- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Phase Connection:
- BC
- Height:
- 137 mm
- Wire Stripping Length:
- 20 mm
- Tightening Torque:
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Product Or Component Type:
- circuit breaker
- Circularity Profile:
- N/A
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.
- Device Short Name:
- BJ 020
- Depth:
- 89 mm
- Quantity Per Set:
- set of 1
- Product Name:
- PowerPact B
- Network Frequency:
- 50/60 Hz
- Eu Rohs Directive:
- Compliant with Exemptions
- Sustainable Offer Status:
- Green Premium product
- Environmental Disclosure:
- ENVPEP1610005EN
- Halogen Content Performance:
- Halogen free product
- Mounting Mode:
- I-Line
- Pollution Degree:
- 3 IEC 60947-1
- Awg Gauge:
- AWG 14...AWG 2/0 aluminium/copper
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Width:
- 54 mm
- Pvc Free:
- Yes
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- Color:
- Gray RAL 7016)
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz UL 489
- Net Weight:
- 0.952 kg
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Ambient Air Temperature For Operation:
- -25-70 °C
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Range:
- PowerPact
- Circuit Breaker Application:
- HACR rated
- Breaking Capacity Code:
- J
- 9 Mm Pitches:
- 6
- Standards:
- UL 489 || GB 14048.2 || EN/IEC 60947-2 || NMX J-266 || EN/IEC 60947-5-1 || CSA C22.2 No 5 || NEMA AB1
- Quality Labels:
- CE
- Electrical Connection:
- I-Line connection, line || lugs, load
- Mounting Height:
- 76.2 mm
- Line Rated Current:
- 20-20 A
- Rohs Exemption Information:
- Yes
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Suitability For Isolation:
- yes IEC 60947-2
- Local Signalling:
- presence of auxiliary contacts flag green)
- Breaking Capacity:
- 100 kA 208Y/120 V AC 50/60 Hz UL 489 || 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480/277 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600Y/347 V AC 50/60 Hz UL 489 || 50 kA 250 V DC UL 489
- Ambient Air Temperature For Storage:
- -50-85 °C
- Mercury Free:
- Yes
- Device Application:
- distribution
- [Ics] Rated Service Breaking Capacity:
- 100 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 25 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 10 kA 690 V AC 50/60 Hz IEC 60947-2 || 65 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 65 kA 440 V AC 50/60 Hz IEC 60947-2
- Ik Degree Of Protection:
- IK07 IEC 62262
- Connection Pitch:
- 27 mm
- Utilisation Category:
- category A
- Poles Description:
- 2P
- Continuous Current Rating:
- 0.8
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Trip Unit Technology:
- thermal-magnetic
- Control Type:
- toggle
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in)