485
Data Format:
8 bits, configurable odd, even or no parity
Transmission Frame:
RTU
Discrete Output Type:
relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Variant:
standard version
Emc Filter:
integrated 150 m IEC 61800-3 category C3
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Overvoltage Category:
III
[Us] Rated Supply Voltage:
380...480 V
Supply Frequency:
50...60 Hz - 5...5 %
Device Short Name:
ATV630
Maximum Output Frequency:
500 kHz
Power Range:
110-220 kW 380-440 V 3 phase || 110-220 kW 480-500 V 3 phase
Upgradeability:
Upgraded components available
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Sustainable Offer Status:
Green Premium product
Discrete Input Type:
DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Standards:
UL 508C || IEC 61800-3 || IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Mounting Mode:
wall mount
Environmental Disclosure:
ENVPEP1501011EN
Transmission Rate:
10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Isolation:
between power and control terminals
Rohs Exemption Information:
Yes
Discrete Input Logic:
16 preset speeds
Pollution Degree:
2
Electrical Connection:
control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || line side screw terminal 2 x 50...3 x 120 mm² 2 x AWG 1/0...2 x 300 kcmil || motor screw terminal 2 x 50...3 x 120 mm² 2 x AWG 1/0...2 x 300 kcmil
Phase:
3 phase
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Asynchronous Motor Control Profile:
constant torque standard || optimized torque mode || variable torque standard
Safety Function:
STO (safe torque off) SIL 3
Connector Type:
RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Range Of Product:
Altivar Process ATV600
Product Certifications:
ATEX zone 2/22 || ATEX INERIS || TÜV || CSA || UL || DNV-GL
Enclosure Mounting:
wall mounted
Maximum Thdi:
<48 % full load IEC 61000-3-12
Nominal Switching Frequency:
2.5 kHz
Pollution Degree:
2 IEC 61800-5-1
Number Of Addresses:
1-247 Modbus serial
Width:
320 mm
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Maximum Switching Current:
relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2
Prospective Line Isc:
50 kA
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Relay Output Type:
configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
Output Voltage:
<= power supply voltage
Frequency Resolution:
display unit 0.1 Hz || analog input 0.012/50 Hz
Operating Position:
vertical +/- 10 degree
Speed Drive Output Frequency:
0.1-500 Hz
Ip Degree Of Protection:
IP00IEC 61800-5-1 || IP00IEC 60529 || IP21 with kit VW3A9704)IEC 61800-5-1 || IP21 with kit VW3A9704)IEC 60529
Maximum Horse Power Rating:
150 hp normal duty || 125 hp heavy duty
Method Of Access:
slave Modbus TCP
China Rohs Regulation:
X
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Quantity Per Set:
1
Height:
852 mm
Motor Power Kw:
110 kW normal duty) || 90 kW heavy duty)
Analogue Output Number:
2
Braking To Standstill:
by DC injection
Ambient Air Temperature For Storage:
-40-70 °C
Volume Of Cooling Air:
600 m3/h
Discrete Input Number:
8
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Circularity Profile:
ENVEOLI1501011EN
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Noise Level:
69.9 dB
Regulation Loop:
adjustable PID regulator
Synchronous Motor Control Profile:
permanent magnet motor || synchronous reluctance motor
Ambient Air Temperature For Operation:
-15-50 °C without derating) || 50-60 °C with derating factor)
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
Switching Frequency:
2.5...8 kHz with derating factor || 2...8 kHz adjustable
Net Weight:
82 kg
Option Card:
slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A c
Discrete And Process Manufacturing:
building - HVAC compressor centrifugal || food and beverage processing other application || mining mineral and metal fan || mining mineral and metal pump || oil and gas fan || water and waste water other application || building - HVAC screw compresso
Motor Slip Compensation:
can be suppressed || not available in permanent magnet motor law || automatic whatever the load || adjustable
Type Of Polarization:
no impedance
Permissible Temporary Current Boost:
1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Noise Level:
69.9 dB 86/188/EEC
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
Depth:
390 mm
Relay Output Number:
3
Apparent Power:
121.8 kVA 480 V normal duty) || 102.6 kVA 480 V heavy duty)
Communication Port Protocol:
Modbus TCP || Ethernet || Modbus serial
Power Dissipation In W:
forced convection 2026 W 380 V 2.5 kHz
Local Signalling:
for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
Brochure:
View
Catalog:
View
Datasheet:
View
$17,630.94

Description

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 380V to 480V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 110kW / 150hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 90kW / 125hp for applications requiring significant overload (up to 150%). It weighs 82kg and its dimensions are, 320mm wide, 852mm high, 390mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
View AllClose