Schneider Electric ATV630D15M3 Variable Speed Drive Ip21 15Kw 200V/240V

(No reviews yet) Write a Review
SKU:
ATV630D15M3
UPC:
3606480701481
Condition:
New
Noise Level:
63.5 dB 86/188/EEC
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Analogue Input Number:
3
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Supply Frequency:
50...60 Hz - 5...5 %
Standards:
UL 508C || IEC 61800-3 || IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Discrete Output Number:
0
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Power Dissipation In W:
natural convection 87 W 200 V 4 kHz || forced convection 486 W 200 V 4 kHz
Transmission Frame:
RTU
Continuous Output Current:
63.4 A 4 kHz normal duty || 46.8 A 4 kHz heavy duty
Net Weight:
13.6 kg
Switching Frequency:
2...12 kHz adjustable || 4...12 kHz with derating factor
Type Of Polarization:
no impedance
Overvoltage Category:
III
Product Certifications:
ATEX zone 2/22 || TÜV || CSA || DNV-GL || UL || ATEX INERIS
Apparent Power:
18.9 kVA 240 V normal duty) || 14.3 kVA 240 V heavy duty)
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Ambient Air Temperature For Operation:
-15-50 °C without derating) || 50-60 °C with derating factor)
Degree Of Protection:
UL type 1 UL 508C
Noise Level:
63.5 dB
Product Destination:
asynchronous motors || synchronous motors
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immu
Width:
226 mm
Motor Power Kw:
15 kW normal duty) || 11 kW heavy duty)
Variant:
standard version
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Upgradeability:
Upgraded components available
Connector Type:
RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
Maximum Horse Power Rating:
20 hp normal duty || 15 hp heavy duty
Isolation:
between power and control terminals
Height:
673 mm
Asynchronous Motor Control Profile:
variable torque standard || constant torque standard || optimized torque mode
Rohs Exemption Information:
Yes
Maximum Thdi:
<48 % from 80...100 % of load IEC 61000-3-12
[Us] Rated Supply Voltage:
200...240 V
Method Of Access:
slave Modbus TCP
Maximum Output Frequency:
500 kHz
Discrete Input Type:
DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Nominal Switching Frequency:
4 kHz
Marking:
CE
Circularity Profile:
ENVEOLI1411001EN
Regulation Loop:
adjustable PID regulator
Product Or Component Type:
variable speed drive
Option Card:
slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A c
Line Current:
52.6 A 200 V normal duty) || 45.5 A 240 V normal duty) || 40.1 A 200 V heavy duty) || 34.3 A 240 V heavy duty)
Relay Output Number:
3
Data Format:
8 bits, configurable odd, even or no parity
Mounting Mode:
wall mount
Phase:
3 phase
Range Of Product:
Altivar Process ATV600
Synchronous Motor Control Profile:
permanent magnet motor || synchronous reluctance motor
Relay Output Type:
configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
Volume Of Cooling Air:
240 m3/h
Communication Port Protocol:
Ethernet || Modbus serial || Modbus TCP
Physical Interface:
Ethernet || 2-wire RS 485
Pollution Degree:
2
Sustainable Offer Status:
Green Premium product
Power Range:
15-25 kW 200-240 V 3 phase
Analogue Output Number:
2
Vibration Resistance:
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Depth:
271 mm
Discrete Input Logic:
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
Device Short Name:
ATV630
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
Discrete Input Number:
8
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Safety Function:
STO (safe torque off) SIL 3
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Environmental Disclosure:
ENVPEP1411001EN
Discrete And Process Manufacturing:
building - HVAC compressor centrifugal || food and beverage processing other application || mining mineral and metal fan || mining mineral and metal pump || oil and gas fan || water and waste water other application || building - HVAC screw compresso
Mercury Free:
Yes
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
[Us] Rated Supply Voltage:
200...240 V - 15...10 %
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
China Rohs Regulation:
X
Quantity Per Set:
1
Emc Filter:
without EMC filter
Discrete Input Logic:
16 preset speeds
Motor Slip Compensation:
can be suppressed || automatic whatever the load || not available in permanent magnet motor law || adjustable
Speed Drive Output Frequency:
0.1-500 Hz
Input Compatibility:
DI1...DI6 discrete input level 1 PLC IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
Discrete Output Type:
relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
Maximum Transient Current:
69.7 A 60 s normal duty) || 70.2 A 60 s heavy duty)
Ambient Air Temperature For Storage:
-40-70 °C
Prospective Line Isc:
50 kA
Operating Position:
vertical +/- 10 degree
Number Of Addresses:
1-247 Modbus serial
Local Signalling:
for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
Type Of Cooling:
forced convection
Permissible Temporary Current Boost:
1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Electrical Connection:
control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || line side screw terminal 25...50 mm² AWG 4...AWG 1 || motor screw terminal 25...50 mm² AWG 4...AWG 1
Pollution Degree:
2 IEC 61800-5-1
Maximum Switching Current:
relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Ip Degree Of Protection:
IP21IEC 61800-5-1 || IP21IEC 60529
Product Specific Application:
process and utilities
Transmission Rate:
10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Braking To Standstill:
by DC injection
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Output Voltage:
<= power supply voltage
Frequency Resolution:
display unit 0.1 Hz || analog input 0.012/50 Hz
Enclosure Mounting:
wall mounted
  • Schneider Electric ATV630D15M3 Variable Speed Drive Ip21 15Kw 200V/240V
  • Schneider Electric ATV630D15M3 Variable Speed Drive Ip21 15Kw 200V/240V
  • Schneider Electric ATV630D15M3 Variable Speed Drive Ip21 15Kw 200V/240V
$4,555.94

Description

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 200V to 240V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 15kW / 20hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 11kW / 15hp for applications requiring significant overload (up to 150%). It weighs 13.6kg and its dimensions are, 226mm wide, 673mm high, 271mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
View AllClose