Schneider Electric EGB34090 Miniature Circuit Breaker 480Y/277V 90A

(No reviews yet) Write a Review
SKU:
EGB34090
UPC:
785901130475
Condition:
New
Local Signalling:
trip indicator
Height:
5.66 in
Warranty:
18 months
Device Short Name:
EGB
Net Weight:
4 lb(US)
Number Of Spaces Required:
3
Width:
2.94 in
Module Type:
E-Frame
Depth:
4.05 in
Breaking Capacity:
35 kA 277 V AC || 65 kA 240 V AC || 35 kA 480Y/277 V AC || 65 kA 120 V AC || 65 kA 120/240 V AC
Mercury Free:
Yes
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Product Destination:
NF panelboard
Trip Unit Rating:
2300-2300 A
Product Certifications:
cULus
Awg Gauge:
AWG 12...AWG 2/0 aluminium || AWG 14...AWG 2/0 copper
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Line Rated Current:
90 A
Breaking Capacity Code:
G
Mounting Mode:
bolt-on
Range Of Product:
125 A Frame EDB-EGB-EJB
Ambient Air Temperature For Operation:
40 °C
Electrical Connection:
lugs aluminium
Circuit Breaker Application:
HACR rated
Rohs Exemption Information:
Yes
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Tightening Torque:
3.9-3.9 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5.6-5.6 N.m 10-70 mm² (AWG 8...AWG 2/0)
Number Of Poles:
3
Trip Unit Technology:
thermal-magnetic
Protection Type:
short-circuit || overload
Product Or Component Type:
miniature circuit-breaker
Holding Current:
1000 A
[Ue] Rated Operational Voltage:
480Y/277 V AC
Number Of Spaces:
3
  • Schneider Electric EGB34090 Miniature Circuit Breaker 480Y/277V 90A
  • Schneider Electric EGB34090 Miniature Circuit Breaker 480Y/277V 90A
  • Schneider Electric EGB34090 Miniature Circuit Breaker 480Y/277V 90A
$1,292.00

Description

E-Frame Breaker are Lighting Panelboard Circuit breakers that are proven effective and reliable which provide a wide variety or robust features that are use specifically in Square D NF Panelboards. This range of breaker is ideally designed to offer superior overload and short circuit protection. All E-Frame breakers have a thermal-magnetic trip unit as well as signal indicator that will indicate when a trip has occur. Mounting bolts are used to hold these breakers in place. This E-Frame breaker is 90A, 3 pole, and has an operating voltage of 480Y/277 VAC. It also provides a 65 kA max interrupt rating at 120 VAC. This device has a hold current of 1000A which is the maximum current the breaker can be held to ensure it will trip and a trip current of 2300A which is the current value when the breaker is guaranteed to trip. Many accessories are available for this breaker. This breaker was calibrated for 40 degrees C. HACR rated.
View AllClose