- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Mounting Height:
- 114 mm
- Wire Stripping Length:
- 20 mm
- Eu Rohs Directive:
- Compliant with Exemptions
- Quality Labels:
- CE
- Environmental Disclosure:
- ENVPEP1610005EN
- Control Type:
- toggle
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Device Application:
- distribution
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Continuous Current Rating:
- 0.8
- Net Weight:
- 1.315 kg
- Height:
- 137 mm
- Connection Pitch:
- 27 mm
- Pvc Free:
- Yes
- Breaking Capacity Code:
- G
- Standards:
- NMX J-266 || CSA C22.2 No 5 || EN/IEC 60947-5-1 || UL 489 || EN/IEC 60947-2 || GB 14048.2 || NEMA AB1
- Depth:
- 89 mm
- Product Name:
- PowerPact B
- Pollution Degree:
- 3 IEC 60947-1
- Rohs Exemption Information:
- Yes
- Mercury Free:
- Yes
- Circuit Breaker Application:
- HACR rated
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Local Signalling:
- presence of auxiliary contacts flag green)
- Line Rated Current:
- 60-60 A
- Network Frequency:
- 50/60 Hz
- Product Or Component Type:
- circuit breaker
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Ambient Air Temperature For Storage:
- -50-85 °C
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Range:
- PowerPact
- [Ue] Rated Operational Voltage:
- 525 V AC 50/60 Hz UL 489
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- Breaking Capacity:
- 65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 18 kA 250 V DC UL 489 || 20 kA 600Y/347 V AC 50/60 Hz UL 489
- Tightening Torque:
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Ambient Air Temperature For Operation:
- -25-70 °C
- 9 Mm Pitches:
- 9
- Device Short Name:
- BG 060
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
- Quantity Per Set:
- set of 1
- Sustainable Offer Status:
- Green Premium product
- Color:
- Gray RAL 7016)
- Poles Description:
- 3P
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Circularity Profile:
- N/A
- Awg Gauge:
- AWG 14...AWG 2/0 aluminium/copper
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
- Mounting Mode:
- I-Line
- Ik Degree Of Protection:
- IK07 IEC 62262
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Halogen Content Performance:
- Halogen free product
- Utilisation Category:
- category A
- Electrical Connection:
- I-Line connection, line || lugs, load
- Suitability For Isolation:
- yes IEC 60947-2
- Phase Connection:
- ABC
- Width:
- 81 mm
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold