- Awg Gauge:
- AWG 14...AWG 2/0 aluminium/copper
- Electrical Connection:
- I-Line connection, line || lugs, load
- Phase Connection:
- AC
- Connection Pitch:
- 27 mm
- Circuit Breaker Application:
- HACR rated
- [Ue] Rated Operational Voltage:
- 525 V AC 50/60 Hz UL 489
- Sustainable Offer Status:
- Green Premium product
- 9 Mm Pitches:
- 6
- Line Rated Current:
- 60-60 A
- Local Signalling:
- presence of auxiliary contacts flag green)
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Wire Stripping Length:
- 20 mm
- Width:
- 54 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Quantity Per Set:
- set of 1
- Range:
- PowerPact
- Control Type:
- toggle
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Suitability For Isolation:
- yes IEC 60947-2
- Product Or Component Type:
- circuit breaker
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Mounting Mode:
- I-Line
- Color:
- Gray RAL 7016)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Utilisation Category:
- category A
- Ambient Air Temperature For Storage:
- -50-85 °C
- Poles Description:
- 2P
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Quality Labels:
- CE
- Ambient Air Temperature For Operation:
- -25-70 °C
- Ik Degree Of Protection:
- IK07 IEC 62262
- Rohs Exemption Information:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Height:
- 137 mm
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Device Short Name:
- BD 060
- Net Weight:
- 0.952 kg
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
- Device Application:
- distribution
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Circularity Profile:
- N/A
- Depth:
- 89 mm
- Standards:
- UL 489 || GB 14048.2 || NEMA AB1 || EN/IEC 60947-2 || CSA C22.2 No 5 || NMX J-266 || EN/IEC 60947-5-1
- Breaking Capacity Code:
- D
- Environmental Disclosure:
- ENVPEP1610005EN
- Tightening Torque:
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Product Name:
- PowerPact B
- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Trip Unit Technology:
- thermal-magnetic
- Pollution Degree:
- 3 IEC 60947-1
- Continuous Current Rating:
- 0.8
- Halogen Content Performance:
- Halogen free product
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- Breaking Capacity:
- 25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600Y/347 V AC 50/60 Hz UL 489 || 10 kA 250 V DC UL 489
- Network Frequency:
- 50/60 Hz
- Pvc Free:
- Yes
- Mercury Free:
- Yes
- Mounting Height: