Schneider Electric ATV950D22N4EU Atv950 Ip55 Ultype12 22Kw 400V/480V With
SKU:
ATV950D22N4EU
UPC:
3.60648E+12
MPN:
Condition:
New
With Safety Function Safe Operating Stop (Sos):
FALSE
With Safety Function Safe Direction (Sdi):
FALSE
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
With Sft Fct Safe Stop 2 (Ss2):
FALSE
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Discrete Output Type:
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
chemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Maximum Transient Current:
55.6 A 60 s normal duty) || 58.8 A 60 s heavy duty)
Synchronous Motor Control Profile:
permanent magnet motor || synchronous reluctance motor
Reference contains Substances of Very High Concern above the threshold
Ambient Air Transport Temperature:
-40-70 °C
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Device Application:
Industrial Application
Product Destination:
synchronous motors || asynchronous motors
Maximum Acceleration Under Shock Impact (During Operation):
150 m/s² at 11 ms
Electrical Connection:
control screw terminal 0.5...1.5 mm² || line side screw terminal 10...16 mm² || DC bus screw terminal 10...16 mm² || motor screw terminal 16 mm²
Marking:
CE
Maximum Deflection Under Vibratory Load (During Operation):
1.5 mm at 2...13 Hz
Type Of Polarization:
no impedance
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Maximum Acceleration Under Vibrational Stress (During Operation):
10 m/s² at 13...200 Hz
Degree Of Protection:
UL type 12
Width:
264 mm
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
With Safety Function Safely Limited Speed (Sls):
TRUE
Phase:
3 phase
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
4 Quadrant Operation Possible:
TRUE
Discrete Input Logic:
16 preset speeds
Quantity Per Set:
1
Relay Output Number:
3
Motor Power Kw:
22.0 kW normal duty || 18.5 kW heavy duty
Environmental Class (During Operation):
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
Vibration Resistance:
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
Data Format:
8 bits, configurable odd, even or no parity
Relative Symmetric Network Frequency Tolerance:
0.05
Base Load Current At High Overload:
39.2 A
Mercury Free:
Yes
Connector Type:
2 RJ45 || 1 RJ45
Physical Interface:
Ethernet || 2-wire RS 485
Ambient Air Temperature For Operation:
-15-40 °C without derating) || 40-50 °C with derating factor)
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Data Format:
8 bits, configurable odd, even or no parity Modbus serial
Continuous Output Current:
46.3 A 4 kHz normal duty || 39.2 A 4 kHz heavy duty
Rohs Exemption Information:
Yes
Product Or Component Type:
variable speed drive
Overvoltage Category:
III
Discrete Input Type:
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
39.6 A 380 V normal duty) || 34.1 A 380 V heavy duty) || 34.4 A 480 V normal duty) || 29.9 A 480 V heavy duty)
Local Signalling:
local diagnostic 3 LED mono/dual colour) || embedded communication status 5 LED dual colour) || communication module status 2 LED dual colour) || presence of voltage 1 LED red)
Variant:
with braking chopper || with load break switch
Noise Level:
53.7 dB
Communication Port Protocol:
Modbus TCP || Modbus serial || EtherNet/IP
Assembly Style:
enclosed
With Safety Function Safely Limited Position (Slp):
FALSE
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Asynchronous Motor Control Profile:
constant torque standard || optimized torque mode || variable torque standard
Nominal Switching Frequency:
4 kHz
Discrete Input Number:
10
[Us] Rated Supply Voltage:
380...480 V - 15...10 %
With Safety Function Safe Speed Monitor (Ssm):
FALSE
Braking To Standstill:
by DC injection
Method Of Access:
slave Modbus TCP
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Emc Filter:
integrated || with EMC plate option
Maximum Output Voltage:
480.0 V
Sustainable Offer Status:
Green Premium product
With Safety Function Safe Torque Off (Sto):
TRUE
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Permitted Relative Humidity (During Operation):
class 3K5 according to EN 60721-3
With Safety Function Safe Position (Sp):
FALSE
Analogue Input Number:
3
Maximum Thdi:
<48 % from 80...100 % of load IEC 61000-3-12
Prospective Line Isc:
50 kA
Network Frequency:
50-60 Hz
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Pollution Degree:
2
With Safety Function Safe Brake Management (Sbc/Sbt):
TRUE
Maximum Switching Current:
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R
Noise Level:
53.7 dB 86/188/EEC
Isolation:
between power and control terminals
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Number Of Addresses:
1-247 Modbus serial
Option Card:
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module