Schneider Electric ATV930D45M3C Atv930 Ip21 45Kw 200V/240V W/O Braking C

(No reviews yet) Write a Review
SKU:
ATV930D45M3C
UPC:
3606480883705
Condition:
New
Power Dissipation In W:
natural convection 175 W 200 V 2.5 kHz || forced convection 1367 W 200 V 2.5 kHz
Base Load Current At Low Overload:
176.0 A
Discrete Input Type:
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
Regulation Loop:
adjustable PID regulator
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Connector Type:
2 RJ45 || 1 RJ45
Physical Interface:
Ethernet || 2-wire RS 485
Relative Symmetric Network Frequency Tolerance:
0.05
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Quantity Per Set:
1
Discrete Input Logic:
16 preset speeds
Number Of Addresses:
1-247 Modbus serial
Noise Level:
68.3 dB
Asynchronous Motor Control Profile:
constant torque standard || variable torque standard || optimized torque mode
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Motor Power Kw:
45.0 kW normal duty || 37.0 kW heavy duty
4 Quadrant Operation Possible:
TRUE
Permitted Relative Humidity (During Operation):
class 3K5 according to EN 60721-3
Vibration Resistance:
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Maximum Output Voltage:
240.0 V
With Safety Function Safely Limited Speed (Sls):
TRUE
Input Compatibility:
DI1...DI8 discrete input level 1 PLC IEC 61131-2 || DI7, DI8 pulse input level 1 PLC IEC 65A-68 || STOA, STOB discrete input level 1 PLC IEC 61131-2
Braking To Standstill:
by DC injection
With Safety Function Safe Position (Sp):
FALSE
Sustainable Offer Status:
Green Premium product
Isolation:
between power and control terminals
Net Weight:
56.6 kg
With Safety Function Safe Speed Monitor (Ssm):
FALSE
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Relay Output Number:
3
Motor Slip Compensation:
can be suppressed || automatic whatever the load || not available in permanent magnet motor law || adjustable
Maximum Acceleration Under Shock Impact (During Operation):
150 m/s² at 11 ms
Variant:
standard version || without braking chopper
Apparent Power:
54.2 kVA 240 V normal duty) || 45.1 kVA 240 V heavy duty)
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Method Of Access:
slave Modbus TCP
Mercury Free:
Yes
Local Signalling:
local diagnostic 3 LED mono/dual colour) || embedded communication status 5 LED dual colour) || communication module status 2 LED dual colour) || presence of voltage 1 LED red)
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Marking:
CE
Transmission Rate:
10/100 Mbit/s Ethernet IP/Modbus TCP || 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
Type Of Polarization:
no impedance Modbus serial
With Safety Function Safe Programmable Logic:
FALSE
Environmental Disclosure:
ENVPEP1411014EN
Discrete Output Type:
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Data Format:
8 bits, configurable odd, even or no parity Modbus serial
Product Destination:
asynchronous motors || synchronous motors
Phase:
3 phase
With Safety Function Safely Limited Position (Slp):
FALSE
With Safety Function Safe Torque Off (Sto):
TRUE
Discrete Output Number:
2
Mounting Mode:
wall mount
Noise Level:
68.3 dB 86/188/EEC
Ambient Air Temperature For Storage:
-40-70 °C
Height:
922 mm
Maximum Transient Current:
211.2 A 60 s normal duty) || 223.5 A 60 s heavy duty)
Electrical Connection:
control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 || line side screw terminal 120 mm² AWG 4/0...250 kcmil || motor screw terminal 120 mm² 250 kcmil || DC bus screw terminal 120 mm² AWG 4/0...250 kcmil
With Safety Function Safe Brake Management (Sbc/Sbt):
TRUE
Device Application:
Industrial Application
Product Specific Application:
process for industrial
Relay Output Type:
configurable relay logic R1 fault relay NO/NC 100000 cycles || configurable relay logic R2 sequence relay NO 1000000 cycles || configurable relay logic R3 sequence relay NO 1000000 cycles
Type Of Polarization:
no impedance
Communication Port Protocol:
Modbus serial || Modbus TCP || EtherNet/IP
Transmission Rate:
10, 100 Mbits || 4.8 kbps || 9600 bit/s || 19200 bit/s
Line Current:
155.1 A 200 V normal duty) || 128.5 A 200 V heavy duty) || 130.4 A 240 V normal duty) || 108.5 A 240 V heavy duty)
Maximum Thdi:
<48 % from 80...100 % of load IEC 61000-3-12
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Emc Filter:
integrated || with EMC plate option
Nominal Switching Frequency:
2.5 kHz
Number Of Addresses:
1-247
Degree Of Protection:
UL type 1
Ambient Air Temperature For Operation:
-15-50 °C without derating) || 50-60 °C with derating factor)
Upgradeability:
Upgraded components available
Maximum Deflection Under Vibratory Load (During Operation):
1.5 mm at 2...13 Hz
Ambient Air Transport Temperature:
-40-70 °C
Overvoltage Category:
III
Product Or Component Type:
variable speed drive
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Ip Degree Of Protection:
IP21
Rohs Exemption Information:
Yes
Brake Chopper Integrated:
TRUE
Continuous Output Current:
176 A 2.5 kHz normal duty || 149 A 2.5 kHz heavy duty
Synchronous Motor Control Profile:
permanent magnet motor || synchronous reluctance motor
Volume Of Cooling Air:
295 m3/h
Pollution Degree:
2
Assembly Style:
enclosed
Base Load Current At High Overload:
149.0 A
Maximum Switching Current:
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Discrete Input Logic:
positive logic (source) DI1...DI8), < 5 V, > 11 V || negative logic (sink) DI1...DI8), > 16 V, < 10 V || positive logic (source) DI7, DI8), < 0.6 V, > 2.5 V || positive logic (source) STOA, STOB), < 5 V, > 11 V
Maximum Acceleration Under Vibrational Stress (During Operation):
10 m/s² at 13...200 Hz
Prospective Line Isc:
50 kA
Operating Position:
vertical +/- 10 degree
Analogue Input Number:
3
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation:
X
Depth:
325.5 mm
Analogue Output Number:
2
Option Card:
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module
Switching Frequency:
1...8 kHz adjustable || 2.5...8 kHz with derating factor
Maximum Output Frequency:
599 Hz
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Standards:
UL 508C || IEC 61800-3 || IEC 61800-5-1 || IEC 61000-3-12 || IEC 60721-3 || IEC 61508 || IEC 13849-1
Range Of Product:
Altivar Process ATV900
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
With Sft Fct Safe Stop 2 (Ss2):
FALSE
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
With Safety Function Safe Stop 1 (Ss1):
TRUE
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Network Frequency:
50-60 Hz
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Environmental Characteristic:
chemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
Data Format:
8 bits, configurable odd, even or no parity
Circularity Profile:
ENVEOLI1411014EN
Transmission Frame:
RTU
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
Environmental Class (During Operation):
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
With Safety Function Safe Operating Stop (Sos):
FALSE
Product Certifications:
CSA || TÜV || UL
Discrete Input Number:
10
With Safety Function Safe Direction (Sdi):
FALSE
Width:
290 mm
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
[Us] Rated Supply Voltage:
200...240 V - 15...10 %
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Catalog:
View
Datasheet:
View
$11,111.64

Description

This Altivar Process ATV900 variable speed drive can feed 3-phase synchronous and asynchronous power motors. It is suitable for motors with power rating up to 45kW/60HP for applications requiring slight overload (up to 120%). It is suitable for motors with power rating up to 37kW/50HP for applications requiring significant overload (up to 150%). It works at a rated supply voltage from 200Vac to 240Vac. This variable speed / frequency drive (VSD / VFD) is specifically designed for industrial processes. In the following market segments: oil and gas, mining, minerals and metals, food and beverage water and wastewater. It offers high motor performance on any motor and total control of any kind of coupling in master/slave applications. Network services help ensure operation continuity even in case of connection breakdown. Web server and data logging help reduce downtime through fast troubleshooting and preventive maintenance. Its advanced connectivity, including EtherNet/IP and Modbus TCP, allows deep integration into automation architectures.
View AllClose