- Color:
- Gray RAL 7016)
- Wire Stripping Length:
- 20 mm
- Device Application:
- distribution
- Depth:
- 80 mm
- Connection Pitch:
- 27 mm
- Mounting Mode:
- clip-on 35 mm symmetrical DIN rail) || by screws plate)
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Range:
- PowerPact
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Halogen Content Performance:
- Halogen free product
- Product Name:
- PowerPact B
- Electrical Connection:
- terminal nut, ON and OFF end
- Ik Degree Of Protection:
- IK07 IEC 62262
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
- Height:
- 137 mm
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Environmental Disclosure:
- ENVPEP1610005EN
- Circuit Breaker Application:
- HACR rated
- Protected Poles Description:
- 3t
- Device Short Name:
- BG 100
- Sustainable Offer Status:
- Green Premium product
- Local Signalling:
- presence of auxiliary contacts flag green)
- Network Frequency:
- 50/60 Hz
- Continuous Current Rating:
- 0.8
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Name:
- TM-D
- Line Rated Current:
- 100-100 A
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Quantity Per Set:
- set of 1
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Tightening Torque:
- 5-5 N.m 2.5-16 mm² (AWG 14...AWG 4) || 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
- Mercury Free:
- Yes
- Net Weight:
- 0.924 kg
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- [Ue] Rated Operational Voltage:
- 525 V AC 50/60 Hz UL 489
- Mechanical Durability:
- 15000 cycles IEC 947-1 Annex K ed 5.2
- Breaking Capacity Code:
- G
- Poles Description:
- 3P
- Awg Gauge:
- AWG 14...AWG 8 aluminium/copper || AWG 6...AWG 3/0 aluminium/copper
- Breaking Capacity:
- 65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480/277 V AC 50/60 Hz UL 489 || 35 kA 480 V AC 50/60 Hz UL 489 || 20 kA 250 V DC UL 489 || 18 kA 600Y/347 V AC 50/60 Hz UL 489
- Suitability For Isolation:
- yes IEC 60947-2
- Quality Labels:
- CE
- 9 Mm Pitches:
- 9
- Circularity Profile:
- N/A
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Operating Altitude:
- 6561.68 ft (2000 m) without derating || 5000 m with derating
- Ambient Air Temperature For Storage:
- -50-85 °C
- Utilisation Category:
- category A
- Pvc Free:
- Yes
- Control Type:
- toggle
- Rohs Exemption Information:
- Yes
- Eu Rohs Directive:
- Compliant with Exemptions
- Product Or Component Type:
- circuit breaker
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 18 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 35 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 35 kA 440 V AC 50/60 Hz IEC 60947-2
- Width:
- 81 mm
- Standards:
- UL 489 || EN/IEC 60947-5-1 || CSA C22.2 No 5 || GB 14048.2 || NMX J-266 || EN/IEC 60947-2 || NEMA AB1
- Pollution Degree:
- 3 IEC 60947-1
- Ambient Air Temperature For Operation:
- -25-70 °C
- Trip Unit Technology:
- thermal-magneticTM-D,