- Trip Unit Technology:
- thermal-magnetic
- Suitability For Isolation:
- yes IEC 60947-2
- Environmental Disclosure:
- ENVPEP1610005EN
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
- Range:
- PowerPact
- Poles Description:
- 3P
- Breaking Capacity:
- 25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600Y/347 V AC 50/60 Hz UL 489 || 10 kA 250 V DC UL 489
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Utilisation Category:
- category A
- Wire Stripping Length:
- 20 mm
- Device Short Name:
- BD 015
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Device Application:
- distribution
- Rohs Exemption Information:
- Yes
- Line Rated Current:
- 15-15 A
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Name:
- PowerPact B
- Electrical Connection:
- I-Line connection, line || lugs, load
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Circuit Breaker Application:
- HACR rated
- Phase Connection:
- ABC
- Eu Rohs Directive:
- Compliant with Exemptions
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- Breaking Capacity Code:
- D
- Continuous Current Rating:
- 0.8
- Net Weight:
- 1.315 kg
- Ik Degree Of Protection:
- IK07 IEC 62262
- Depth:
- 89 mm
- [Ue] Rated Operational Voltage:
- 525 V AC 50/60 Hz UL 489
- Ambient Air Temperature For Operation:
- -25-70 °C
- Tightening Torque:
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Product Or Component Type:
- circuit breaker
- Circularity Profile:
- N/A
- Pollution Degree:
- 3 IEC 60947-1
- Sustainable Offer Status:
- Green Premium product
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Network Frequency:
- 50/60 Hz
- 9 Mm Pitches:
- 9
- Width:
- 81 mm
- Ambient Air Temperature For Storage:
- -50-85 °C
- Color:
- Gray RAL 7016)
- Mounting Mode:
- I-Line
- Control Type:
- toggle
- Mounting Height:
- 114 mm
- Connection Pitch:
- 27 mm
- Quality Labels:
- CE
- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Pvc Free:
- Yes
- Local Signalling:
- presence of auxiliary contacts flag green)
- Standards:
- EN/IEC 60947-5-1 || GB 14048.2 || UL 489 || CSA C22.2 No 5 || EN/IEC 60947-2 || NEMA AB1 || NMX J-266
- Awg Gauge:
- AWG 14...AWG 2/0 aluminium/copper
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Mercury Free:
- Yes
- Quantity Per Set:
- set of 1
- Height:
- 137 mm
- Halogen Content Performance:
- Halogen free product