Schneider Electric GV2P21 Tesys Motor Circuit Breaker

(No reviews yet) Write a Review
SKU:
GV2P21
UPC:
3.38911E+12
Condition:
New
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Ambient Air Temperature For Operation:
-20-60 °C
Operating Altitude:
6561.68 ft (2000 m)
Height:
89 mm
Range:
TeSys Deca
[Ics] Rated Service Short-Circuit Breaking Capacity:
100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 50 % 400/415 V AC 50/60 Hz IEC 60947-2 || 75 % 440 V AC 50/60 Hz IEC 60947-2 || 75 % 500 V AC 50/60 Hz IEC 60947-2 || 100 % 690 V AC 50/60 Hz IEC 60947-2
Network Frequency:
50/60 Hz IEC 60947-4-1
Phase Failure Sensitivity:
yes IEC 60947-4-1
Warranty:
18 months
California Proposition 65:
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Network Type:
AC
Line Rated Current:
23 A
Ip Degree Of Protection:
IP20 IEC 60529
Ik Degree Of Protection:
IK04
Tightening Torque:
1.7 N.m screw clamp terminal
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz IEC 60947-2
Standards:
EN/IEC 60947-2 || EN/IEC 60947-4-1
Electrical Durability:
100000 cycles AC-3 415 V In || 100000 cycles AC-3e 415 V In
Product Or Component Type:
motor circuit breaker
Device Short Name:
GV2P
Poles Description:
3P
Fire Resistance:
960 °C IEC 60695-2-11
Environmental Disclosure:
ENVPEP2211002
Depth:
97 mm
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-2
Device Application:
motor protection
Climatic Withstand:
IACS E10
Ambient Air Temperature For Storage:
-40-80 °C
Control Type:
rotary handle
[Ith] Conventional Free Air Thermal Current:
23 A IEC 60947-4-1
Motor Power Kw:
9-9 kW 400/415 V AC 50/60 Hz || 11-11 kW 500 V AC 50/60 Hz || 18.5-18.5 kW 690 V AC 50/60 Hz
Mechanical Robustness:
shocks 30 Gn for 11 ms || vibrations 5 Gn, 5...150 Hz
Width:
45 mm
Fixing Mode:
35 mm symmetrical DIN rail clipped || panel screwed with 2 x M4 screws)
Power Dissipation Per Pole:
2.5 W
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Product Name:
TeSys GV2 || TeSys Deca
Product Certifications:
CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || RINA || DNV-GL || UKCA
[Ui] Rated Insulation Voltage:
690 V AC 50/60 Hz IEC 60947-2
Circularity Profile:
ENVEOLI2211002
Utilisation Category:
category A IEC 60947-2 || AC-3 IEC 60947-4-1 || AC-3e IEC 60947-4-1
Thermal Protection Adjustment Range:
17-23 A IEC 60947-4-1
Suitability For Isolation:
yes IEC 60947-1 § 7-1-6
Eu Rohs Directive:
Compliant with Exemptions
Trip Unit Technology:
thermal-magnetic
Color:
dark grey
Breaking Capacity:
100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 20 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 10 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 4 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Magnetic Tripping Current:
327-327 A
Mechanical Durability:
100000 cycles
Rated Duty:
continuous IEC 60947-4-1
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Catalog:
View
Datasheet:
View
  • Schneider Electric GV2P21 Tesys Motor Circuit Breaker
  • Schneider Electric GV2P21 Tesys Motor Circuit Breaker
$278.00

Description

The GV2 manual starter and protector provides manual isolation, manual motor control, and thermal overcurrent protection in one compact unit. The basic motor starter GV2P controls motors with full load currents up to 32 A. The manual starter is three pole with horsepower ratings. The manual starter is operated by a rotary handle. The Class 10 ambient compensated thermal over current is adjustable from 17 ampere to 23 ampere. This device has screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
View AllClose