- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Connection Pitch:
- 27 mm
- Trip Unit Technology:
- thermal-magnetic
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Or Component Type:
- circuit breaker
- Local Signalling:
- presence of auxiliary contacts flag green)
- [Ue] Rated Operational Voltage:
- 525 V AC 50/60 Hz UL 489
- Depth:
- 80 mm
- Control Type:
- toggle
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Range:
- PowerPact
- Mercury Free:
- Yes
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Utilisation Category:
- category A
- Net Weight:
- 1.441 kg
- [Ics] Rated Service Breaking Capacity:
- 25 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 14 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 18 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 18 kA 440 V AC 50/60 Hz IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70 °C
- Environmental Disclosure:
- ENVPEP1610005EN
- Circularity Profile:
- N/A
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Width:
- 108 mm
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Quality Labels:
- CE
- Sustainable Offer Status:
- Green Premium product
- Rohs Exemption Information:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- Pvc Free:
- Yes
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Height:
- 137 mm
- Poles Description:
- 4P
- Product Name:
- PowerPact B
- Pollution Degree:
- 3 IEC 60947-1
- Awg Gauge:
- AWG 6...AWG 2/0 fine stranded aluminium/copper || AWG 14...AWG 3/0 rigid or stranded aluminium/copper
- Breaking Capacity Code:
- D
- Wire Stripping Length:
- 20 mm
- Mounting Mode:
- clip-on 35 x 15 mm symmetrical DIN rail) || by screws plate)
- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Breaking Capacity:
- 25 kA 208Y/120 V AC 50/60 Hz UL 489 || 25 kA 240 V AC 50/60 Hz UL 489 || 18 kA 480/277 V AC 50/60 Hz UL 489 || 18 kA 480 V AC 50/60 Hz UL 489 || 14 kA 600Y/347 V AC 50/60 Hz UL 489 || 10 kA 250 V DC UL 489
- Circuit Breaker Application:
- HACR rated
- Tightening Torque:
- 5-5 N.m 2.5-16 mm² (AWG 14...AWG 4) || 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- Network Frequency:
- 50/60 Hz
- Continuous Current Rating:
- 0.8
- Ik Degree Of Protection:
- IK07 IEC 62262
- Quantity Per Set:
- set of 1
- Device Short Name:
- BD 100
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Electrical Connection:
- Everlink lug, line || Everlink lug, load
- 9 Mm Pitches:
- 12
- Device Application:
- distribution
- Standards:
- CSA C22.2 No 5 || NMX J-266 || EN/IEC 60947-2 || UL 489 || GB 14048.2 || NEMA AB1 || EN/IEC 60947-5-1
- Ambient Air Temperature For Storage:
- -50-85 °C
- Color:
- Gray RAL 7016)
- Line Rated Current:
- 100-100 A
- Halogen Content Performance:
- Halogen free product
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2