- Breaking Capacity Code:
- J
- Ambient Air Temperature For Operation:
- -25-70 °C
- Width:
- 81 mm
- Wire Stripping Length:
- 20 mm
- Product Or Component Type:
- circuit breaker
- Reach Regulation:
- Reference contains Substances of Very High Concern above the threshold
- Operating Altitude:
- < 6561.68 ft (2000 m) without derating || 5000 m with derating
- Electrical Connection:
- I-Line connection, line || lugs, load
- Color:
- Gray RAL 7016)
- Quantity Per Set:
- set of 1
- Line Rated Current:
- 50-50 A
- Device Short Name:
- BJ 050
- Mechanical Durability:
- 20000 cycles IEC 947-1 Annex K ed 5.2
- Range:
- PowerPact
- Pvc Free:
- Yes
- Connection Pitch:
- 27 mm
- Utilisation Category:
- category A
- Environmental Disclosure:
- ENVPEP1610005EN
- Rohs Exemption Information:
- Yes
- Ambient Air Temperature For Storage:
- -50-85 °C
- Awg Gauge:
- AWG 14...AWG 2/0 aluminium/copper
- [Ui] Rated Insulation Voltage:
- 800 V IEC 60947-2
- Number Of Slots:
- 1 auxiliary switch OF plug-in) || 1 voltage release MN or MX plug-in) || 1 alarm switch SD plug-in)
- Ik Degree Of Protection:
- IK07 IEC 62262
- Network Frequency:
- 50/60 Hz
- Phase Connection:
- ABC
- Electrical Durability:
- 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
- Pollution Degree:
- 3 IEC 60947-1
- California Proposition 65:
- WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information
- Ip Degree Of Protection:
- front cover IP40 IEC 60529
- Local Signalling:
- presence of auxiliary contacts flag green)
- Poles Description:
- 3P
- Depth:
- 89 mm
- Trip Unit Technology:
- thermal-magnetic
- Mercury Free:
- Yes
- Halogen Content Performance:
- Halogen free product
- [Ics] Rated Service Breaking Capacity:
- 100 kA 220...240 V AC 50/60 Hz IEC 60947-2 || 25 kA 500...525 V AC 50/60 Hz IEC 60947-2 || 10 kA 690 V AC 50/60 Hz IEC 60947-2 || 65 kA 380...415 V AC 50/60 Hz IEC 60947-2 || 65 kA 440 V AC 50/60 Hz IEC 60947-2
- Continuous Current Rating:
- 0.8
- Breaking Capacity:
- 100 kA 208Y/120 V AC 50/60 Hz UL 489 || 100 kA 240 V AC 50/60 Hz UL 489 || 65 kA 480/277 V AC 50/60 Hz UL 489 || 65 kA 480 V AC 50/60 Hz UL 489 || 25 kA 600Y/347 V AC 50/60 Hz UL 489 || 50 kA 250 V DC UL 489
- Quality Labels:
- CE
- [Uimp] Rated Impulse Withstand Voltage:
- 8 kV IEC 60947-2
- Circularity Profile:
- N/A
- Circuit Breaker Application:
- HACR rated
- Standards:
- EN/IEC 60947-2 || NMX J-266 || UL 489 || CSA C22.2 No 5 || EN/IEC 60947-5-1 || GB 14048.2 || NEMA AB1
- Tightening Torque:
- 3.6-4.4 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5-6.2 N.m 10-70 mm² (AWG 8...AWG 2/0)
- Product Name:
- PowerPact B
- Eu Rohs Directive:
- Compliant with Exemptions
- Mounting Mode:
- I-Line
- Height:
- 137 mm
- Device Application:
- distribution
- Control Type:
- toggle
- Product Certifications:
- UL || IEC || CCC || EAC || CSA || NOM
- Suitability For Isolation:
- yes IEC 60947-2
- 9 Mm Pitches:
- 9
- Weee:
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- Net Weight:
- 1.315 kg
- Mounting Height:
- 114 mm
- Sustainable Offer Status:
- Green Premium product
- [Ue] Rated Operational Voltage:
- 690 V AC 50/60 Hz UL 489
- China Rohs Regulation:
- Product out of China RoHS scope. Substance declaration for your information.