Schneider Electric ATV630D15N4 Variable Speed Drive Ip21 15Kw 400V/480V
Schneider Electric
$4,123.35
This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It features 3 built-in RJ45 communication ports as standard, 1 Ethernet port, 2 serial ports. It works at a rated supply voltage from 380V to 480V AC. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 15kW / 20hp for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 11kW / 15hp for applications requiring significant overload (up to 150%). It weighs 13.6kg and its dimensions are, 211mm wide, 546mm high, 232mm deep. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. Accessories (fan kit, graphic display terminal) and options (I/O expansion modules, communication modules, EMC input filters) are available with Altivar Process ATV600 drives, depending on the drive rating. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
- Noise Level:
- 59.5 dB
- Switching Frequency:
- 2...12 kHz adjustable || 4...12 kHz with derating factor
- Speed Drive Output Frequency:
- 0.1-500 Hz
- Marking:
- CE
- Maximum Horse Power Rating:
- 20 hp normal duty || 15 hp heavy duty
- Transmission Rate:
- 10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
- China Rohs Regulation:
- X
- Safety Function:
- STO (safe torque off) SIL 3
- Mercury Free:
- Yes
- Electromagnetic Compatibility:
- electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
- Protection Type:
- thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Product Certifications:
- ATEX zone 2/22 || TÃV || ATEX INERIS || CSA || UL || DNV-GL
- Upgradeability:
- Upgraded components available
- Output Voltage:
- <= power supply voltage
- Refresh Time:
- relay output R1, R2, R3)5 ms +/- 0.5 ms)
- Local Signalling:
- for local diagnostic 3 LEDs || for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red)
- Product Specific Application:
- process and utilities
- Pollution Degree:
- 2 EN/IEC 61800-5-1
- Pollution Degree:
- 2
- Apparent Power:
- 19.4 kVA 480 V normal duty) || 15 kVA 480 V heavy duty)
- Overvoltage Category:
- III
- Physical Interface:
- Ethernet || 2-wire RS 485
- Motor Power Kw:
- 15 kW normal duty) || 11 kW heavy duty)
- Volume Of Cooling Air:
- 215 m3/h
- Product Destination:
- asynchronous motors || synchronous motors
- Number Of Addresses:
- 1-247 Modbus serial
- Noise Level:
- 59.5 dB 86/188/EEC
- Analogue Input Type:
- AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
- Maximum Transient Current:
- 34.9 A 60 s normal duty) || 35.3 A 60 s heavy duty)
- Asynchronous Motor Control Profile:
- constant torque standard || variable torque standard || optimized torque mode
- Ip Degree Of Protection:
- IP21IEC 61800-5-1 || IP21IEC 60529
- Product Or Component Type:
- variable speed drive
- Rohs Exemption Information:
- Yes
- Permissible Temporary Current Boost:
- 1.1 x In 60 s normal duty) || 1.5 x In 60 s heavy duty)
- Method Of Access:
- slave Modbus TCP
- Discrete Input Logic:
- 16 preset speeds
- Maximum Thdi:
- <48 % from 80...100 % of load IEC 61000-3-12
- Height:
- 546 mm
- Electrical Connection:
- control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16 || line side screw terminal 10...16 mm² AWG 8...AWG 6 || motor screw terminal 10...16 mm² AWG 8...AWG 6
- Maximum Output Frequency:
- 500 kHz
- [Us] Rated Supply Voltage:
- 380...480 V
- Exchange Mode:
- half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
- [Us] Rated Supply Voltage:
- 380...480 V - 15...10 %
- Insulation Resistance:
- > 1 MOhm 500 V DC for 1 minute to earth
- Relay Output Type:
- configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- Net Weight:
- 13.6 kg
- Operating Altitude:
- <= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
- Supply:
- external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Ambient Air Temperature For Operation:
- -15-50 °C without derating) || 50-60 °C with derating factor)
- Accuracy:
- +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
- Regulation Loop:
- adjustable PID regulator
- Supply Frequency:
- 50...60 Hz - 5...5 %
- Discrete Input Type:
- DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
- Acceleration And Deceleration Ramps:
- linear adjustable separately from 0.01...9999 s
- Synchronous Motor Control Profile:
- permanent magnet motor || synchronous reluctance motor
- Relative Humidity:
- 5-95 % without condensation IEC 60068-2-3
- Option Card:
- slot A communication module, Profibus DP V1 || slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A c
- Vibration Resistance:
- 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
- Continuous Output Current:
- 31.7 A 4 kHz normal duty || 23.5 A 4 kHz heavy duty
- Discrete Output Number:
- 0
- Type Of Cooling:
- forced convection
- Power Range:
- 15-25 kW 380-440 V 3 phase || 15-25 kW 480-500 V 3 phase
- Power Dissipation In W:
- natural convection 59 W 380 V 4 kHz || forced convection 366 W 380 V 4 kHz
- Operating Position:
- vertical +/- 10 degree
- Environmental Disclosure:
- ENVPEP1404008EN
- Analogue Input Number:
- 3
- Linearity Error:
- AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AO1, AO2 +/- 0.2 % analog output
- Variant:
- standard version
- Communication Port Protocol:
- Ethernet || Modbus serial || Modbus TCP
- Circularity Profile:
- ENVEOLI1404008EN
- Isolation:
- between power and control terminals
- Ambient Air Temperature For Storage:
- -40-70 °C
- Sustainable Offer Status:
- Green Premium product
- Line Current:
- 27 A 380 V normal duty) || 23.3 A 480 V normal duty) || 20.6 A 380 V heavy duty) || 18.1 A 480 V heavy duty)
- Quantity Per Set:
- 1
- Mounting Mode:
- wall mount
- Width:
- 211 mm
- Discrete Input Logic:
- positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
- Standards:
- UL 508C || EN/IEC 61800-3 || EN/IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || EN/IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
- Eu Rohs Directive:
- Pro-active compliance (Product out of EU RoHS legal scope)
- Type Of Polarization:
- no impedance
- Prospective Line Isc:
- 50 kA
- Discrete And Process Manufacturing:
- building - HVAC compressor centrifugal || food and beverage processing other application || mining mineral and metal fan || mining mineral and metal pump || oil and gas fan || water and waste water other application || building - HVAC screw compresso
- Discrete Output Type:
- relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
- Data Format:
- 8 bits, configurable odd, even or no parity
- Degree Of Protection:
- UL type 1 UL 508C
- Relay Output Number:
- 3
- Range Of Product:
- Altivar Process ATV600
- Sampling Duration:
- 2 ms +/- 0.5 ms DI1...DI4) - discrete input || 5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output
- Motor Slip Compensation:
- can be suppressed || adjustable || automatic whatever the load || not available in permanent magnet motor law
- Analogue Output Number:
- 2
- Minimum Switching Current:
- relay output R1, R2, R3 5 mA 24 V DC
- Frequency Resolution:
- display unit 0.1 Hz || analog input 0.012/50 Hz
- Shock Resistance:
- 15 gn 11 ms IEC 60068-2-27
- Discrete Input Number:
- 8
- Phase:
- 3 phase
- Transmission Frame:
- RTU
- Emc Filter:
- integrated 50 m EN/IEC 61800-3 category C2 || integrated 150 m EN/IEC 61800-3 category C3
- Maximum Switching Current:
- relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC || relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2
- Nominal Switching Frequency:
- 4 kHz
- Device Short Name:
- ATV630
- Braking To Standstill:
- by DC injection
- Enclosure Mounting:
- wall mounted
- Depth:
- 232 mm
- Input Compatibility:
- DI1...DI6 discrete input level 1 PLC EN/IEC 61131-2 || DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC EN/IEC 61131-2
- Analogue Output Type:
- software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
- Connector Type:
- RJ45 on the remote graphic terminal)Ethernet/Modbus TCP || RJ45 on the remote graphic terminal)Modbus serial
- Brochure:
- View
- Catalog:
- View
- Datasheet:
- View