Schneider Electric EGB34050SA Miniature Circuit Breaker 480Y/277V 50A

(No reviews yet) Write a Review
SKU:
EGB34050SA
UPC:
7.85901E+11
Condition:
New
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Holding Current:
630 A
Height:
5.66 in
Local Signalling:
trip indicator
Product Destination:
NF panelboard
Tightening Torque:
3.9-3.9 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5.6-5.6 N.m 10-70 mm² (AWG 8...AWG 2/0)
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Electrical Connection:
lugs aluminium
Trip Unit Rating:
1800-1800 A
Breaking Capacity:
35 kA 277 V AC || 65 kA 240 V AC || 35 kA 480Y/277 V AC || 65 kA 120 V AC || 65 kA 120/240 V AC
Product Or Component Type:
miniature circuit-breaker
Mercury Free:
Yes
Net Weight:
4 lb(US)
Mounting Mode:
bolt-on
Line Rated Current:
50 A
Warranty:
18 months
Device Short Name:
EGB
Module Type:
E-Frame
Width:
3.92 in
Breaking Capacity Code:
G
Protection Type:
short-circuit || overload
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Awg Gauge:
AWG 12...AWG 2/0 aluminium || AWG 14...AWG 2/0 copper
Product Certifications:
cULus
Device Composition:
shunt trip
Rohs Exemption Information:
Yes
Circuit Breaker Application:
HACR rated || HID rated
[Ue] Rated Operational Voltage:
480Y/277 V AC
Trip Unit Technology:
thermal-magnetic
Number Of Poles:
3
Depth:
4.05 in
Number Of Spaces Required:
4
Range Of Product:
125 A Frame EDB-EGB-EJB
Number Of Spaces:
4
Ambient Air Temperature For Operation:
40 °C
  • Schneider Electric EGB34050SA Miniature Circuit Breaker 480Y/277V 50A
  • Schneider Electric EGB34050SA Miniature Circuit Breaker 480Y/277V 50A
$1,886.00

Description

E-Frame Breaker are Lighting Panelboard Circuit breakers that are proven effective and reliable which provide a wide variety or robust features that are use specifically in Square D NF Panelboards. This range of breaker is ideally designed to offer superior overload and short circuit protection. All E-Frame breakers have a thermal-magnetic trip unit as well as signal indicator that will indicate when a trip has occur. Mounting bolts are used to hold these breakers in place. This E-Frame breaker is 50A, 3 pole, and has an operating voltage of 480Y/277 VAC. It also provides a 65 kA max interrupt rating at 120 VAC. This device has a hold current of 630A which is the maximum current the breaker can be held to ensure it will trip and a trip current of 1800A which is the current value when the breaker is guaranteed to trip. Many accessories are available for this breaker. This one includes a shunt trip. This breaker was calibrated for 40 degrees C. This product is UL Listed as High Intensity Discharge. HACR rated.
View AllClose