Schneider Electric EJB36045 Miniature Circuit Breaker 600V 45A

(No reviews yet) Write a Review
SKU:
EJB36045
UPC:
785901407041
Condition:
New
Height:
5.66 in
Circuit Breaker Application:
HACR rated
Product Certifications:
cULus
Number Of Spaces:
3
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Holding Current:
630 A
Rohs Exemption Information:
Yes
Electrical Connection:
lugs aluminium
Product Or Component Type:
circuit-breaker
Net Weight:
4 lb(US)
Trip Unit Rating:
1800-1800 A
[Ue] Rated Operational Voltage:
600Y/347 V AC
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Protection Type:
overload || short-circuit
Width:
2.94 in
Number Of Spaces Required:
3
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Range Of Product:
125 A Frame EDB-EGB-EJB
Mounting Mode:
bolt-on
Mercury Free:
Yes
Breaking Capacity:
25 kA 600Y/347 V AC
Depth:
4.05 in
Ambient Air Temperature For Operation:
40 °C
Awg Gauge:
AWG 12...AWG 2/0 aluminium || AWG 14...AWG 2/0 copper
Breaking Capacity Code:
J
Local Signalling:
trip indicator
Tightening Torque:
3.9-3.9 N.m 2.5-6 mm² (AWG 14...AWG 10) || 5.6-5.6 N.m 10-70 mm² (AWG 8...AWG 2/0)
Line Rated Current:
45 A
Module Type:
E-Frame
Warranty:
18 months
Number Of Poles:
3
Product Destination:
NF panelboard
Device Short Name:
EJB
Trip Unit Technology:
thermal-magnetic
Brochure:
View
Datasheet:
View
$2,713.50

Description

E-Frame Breaker are Lighting Panelboard Circuit breakers that are proven effective and reliable which provide a wide variety or robust features that are use specifically in Square D NF Panelboards. This range of breaker is ideally designed to offer superior overload and short circuit protection. All E-Frame breakers have a thermal-magnetic trip unit as well as signal indicator that will indicate when a trip has occur. Mounting bolts are used to hold these breakers in place. This E-Frame breaker is 45A, 3 pole, and has an operating voltage of 600Y/347 VAC. It also provides a 100 kA max interrupt rating at 120 VAC. This device has a hold current of 630A which is the maximum current the breaker can be held to ensure it will trip and a trip current of 1800A which is the current value when the breaker is guaranteed to trip. Many accessories are available for this breaker. This breaker was calibrated for 40 degrees C. This product is UL Listed as High Intensity Discharge. HACR rated.
View AllClose