Schneider Electric EGB26030 Miniature Circuit Breaker 600V 30A

(No reviews yet) Write a Review
SKU:
EGB26030
UPC:
785901294832
Condition:
New
Ambient Air Temperature For Operation:
40 °C
Number Of Spaces Required:
2
Product Certifications:
cULus
Warranty:
18 months
Tightening Torque:
3.4-3.4 N.m 2.5-16 mm² (AWG 14...AWG 6)
Range Of Product:
125 A Frame EDB-EGB-EJB
Width:
1.96 in
Number Of Spaces:
2
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mounting Mode:
bolt-on
Device Short Name:
EGB
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Net Weight:
3 lb(US)
Circuit Breaker Application:
HACR rated
Mercury Free:
Yes
Product Or Component Type:
circuit-breaker
Holding Current:
270 A
Electrical Connection:
lugs aluminium
Product Destination:
NF panelboard
Protection Type:
short-circuit || overload
Local Signalling:
trip indicator
Number Of Poles:
2
Trip Unit Rating:
875-875 A
Height:
5.66 in
Module Type:
E-Frame
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
[Ue] Rated Operational Voltage:
600Y/347 V AC
Line Rated Current:
30 A
Breaking Capacity Code:
G
Depth:
4.05 in
Trip Unit Technology:
thermal-magnetic
Breaking Capacity:
18 kA 600Y/347 V AC
Awg Gauge:
AWG 12...AWG 6 aluminium || AWG 14...AWG 6 copper
Rohs Exemption Information:
Yes
Brochure:
View
Catalog:
View
Datasheet:
View
$647.00

Description

E-Frame Breaker are Lighting Panelboard Circuit breakers that are proven effective and reliable which provide a wide variety or robust features that are use specifically in Square D NF Panelboards. This range of breaker is ideally designed to offer superior overload and short circuit protection. All E-Frame breakers have a thermal-magnetic trip unit as well as signal indicator that will indicate when a trip has occur. Mounting bolts are used to hold these breakers in place. This E-Frame breaker is 30A, 2 pole, and has an operating voltage of 600Y/347 VAC. It also provides a 65 kA max interrupt rating at 120 VAC. This device has a hold current of 270A which is the maximum current the breaker can be held to ensure it will trip and a trip current of 875A which is the current value when the breaker is guaranteed to trip. Many accessories are available for this breaker. This breaker was calibrated for 40 degrees C. This product is UL Listed as High Intensity Discharge. HACR rated.
View AllClose