Schneider Electric

Schneider Electric ATV650U40N4EU Atv650 Ip55 Ultype12 4Kw 5Hp 400V/480V W

(No reviews yet) Write a Review
SKU:
ATV650U40N4EU
UPC:
3606480907043
Condition:
New
Discrete Input Number:
8
Net Weight:
10.6 kg
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 10 bits || software-configurable current DQ-, DQ+ 30 V DC || software-configurable current DQ-, DQ+ 100 mA
Quantity Per Set:
1
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Maximum Output Frequency:
500 kHz
Mounting Mode:
wall mount
Type Of Polarization:
no impedance
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Motor Power Kw:
3 kW heavy duty) || 4 kW normal duty)
Marking:
CE
Supply Frequency:
50...60 Hz - 5...5 %
Frequency Resolution:
analog input 0.012/50 Hz || display unit 0.1 Hz
Linearity Error:
AO1, AO2 +/- 0.2 % analog output || AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
Variant:
with disconnect switch
Product Destination:
asynchronous motors || synchronous motors
Noise Level:
52 dB 86/188/EEC
Maximum Switching Current:
relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R1, R2, R3 resistive, cos phi = 1 3
Communication Port Protocol:
Modbus TCP || Ethernet || Modbus serial
Upgradeability:
Upgraded components available
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Device Short Name:
ATV650
Mercury Free:
Yes
Ambient Air Temperature For Storage:
-40-70 °C
Option Card:
slot A communication module, PROFINET || slot A communication module, DeviceNet || slot A communication module, Modbus TCP/EtherNet/IP || slot A communication module, CANopen daisy chain RJ45 || slot A communication module, CANopen SUB-D 9 || slot A
Braking To Standstill:
by DC injection
Discrete Input Type:
DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits || AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Maximum Thdi:
<48 % full load IEC 61000-3-12
Product Specific Application:
process and utilities
Operating Position:
vertical +/- 10 degree
Environmental Disclosure:
ENVPEP1508009EN
Data Format:
8 bits, configurable odd, even or no parity
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Electrical Connection:
line side screw terminal 4...6 mm² || motor screw terminal 4...6 mm² || control removable screw terminals 0.5...1.5 mm²
Number Of Addresses:
1-247 Modbus serial
Sustainable Offer Status:
Green Premium product
Local Signalling:
for embedded communication status 3 LEDs (dual colour) || for communication module status 4 LEDs (dual colour) || for presence of voltage 1 LED (red) || for local diagnostic 3 LEDs
Motor Slip Compensation:
not available in permanent magnet motor law || adjustable || automatic whatever the load || can be suppressed
Accuracy:
+/- 1 % AO1, AO2 for a temperature variation 60 °C analog output || +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Isolation:
between power and control terminals
China Rohs Regulation:
X
Discrete Input Logic:
16 preset speeds
Noise Level:
52 dB
Transmission Frame:
RTU
Input Compatibility:
DI5, DI6 discrete input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2 || DI1...DI6 discrete input level 1 PLC IEC 61131-2
Maximum Horse Power Rating:
4 hp heavy duty || 5 hp normal duty
Relay Output Number:
3
Ambient Air Temperature For Operation:
40-50 °C with derating factor) || -15-40 °C without derating)
Relay Output Type:
configurable relay logic R2 sequence relay NO 100000 cycles || configurable relay logic R3 sequence relay NO 100000 cycles || configurable relay logic R1 fault relay NO/NC 100000 cycles
Degree Of Protection:
UL type 12 UL 508C
Enclosure Mounting:
wall mounted
Nominal Switching Frequency:
4 kHz
Height:
678 mm
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Prospective Line Isc:
50 kA
Sampling Duration:
5 ms +/- 1 ms DI5, DI6) - discrete input || 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input || 10 ms +/- 1 ms AO1) - analog output || 2 ms +/- 0.5 ms DI1...DI4) - discrete input
Product Certifications:
UL || TÜV || ATEX zone 2/22 || DNV-GL || CSA
Type Of Cooling:
forced convection
Connector Type:
RJ45 on the remote graphic terminal)Modbus serial || RJ45 on the remote graphic terminal)Ethernet/Modbus TCP
Discrete Output Type:
relay outputs R1A, R1B, R1C 250 V AC 3000 mA || relay outputs R1A, R1B, R1C 30 V DC 3000 mA || relay outputs R2A, R2C 250 V AC 5000 mA || relay outputs R2A, R2C 30 V DC 5000 mA || relay outputs R3A, R3C 250 V AC 5000 mA || relay outputs R3A, R3C 30 V
Circularity Profile:
ENVEOLI1508009EN
Synchronous Motor Control Profile:
synchronous reluctance motor || permanent magnet motor
Physical Interface:
Ethernet || 2-wire RS 485
Width:
264 mm
Electromagnetic Compatibility:
radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 || conducted radio-frequency
Speed Drive Output Frequency:
0.1-500 Hz
Range Of Product:
Altivar Process ATV600
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
Transmission Rate:
10, 100 Mbits || 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Analogue Output Number:
2
Phase:
3 phase
Standards:
IEC 61800-3 environment 1 category C2 || EN/IEC 61800-3 environment 2 category C3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1 || IEC 61800-3
Product Or Component Type:
variable speed drive
Line Current:
6.7 A 480 V normal duty) || 6 A 380 V heavy duty) || 5.4 A 480 V heavy duty) || 7.6 A 380 V normal duty)
Protection Type:
safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-circuit protection drive || m
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Operating Altitude:
1000...4800 m with current derating 1 % per 100 m || <= 3280.84 ft (1000 m) without derating
Output Voltage:
<= power supply voltage
[Us] Rated Supply Voltage:
380...480 V
Asynchronous Motor Control Profile:
variable torque standard || optimized torque mode
Apparent Power:
4.5 kVA 480 V heavy duty) || 5.6 kVA 480 V normal duty)
Depth:
300 mm
Discrete Output Number:
0
Supply:
internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection || external suppl
Switching Frequency:
4...12 kHz with derating factor || 2...12 kHz adjustable
Overvoltage Category:
III
Method Of Access:
slave Modbus TCP
Analogue Input Number:
3
Maximum Transient Current:
10.2 A 60 s normal duty) || 10.8 A 60 s heavy duty)
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Discrete Input Logic:
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V
Permissible Temporary Current Boost:
1.5 x In 60 s heavy duty) || 1.1 x In 60 s normal duty)
Safety Function:
STO (safe torque off) SIL 3
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Rohs Exemption Information:
Yes
Pollution Degree:
2 IEC 61800-5-1
Emc Filter:
integrated 50 m IEC 61800-3 category C2 || integrated 150 m IEC 61800-3 category C3
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Vibration Resistance:
1 gn 13-200 Hz)IEC 60068-2-6 || 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6
Pollution Degree:
3
Regulation Loop:
adjustable PID regulator
Ip Degree Of Protection:
IP55IEC 60529 || IP55IEC 61800-5-1
Continuous Output Current:
7.2 A 4 kHz heavy duty || 9.3 A 4 kHz normal duty
Datasheet:
View
$2,706.90

Description

This Altivar Process ATV600 variable speed drive can feed 3-phase synchronous and asynchronous power motors. This variable speed drive features an integrated EMC filter with 50m and 150m cable conforming to categories C2 and C3. It works at a rated supply voltage from 380V to 480VAC and it is an IP55 UL type 12 rated product. This drive provides up to 30% energy saving when on standby due to the innovative ‘‘Stop and Go’’operation without additional costs. It is suitable for motors with power rating up to 4kW/5HP for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 3kW/4HP for applications requiring significant overload (up to 150%). Its dimensions are 264mm (width) x 300mm (depth) x 678mm (height). It weighs 10.6kg. This drive is focused on fluids management processing and energy saving, it offers extensive flexibility in water and wastewater, mining, minerals and metals, oil and gas and food and beverage applications. This product is certified by ATEX INERIS, ATEX zone 2/22, CE, UL, CSA, BV and TUV. It meets EN/IEC 61800, IEC 61000-3-12, IEC 60721-3, IEC 61508 and IEC 13849-1 standards. It is designed to be mounted in vertical position (+/- 10 °) on a wall. This new concept of drives meets the major needs of process and utilities in terms of equipment efficiency and total cost of ownership by supporting the energy management, asset management and also the overall performance of the process.
View AllClose