- Awg Gauge:
- AWG 14...AWG 2/0 aluminium/copper
- Mercury Free:
- Yes
- Control Type:
- toggle
- Phase Connection:
- AB
- Poles Description:
- 2P
- Net Weight:
- 0.952 kg
- Ambient Air Temperature For Storage:
- -50-85 °C
- Ambient Air Temperature For Operation:
- -25-70 °C
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Line Rated Current:
- 20-20 A
- Pvc Free:
- Yes
- Continuous Current Rating:
- 0.8
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
- Sustainable Offer Status:
- Green Premium product
- Breaking Capacity:
- 25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600Y/347 V AC 50/60 Hz UL 489 || 10 kA 250 V DC UL 489
- Quantity Per Set:
- set of 1
- Standards:
- EN/IEC 60947-5-1 || NMX J-266 || CSA C22.2 No 5 || NEMA AB1 || UL 489 || GB 14048.2 || EN/IEC 60947-2
- [Ue] Rated Operational Voltage:
- 525 V AC 50/60 Hz UL 489
- Pollution Degree:
- 3 IEC 60947-1
- 9 Mm Pitches:
- 6
- Halogen Content Performance:
- Halogen free product
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Mounting Height:
- 76.2 mm
- Environmental Disclosure:
- ENVPEP1610005EN
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Local Signalling:
- presence of auxiliary contacts flag green)
- Circularity Profile:
- N/A
- Ik Degree Of Protection:
- IK07 IEC 62262
- Connection Pitch:
- 27 mm
- Breaking Capacity Code:
- D
- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Eu Rohs Directive:
- Compliant with Exemptions
- Height:
- 137 mm
- Circuit Breaker Application:
- HACR rated
- Trip Unit Technology:
- thermal-magnetic
- Suitability For Isolation:
- yes IEC 60947-2
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
- Quality Labels:
- CE
- Device Application:
- distribution
- Rohs Exemption Information:
- Yes
- Mounting Mode:
- I-Line
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Product Or Component Type:
- circuit breaker
- Range:
- PowerPact
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Network Frequency:
- 50/60 Hz
- Tightening Torque:
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Electrical Connection:
- I-Line connection, line || lugs, load
- Wire Stripping Length:
- 20 mm
- Color:
- Gray RAL 7016)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Depth:
- 89 mm
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Utilisation Category:
- category A
- Width:
- 54 mm
- Device Short Name:
- BD 020
- Product Name:
- PowerPact B