Schneider Electric GV3P736 Tesys Motor Cb Tho/Mag 62-73A Lugs

(No reviews yet) Write a Review
SKU:
GV3P736
UPC:
3606481304582
Condition:
New
Product Or Component Type:
motor circuit breaker
Phase Failure Sensitivity:
yes IEC 60947-4-1
Fire Resistance:
960 °C IEC 60695-2-11
Control Type:
rotary handle
Motor Power Kw:
37-37 kW 400/415 V AC 50/60 Hz || 45-45 kW 500 V AC 50/60 Hz || 55-55 kW 690 V AC 50/60 Hz
Ik Degree Of Protection:
IK09 enclosure
[Ue] Rated Operational Voltage:
690 V AC 50/60 Hz
Device Short Name:
GV3P
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Climatic Withstand:
IACS E10
Warranty:
18 months
Product Certifications:
CCC || UL || CSA || EAC || ATEX || LROS (Lloyds register of shipping) || BV || ABS || DNV-GL || UKCA
China Rohs Regulation:
Product out of China RoHS scope. Substance declaration for your information.
Mechanical Robustness:
shocks 5 Gn for 11 ms contactor open || shocks 30 Gn for 11 ms contactor closed || vibrations 4 Gn, 5...300 Hz
Width:
55 mm
Breaking Capacity:
65 kA Icu 230/240 V AC 50/60 Hz || 50 kA Icu 400/415 V AC 50/60 Hz || 50 kA Icu 440 V AC 50/60 Hz || 12 kA Icu 500 V AC 50/60 Hz || 6 kA Icu 690 V AC 50/60 Hz
Utilisation Category:
AC-3 IEC 60947-4-1
Connection Pitch:
17.5 mm without spreaders
Operating Altitude:
9842.52 ft (3000 m)
Range:
TeSys Deca
Ambient Air Temperature For Storage:
-40-80 °C
Height:
132 mm
[Uimp] Rated Impulse Withstand Voltage:
6 kV IEC 60947-2
Network Type:
AC
Ip Degree Of Protection:
IP20 IEC 60529
Environmental Disclosure:
ENVPEP060901
Power Dissipation Per Pole:
8 W
Tightening Torque:
6 N.m lugs-ring terminals
Trip Unit Technology:
thermal-magnetic
Product Name:
TeSys GV3 || TeSys Deca
Sustainable Offer Status:
Green Premium product
Thermal Protection Adjustment Range:
62-73 A IEC 60947-4-1
Poles Description:
3P
Network Frequency:
50/60 Hz
Color:
dark grey
[Ui] Rated Insulation Voltage:
690 V AC 50/60 Hz IEC 60947-2
[Ics] Rated Service Short-Circuit Breaking Capacity:
100 % 230/240 V AC 50/60 Hz || 60 % 400/415 V AC 50/60 Hz || 60 % 440 V AC 50/60 Hz || 50 % 500 V AC 50/60 Hz || 50 % 690 V AC 50/60 Hz
[Ith] Conventional Free Air Thermal Current:
73 A IEC 60947-4-1
Magnetic Tripping Current:
1120-1120 A
Line Rated Current:
73 A
Rohs Exemption Information:
Yes
Depth:
136 mm
Mechanical Durability:
50000 cycles
Electrical Durability:
20000 cycles AC-3 415 V In
Rated Duty:
continuous IEC 60947-4-1
Fixing Mode:
35 mm symmetrical DIN rail clipped || panel screwed with 3 x M4 screws)
Ambient Air Temperature For Operation:
-20-60 °C
Device Application:
motor protection
Eu Rohs Directive:
Compliant with Exemptions
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Suitability For Isolation:
yes IEC 60947-1
Net Weight:
0.96 kg
Circularity Profile:
ENVEOLI060901
Mercury Free:
Yes
Standards:
EN/IEC 60947-2 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Datasheet:
View
$555.00

Description

TeSys GV motor circuit breaker, 3 poles (3P), 73A/690V, for 3-phase motor applications 37kW@400V. It provides a thermal-magnetic protection with a thermal setting range 62-73A, magnetic tripping at 15xIn, high breaking capacity Icu 50kA@400V. Connection by bars or lugs. Start-stop control by rotary knob guaranteed for 20 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).
View AllClose