- Device Short Name:
- BG 040
- Continuous Current Rating:
- 0.8
- Net Weight:
- 0.51 kg
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Environmental Disclosure:
- ENVPEP1610005EN
- Standards:
- NMX J-266 || EN/IEC 60947-5-1 || UL 489 || GB 14048.2 || EN/IEC 60947-2 || CSA C22.2 No 5 || NEMA AB1
- Network Frequency:
- 50/60 Hz
- Mounting Mode:
- clip-on 35 mm symmetrical DIN rail) || by screws plate)
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Product Or Component Type:
- circuit breaker
- Pollution Degree:
- 3 IEC 60947-1
- Line Rated Current:
- 40-40 A
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 In
- Electrical Connection:
- Everlink lug, line || Everlink lug, load
- Circuit Breaker Application:
- HACR rated
- Sustainable Offer Status:
- Green Premium product
- Breaking Capacity Code:
- G
- Trip Unit Name:
- TM-D
- Protected Poles Description:
- 1t
- Color:
- Gray RAL 7016)
- Connection Pitch:
- 27 mm
- Product Name:
- PowerPact B
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Trip Unit Technology:
- thermal-magneticTM-D,
- Awg Gauge:
- AWG 6...AWG 2/0 fine stranded aluminium/copper || AWG 14...AWG 3/0 rigid or stranded aluminium/copper
- Eu Rohs Directive:
- Compliant
- Tightening Torque:
- 5-5 N.m 2.5-16 mm² (AWG 14...AWG 4) || 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
- Pvc Free:
- Yes
- Rohs Exemption Information:
- Yes
- Suitability For Isolation:
- yes IEC 60947-2
- [Ue] Rated Operational Voltage:
- 240 V AC 50/60 Hz UL 489
- Device Application:
- distribution
- 9 Mm Pitches:
- 3
- Width:
- 27 mm
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Quantity Per Set:
- set of 1
- Range:
- PowerPact
- Utilisation Category:
- category A
- [Ics] Rated Service Breaking Capacity:
- 65 kA 220...240 V AC 50/60 Hz IEC 60947-2
- Halogen Content Performance:
- Halogen free product
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mercury Free:
- Yes
- Depth:
- 80 mm
- Ik Degree Of Protection:
- IK07 IEC 62262
- Quality Labels:
- CE
- Ambient Air Temperature For Operation:
- -25-70 °C
- Control Type:
- toggle
- Breaking Capacity:
- 65 kA 208Y/120 V AC 50/60 Hz UL 489 || 65 kA 240 V AC 50/60 Hz UL 489 || 35 kA 480Y/277 V AC 50/60 Hz UL 489 || 18 kA 600Y/347 V AC 50/60 Hz UL 489 || 20 kA 125 V DC UL 489
- Height:
- 137 mm
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- Mechanical Durability:
- 15000 cycles IEC 947-1 Annex F ed 5.2
- Wire Stripping Length:
- 20 mm
- Operating Altitude:
- 6561.68 ft (2000 m) without derating || 5000 m with derating
- Poles Description:
- 1P